Change of function of DIP switch 8 and actions for customers
Identity-Number:
805038
page
6 of 8
Table 2: Overview of firmware functions
PROFIBUS-bus
terminal
till serial
number 37343
PROFIBUS-bus terminal
as of serial number 37344
PROFIBUS
DP/V0-Mode
DP/V1-Mode
Device entry
Typ 8644
Typ 8644
8644-DP
(DIP8=OFF)
ME02
8644-DPV1
(DIP8=ON) ME02
Name of GSD-file
BUER00F0.gsd
BUER00F0.gsd BUV100F0.gsd
BUER06BA.gsd
Old and new version of PROFIBUS-bus
terminal can be replaced
X
X
X
--
DP/V0 support
(cyclic communication)
184 byte for
process data,
maximum
184 byte of
process data,
maximum
184 byte for
process data,
maximum
176 byte of
process date,
maximum
PCP module operation
--
--
X
X
DP/V1 Read an DP/V1 Write support (acyclic
communication), Class 1 and Class 2 masters
--
--
--
X
Communication with PCP modules via „normal“
process data (DP/V0)
--
--
X
X
Parameterisation of several I/O´s via dialog
boxes in the configuration tool
--
--
--
X
Specification of safety values using the
configuration tool
--
--
--
X
Byte rotation for IB IL 24 DI 16 and IB IL 24 DO
16 for adaptation to the control system format
--
--
X
X
Byte rotation for IB IL 24 DI32 and IB IL 24 DO
32
--
--
New in
firmware B or
later
New in firmware
B or later
Acknowledgement of bus stops, either
automatically or via the application program
--
--
X
X
Acknowledgement at I/O errors, either
automatically or via the application program
--
--
X
X
Diagnostics in PROFIBUS-bus terminal
X
X
X
X
Diagnostics in identification format
--
--
--
X
Diagnostics as status PDU
--
--
--
X
Stop response can be set via DIP switches
X
--
--
--
Stop response can be set via parameter
telegram
--
--
X
(cp.
Figure 2
)
X
(cp.
Figure 1
)