32
Adjustment and functionalities
9.7.1. Commutation modes on the 8400
Two commutation modes on the transistor or relay are available:
-
hysteresis mode;
- window mode.
In hysteresis mode (see Fig. 24), the status of the transistor or
relay is changed:
-
on detection of the high threshold (O HI) when the measured
temperature increases
-
on detection of the low threshold (O LO) when the measured
temperature decreases.
Not inverted
Contact
T°
ON
OFF
OLO OHI
T°
Contact
Inverted
ON
OFF
OLO OHI
Fig. 24: Changing the output in hysteresis mode
In window mode, the status of the transistor or relay output
is changed whenever one of the thresholds is detected (see
Contact
Not inverted
T°
ON
OFF
OLO OHI
ON
OFF
OLO OHI
Contact
Inverted
T°
Fig. 25: Changing the output in window mode
The time delay before commutation (DEL) is valid for both output
thresholds. Commutation is done if one of the thresholds (O HI,
O LO) is exceeded for a period longer than the time delay prior to
commutation, DEL (see Fig. 26).