Technical data
Type 8098
6.6
Electrical data
0
10
20
30
40
50
60
70
80
-20
0
20
40
60
80
100
120
140
160
-10
-20
5
10
15
20
25
30
35
Fluid temperature °C
Ambient temperature °C
Supply voltage V DC
Voltage not allowed
Temperature authorized for a limited duration
Figure 8:
Minimum supply voltage depending on the ambient temperature and the fluid temperature
Connections Circular plug-in connector
without outputs M12 x 1, 5-pin
with outputs (2x AO/DO) M12 x 1, 8-pin
Operating voltage 12 – 35 V DC ±10%
The minimum supply voltage depends on the fluid temperature and the ambient
operating temperature: depending on the variant of the device, see
Filtered and regulated
Safety Extra-Low Voltage circuit (SELV circuit)
Limited Power Source (LPS) according to standards UL/EN 60950-1 or through
a limited-energy circuit according to standards UL/EN 61010-1
Current consumption max. 1 A
Power consumption
without outputs
≤
2.5 W
with outputs (2x AO/DO)
≤
5 W
Polarity reversal Protected
Outputs (variant) Configurable as digital output or analogue output
Analog output 4 – 20 mA current
3.6 mA or 22 mA to indicate an error
Uncertainty: ±0.04 mA
Resolution: 0.8 μA
Open loop detection (diagnostics software function)
Sink or source mode
Galvanically isolated, passive
Protected against polarity reversal
Maximum loop impedance 1300 W at 35 V DC, 1000 W at 30 V DC, 700 W at
24 V DC, 450 W at 18 V DC
English