11
Specific conditions of use
6.3
Operating conditions
The valve provides a cooling function for the solenoid coil. The
solenoid coil may not be operated without a valve. The valve
body must meet the following requirements:
• Material
Metal (brass, aluminium, stainless steel) or polyamide
• Minimum dimensions
32 mm x 32 mm x 10 mm
A larger valve body with a higher heat-dissipating capability can
be used at any time.
The solenoid coils designed for individual installation may not be
used for block assembly.
The solenoid coils designed for block assembly are suitable for
both block assembly and for individual installation.
6.4
Operating temperature range
Observe the operating temperature range specified in the electrical
data for all valve types.
6.5
Supply connection for solenoid coil
with terminal box
For connections, use wires suitable for at least +90 °C (+194 °F).
7
TECHNICAL DATA
7.1
Safety instructions
DANGER!
Risk of explosion.
Dangerous situations can result if the technical safety data and
values specified on the type label aren’t observed or cannot be
met.
▶
The degree of protection and temperature class for use of
the device must be observed.
Exceeding the voltage specified on the type label creates a safety
hazard since it can lead to overheating of the device!
▶
Don’t connect the device to a higher voltage than that speci-
fied on the type label.