LED Colour Assignments
21
LED COLOUR ASSIGNMENTS
The switching statuses of the process valves as well as the device statuses are signalled to the outside via
the central multi-colour status display (device status LED / Top LED), so that quick visual control is possible
also for large systems.
Colours and flashing patterns have been assigned to the signals of the process valve positions and device
statuses – see chapter
“21.1.1 Device specific LED mode “8681 Classic Mode””
fault signalling”. When several signals are overlapped, a priority list applies (“21.3 Signal priorities”).
In order to be able to react to various process valve designs or customer signalling philosophies in the systems,
the colour assignments can be changed on site using the
DIP switches for colour coding
(
see chapter “21.1.1
Device specific LED mode “8681 Classic Mode””
– except for the IO-Link version, which does not have DIP
switches).
For the büS/CANopen and IO-Link variants,
the colours can alternatively be assigned using the Bürkert
Communicator.
With the DeviceNet, büS/CANopen and IO-Link variants,
changes to settings can also be
carried out via the actual bus-specific communication interface; in this case, no settings on the electronic
module are required and, as such, the cover can remain closed.
Factory setting DIP 1 - 4: 0000
– i.e.
DIP1 to 4 in position 0 = OFF
(relates to variants 24 V DC, 120 V AC, AS-i, DeviceNet)
Factory setting DIP 1 - 5: 111110
– i.e.
DIP1 to 5 in position 1 = ON,
DIP 6
= Pos. 0 = OFF
(relates to variant büS/CANopen -
see following chapter
When using the control head in a potentially explosive atmosphere,
the housing may only be
opened in a not energised
state.
8 DIP switches
for setting the
baudrate
and address
(for DeviceNet
and büS/
CANopen only)
4 DIP switches
for colour coding
Position ON = 1
Position OFF = 0
Electronic module büS/CANopen
Electronic module ASI
Fig. 48:
DIP switches for setting the colour coding (in the example of the electronic modules büS/CANopen and AS-i)
21.1
Display modi – overview
The switching status and position feedback (S1, S2, S3, S4IN) of the process valve described above as well
as error and warning messages are displayed differently in the various variants due to the varying design of
the top LED.
With Type 8681 büS/CANopen and IO-Link, further display modes and colour combinations can be selected,