26
Technical Data
electronic base module Me03 / 3-fold 10 mm monostable,
6.5.5.
Me03 / 4-fold monostable
technical data
Me03 / 3-fold
10 mm monostable
Me03 / 4-fold
monostable
Dimensions BxHxT
33 x 93 x 60 mm
66 x 93 x 60 mm
Weight
51 g
91.2 g
Storage temperature
-20 ... +60° C
-20 ... +60° C
Nominal load voltage
DC 24 V
DC 24 V
Number of valve outputs
3
4
Power consumption per valve location during
switching
43 mA
85 mA
Power consumption per valve location after
approx. 65 ms (for ME03 / 4-fold monostable after
approx. 400 ms)
28 mA
52 mA
Power consumption from the backplane bus
max. 15 mA
max. 15 mA
Display of the valve status
1 yellow LED per valve
location
1 yellow LED per valve
location
Power loss of the module at the point of switching
3 W
8 W
Power loss of the module 65 ms after the switching
process (3 x 0.25 W power loss on resistors, 3 x 0.25
W on valve coils)
1.5 W
-
Power loss of the module 400 ms after the switching
process (4 x 0.5 W power loss on resistors, 4 x 0.5 W
on valve coils)
-
4 W
Typ 8644