Plus-X 300 Installation and Operation Manual Rev C 

 

Next, define the behavior for each of eight relay outputs. 
Each relay may be set for momentary or latching output. 
Check the 

Pair Relay Channels

 box in order for the relays 

to act as mutually exclusive pairs. When this box is 
checked, a command to one relay will cause the second 
relay to de-energize.  

Note: When the Pair Relay Channels box is checked, it is 
recommended to configure the two paired relays with the same behavior (Latching / Latching or 
Momentary / Momentary). If one relay is configured as Latching and the other as Momentary, a 
command to the momentary relay will de-energize the latching relay. After the momentary 
command is finished, both relays will remain de-energized until a new command is issued to 
one of the relays.  

Security 

 
Navigate to the Security page to set the 
password for the Plus-X 300. This password is 
used only to access the Plus-X configuration 
screens. ARC Plus user names and passwords 
are set up using AutoLoad Plus software.  

The Plus-X 300 user name is always 

admin

  

Adding Plus-X Channels to the ARC Plus 

 
Now that you have configured the input and output channels on the Plus-X 300, these channels 
may be added to the ARC Plus site using AutoLoad Plus. To add Plus-X 300 channels to the 
ARC Plus: 

1.  Launch AutoLoad Plus and connect to the ARC Plus site to which the Plus-X 300 is 

linked.  

2.  From the 

Edit 

menu, select 

Plus-

X Devices…

and click 

New.

 

3.  When the Plus-X Settings window appears, select Plus-X 300 from the device type drop-

down. Enter a description of the Plus-X 300 for your own reference, followed by the IP 
address and Plus-X port, both of which are already configured on the Plus-X 300.  

4.  Check the box marked 

Map Default Set of Channels

 to add all eight inputs and eight 

relays to the ARC Plus. If you are not using all Plus-X 300 channels or if you do not wish 
for them to appear in sequential order, you will need to manually map these channels 
later. In this case, leave the 

Map Default Set of Channels

 box unchecked.  

5.  Press 

OK

 to close the Plus-X Settings window. Press 

OK

 to close the Plus-X Devices 

window.  

6.  To manually map Plus-X 300 channels to the ARC Plus, click the Metering, Status or 

Commands tabs, as appropriate. Locate an unused channel and clic

k the […] button in 

the Source column. This will bring up the Source dialog box. Click the 

Plus-X

 button and 

choose the Plus-X 300 channel you wish to use. At least one meter channel and one 

Содержание Plus-X 300

Страница 1: ...Plus X 300 Installation and Operation Manual ...

Страница 2: ...ight 2017 Burk Technology Inc Rev C Table of Contents Introduction 1 Compatibility 1 Installation 1 Configuration 2 Uploading New Firmware 5 Operation 5 Getting Help 6 Warranty 6 Appendix A Specifications 7 ...

Страница 3: ...e current Updates are available at www burk com downloads The following are minimum software and firmware requirements Software Version ARC Plus firmware 2 0 or higher AutoLoad Plus software 2 0 or higher AutoPilot software 2 6 or higher Installation The Plus X 300 ships with the following parts which are required for installation 1 Ethernet cable 1 15V wall adapter 1 2 pin Phoenix type connector ...

Страница 4: ...ower connector to the rear panel input marked POWER The power connector is pre wired to the 15V wall adapter Plug the power adapter into a standard 120V outlet The POWER LED will illuminate Finally connect the included Ethernet cable to your network switch Important The Plus X 300 must be addressable by the ARC Plus to which it will communicate Consult your IT department prior to configuration to ...

Страница 5: ...for up to eight status channels as well as relay behavior for each of eight relay outputs In the Status Thresholds table enter the input values that will trigger status changes from low to high and vice versa The Lower threshold is the value below which a voltage sample must decrease in order to change the status from high to low The Upper threshold is the value above which a voltage sample must i...

Страница 6: ...d the input and output channels on the Plus X 300 these channels may be added to the ARC Plus site using AutoLoad Plus To add Plus X 300 channels to the ARC Plus 1 Launch AutoLoad Plus and connect to the ARC Plus site to which the Plus X 300 is linked 2 From the Edit menu select Plus X Devices and click New 3 When the Plus X Settings window appears select Plus X 300 from the device type drop down ...

Страница 7: ... password and revert the IP address to 192 168 0 100 Uploading New Firmware After logging into the Plus X 300 web interface edit the URL in your web browser to address upload where address is the IP address assigned to the Plus X 300 This will take you to the upload page Click the Choose File button to select the firmware file then click Upload to load the new firmware The Plus X 300 will reboot a...

Страница 8: ...chnical support please email support burk com or call our direct technical support line at 978 486 3711 We will be glad to assist you The technical support office is open Monday Friday 9AM to 5PM Eastern time Warranty Burk Technology Inc warrants the Plus X 600 to be free of defects in materials and workmanship for a period of 24 months from the date of purchase Equipment will be repaired or repla...

Страница 9: ...g Power Requirements 15VDC at 0 5A power adapter included Metering Inputs 0 to 10VDC 10mV resolution Status Inputs 0 to 28VDC or switch closure Relay Outputs 5A 240VAC form C relay outputs C NO NC each user configurable for momentary or lacthing output Hysteresis User configurable set points per input channel Mounting Keyhole slots for surface mounting Available RMA300 rack mount adapter ...

Отзывы: