TROUBLESHOOTING (cont.)
PROBLEM
PROBABLE CAUSE
REMEDY
Nothing Flowing from Nozzles
Product Pouring Too Warm and/or
Inside Cabinet Too Warm
1. Dispense switch is OFF.
2. Gas, coffee, and water not
connected.
1. System has not reached tem-
perature (ice bank not fully
formed).
2. BIB or caddy is ambient temp
and needs to cool down.
3. Water bath pump not running.
1. Turn Dispense switch ON.
2. Assure all required connec-
tions are made according to
set-up instructions before op-
erating the system.
1. Wait until system is fully
cooled and ice bank fully
formed. Check Compressor
switch is set to ON and sight
gauge shows full water bath. If
water bath sight gauge is low,
press Dispense switch to OFF.
Wait a few seconds. Press Dis-
pense switch to ON. Bath will
automatically start filling water
bath after 30 seconds.
2. Best practice is to use a chilled
BIB or caddy for proper ni-
trogenation. If using ambient
concentrates, chill BIB or cad-
dy first prior to using.
3. Confirm the compressor/water
bath pump switched is turned
ON. Confirm the water bath
pump and compressor are
running.