BULLDOG HEAT PUMP Vertical Stacked – Installation Manual
4
© Copyright 2017 CGC Group of Companies, Inc. Installation Manual is Subject to Change without Notice - Last Revised Aug 15, 2017
LOCATION
1.
Determine cabinet location using the optional manufacturer-supplied
template.
2.
Locate core holes for risers using supplied template.
3.
Locate the unit in an indoor area. The ambient temperature
surrounding the unit must not be less than 45
°
F (7
°
C). Do not
locate the unit in areas that may be subjected to freezing
temperatures.
CABINET PLACEMENT
1.
Review the riser schedule to identify cabinet type and location.
2.
Position the cabinet. Shim to make cabinet level, then anchor
the cabinet with concrete bolts to floor (See Figure 3). If
installing a base extension, bolt the extension to the concrete
floor (See Figure 5).
3.
The riser knockout to be left exposed for riser installation.
Figure 3
Figure 4
Figure 2