Getting Started With Your System
15
Environmental
Temperature
Operating
10° to 35°C (50° to 95°F) with a maximum
temperature gradation of 10°C per hour
NOTE:
For altitudes above 2950 feet, the
maximum operating temperature is derated 1ºF/550
ft.
Storage
–40° to 65°C (–40° to 149°F) with a maximum
temperature gradation of 20°C per hour
Relative humidity
Operating
20% to 80% (noncondensing) with a maximum
humidity gradation of 10% per hour
Storage
5% to 95% (noncondensing) with a maximum
humidity gradation of 10% per hour
Maximum vibration
Operating
0.26 Grms at 5–350 Hz for 15 min
Storage
1.54 Grms at 10–250 Hz for 15 min
Altitude
Operating
–16 to 3,048 m (–50 to 10,000 ft)
NOTE:
For altitudes above 2950 feet, the
maximum operating temperature is derated 1ºF/550
ft.
Storage
–16 to 10,600 m (–50 to 35,000 ft)
Airborne Contaminant Level
Class
G2 or lower as defined by ISA-S71.04-1985
book.book Page 15 Tuesday, June 8, 2010 9:51 AM