TC-Standard (+) X2
Moisture detector: error cleared automatically after cable break
Display →
toP
→
bLtc
(
bLtc
= broken wire latch). The setting applies to all connected moisture detectors.
Determines whether the cable break alarm must be reset manually or will automatically clear on
valid measuring signal.
Parameter range:
YES
: The status will be indicated until the user restarts the device/clears the error, and the pumps
will be disabled.
no
: The error message will extinguish/the pumps will be released again once the moisture detector
is recognised again.
Factory setting:
YES
Note:
This menu will be hidden if the menu is locked.
Lock Menu
To protect the menu from unauthorised use, enter a value for the lock code. Menu items can then only be accessed after enter-
ing the correct code.
Display →
toP
→
Loc
This setting will cancel/enable the menu lock.
Parameter range:
0 to 9999
Factory setting:
0 (keylock cancelled)
Note:
This menu will be hidden if the menu is locked.
Restart
Display →
toP
→
rESt
(
rESt
= restart)
The device will restart, all settings are saved. All error messages will be reset.
The moisture detector will be reset, irrespective of the settings in menus
h.Itc
and
h.Moi
.
Parameter range:
YES
: Restart. The display will show the software version for the device and returns to measurement
display.
no
: Exit menu without restarting.
Note:
The user settings will be saved.
Factory settings
Display →
toP
→
rst
This setting restores the factory settings.
Parameter range:
Yes
: factory settings restored.
No
: Exit menu without making changes.
Factory setting:
No
Note:
This menu will be hidden if the menu is locked.
Exit submenu 1
Display → Submenu →
E
Selecting this will return you to the main menu.