TF with IO-Link
4 Installation and connection
4.1 Installation
The temperature sensor comes fully assembled and can be mounted to the tank with a screw fitting and seal. Please be sure to
leave enough space between the tank wall and add-ons. The maximum torque of the screw-in thread is 25 Nm. When installing,
be sure the sealing face is clean and even. Only screw the temperature sensor into the designated thread. Sealed with an elastic
sealing ring. No other sealants required.
4.2 Electrical Connections
Electricity is supplied via plug connectors. Please refer to the appendix for installation dimensions, nominal voltage and plug
configuration. The switching outputs are PNP transistors. The level- and temperature sensor is powered with 18 - 30 V direct
voltage. The sensor connects with a cable and standard M12 plug-in connectors.
6
Bühler Technologies GmbH
BE140016 ◦ 09/2020