5.2.2
Installing a safety valve (on-site)
▶ Install a type-tested safety valve that is approved for potable water
(
DN 20) in the cold water supply (
▶ Observe the safety valve installation instructions.
▶ Terminate the discharge pipe where it will be easily visible in the
frost-protected area above a drain.
– The discharge pipe must be at least equal to the outlet cross-
section of the safety valve.
– The discharge pipe must be able to discharge at least the flow rate
that is feasible at the cold water inlet (
Table 4, page 36).
▶ Attach a notice with the following text to the safety valve: "Never
close the discharge pipe. During heating, water may be discharged
for operational reasons."
If the static system pressure exceeds 80 % of the safety valve response
pressure:
▶ Install a pressure reducer upstream (
5.3
Installing the DHW temperature sensor
Fit one DHW temperature sensor respectively at test port [7] (for the
solar thermal system) and [3] (for the heat source) for capturing and
monitoring the DHW temperature at the DHW cylinder
(
▶ Install the DHW temperature sensor (
Fig. 11, page 56). Ensure
that the sensor area has contact with the sensor well surface area
over its full length.
5.4
Immersion heater (accessory)
▶ Install the immersion heater in accordance with the separate
installation instructions.
▶ When installation of the cylinder is complete, inspect the earth
conductor (including metal connection fittings).
6
Commissioning
▶ Commission all assemblies and accessories as specified in the
manufacturer's technical documentation.
6.1
Commissioning the DHW cylinder
On the DHW side, the test pressure must not exceed 10 bar (150 psi)
positive pressure.
▶ Flush the DHW cylinder and pipework thoroughly prior to
commissioning (
6.2
Instructing users
▶ Explain the operation and handling of the heating system and
cylinder, making a particular point of safety-relevant features.
▶ Explain the function and how to check the pressure relief valve.
▶ Hand all enclosed documents over to the user.
▶
Recommendation for the operator:
Conclude a maintenance and
inspection contract with an approved contractor. Have the cylinder
serviced and inspected annually at the specified maintenance
intervals (
Table 8, page 39).
Highlight the following for the user:
▶ Setting the DHW temperature.
– Water may be discharged from the pressure relief valve when
heating-up.
– Always keep discharge pipe for pressure-relief valve open.
– Comply with maintenance intervals (
–
Where there is a risk of frost and when the operator is briefly
away:
Keep the heating system in operation and set the lowest
possible DHW temperature.
7
Shutting down
▶ If an immersion heater has been fitted (accessory), isolate the DHW
cylinder from the power supply (
▶ Switch off the temperature controller at the control unit.
▶ Drain the DHW cylinder (
▶ Decommission all assemblies and accessories of the heating system
as specified in the manufacturer's technical documentation.
▶ Close the shut-off valves (
▶ Depressurize the indirect coils.
▶ Drain and blow out the indirect coils (
▶ To prevent corrosion, dry out the interior and keep the inspection
aperture covers open.
Mains pressure
(static pressure)
Safety valve
response pressure
Pressure reducer
in the EU
outside the EU
< 4.8 bar
6 bar
Not required
5 bar
6 bar
max. 4.8 bar
5 bar
8 bar
Not required
6 bar
8 bar
max. 5.0 bar
Not required
7.8 bar
10 bar
max. 5.0 bar
Not required
Table 7 Selection of a suitable pressure reducer
NOTICE:
Risk of system damage through excessive
pressure!
Excessive pressure can result in tension cracks in the
enamel coating.
▶ Never close the blow-off line of the safety valve.
Check the DHW cylinder for leaks using potable water
only.
WARNING:
Risk of scalding at the hot water draw-off
points!
Depending on the system and operating conditions
(thermal disinfection) there is a risk of scalding at the
DHW draw-off points in DHW mode.
Installation of a thermal mixer is prescribed when setting
a DHW temperature via 60 °C.
▶ Advise users that they should draw off only mixed
water.
WARNING:
Scalding from hot water!
▶ Let the DHW cylinder cool down sufficiently.
Содержание SU300.5
Страница 60: ...9 SU300 5 SU400 5 6 720 819 326 2019 12 60 26 27 6 720 647 567 15 1ITL 6 720 647 567 16 1ITL 1 1 2 3 ...
Страница 61: ...9 SU300 5 SU400 5 6 720 819 326 2019 12 61 ...
Страница 62: ...9 SU300 5 SU400 5 6 720 819 326 2019 12 62 ...
Страница 63: ...9 SU300 5 SU400 5 6 720 819 326 2019 12 63 ...
Страница 64: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www buderus com ...