6 720 808 905 (2014/04)
MP100
8 |
Product details
▶ The product requires different voltages.
Do not connect the extra-low voltage side to the mains
voltage or vice versa.
▶ Also observe connection diagrams of other system
components.
Handover to the end user
When handing over the heating system, explain the operating
conditions to the user.
▶ Explain how to operate the heating system, with particular
emphasis on all safety-related actions.
▶ Explain that conversions or maintenance must only be
carried out by a competent person.
▶ Point out the need for inspections and maintenance for
safe and environmentally friendly operation.
▶ The installation and operating instructions must be given to
the end user for keeping.
Damage caused by frost
The system can freeze if it is switched off:
▶ Observe the notices regarding frost protection.
▶ Due to the additional functions, e.g. DHW heating or anti-
seizing protection, the system should always be left on.
▶ Correct any faults immediately.
2
Product details
•
The module serves to activate a swimming pool connected
to a heat pump with a EMS plus interface.
•
The module serves to determine the swimming pool
temperature and activate a mixer as required by the heat
pump.
•
Anti-seizing function: the connected mixing valve actuator
is monitored and run automatically for a short period after
24 hours of downtime. This prevents the mixer from
seizing up.
A maximum of one MP100 is permitted in a system,
irrespective of the number of other BUS nodes.
2.1
Standard delivery
[1] Module
[2] Bag with installation accessories
[3] Swimming pool temperature sensor TC1 installation set
[4] Installation instructions
2.2
Technical data
Design and operation of this product conform to
European Directives and the supplementary
national requirements. Its conformity is
demonstrated by the CE marking .
Technical data
Measurements
(W × H × D)
151 × 184 × 61 mm (further
dimensions
Maximum conductor
cross-section
•
230 V terminal
•
Extra-low voltage
terminal
•
2.5 mm
2
•
1.5 mm
2
Rated voltages
•
BUS
•
Module power supply
•
User interface
•
Mixer
•
15 V DC (reverse-polarity-
protected)
•
230 V AC, 50 Hz
•
15 V DC (reverse-polarity-
protected)
•
230 V AC, 50 Hz
Circuit breaker
230 V, 5 AT
BUS interface
EMS plus
Power consumption on
– standby
< 1 W
Maximum output
•
Per connection
(VC1)
•
100 W
Temperature sensor
capturing range
•
lower fault limit
•
display range
•
upper fault limit
•
< – 10 °C
•
0 ... 100 °C
•
> 125 °C
Permissible ambient
temperature
0 ... 60 °C
IP rating
•
For installation in
heat source
•
For wall-mounted
installation
•
Determined by the IP rating of
the heat appliance
•
IP 44
Protection class
I
ID no.
Data plate (
Table 2