22
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Heating system start-up
6
6.1.6 Checking the system equipment
The burner is factory-set for natural gas H (Table 11).
Country
Gas type
Factory settings
AT, BA, BE, BG, BR, BY,
CH, CN, CZ, DE, DK, EE,
ES, FI, FR, GB, GR, HR,
HU, IE, IT, LU, PL, PT, RO,
RU, SE, SI, SK, TR, UA
Natural gas H
(G20)
GZ 50
Factory-set ready for use.
The pressure regulator is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
Adjusted to 14.1 kWh/m
3
Applicable for 11.4 to 15.2 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
Adjusted to 14.9 kWh/m
3
Applicable for 12.0 to 16.1 kWh/m
3
DE, NL
Natural gas L
(G25)
After conversion (see Chapter 9 "Converting the boiler to a different gas
type", page 48) suitable for natural gas L.
Wobbe index for 15 °C, 1013 mbar:
Adjusted to 11.5 kWh/m
3
Applicable for 9.5 to 12.4 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
Adjusted to 12.2 kWh/m
3
Applicable for 10.0 to 13.1 kWh/m
3
HU
Natural gas S
(G25.1)
After conversion (see Chapter 9 "Converting the boiler to a different gas
type", page 48) suitable for natural gas S.
Wobbe index for 15 °C, 1013 mbar:
Adjusted to 10.9 kWh/m
3
Applicable for 10.1 to 11.6 kWh/m
3
Wobbe index for 0 °C, 1013 mbar:
Adjusted to 11.5 kWh/m
3
Applicable for 10.7 to 12.2 kWh/m
3
AT, BY, CH, CN, CZ, DE,
ES, FR, GB, HU, HR, IE,
LU, NL, PL, PT, RO, RU,
SI, SK, TR, UA
LPG
Propane
P (G31)
After conversion (see Chapter 9 "Converting the boiler to a different gas
type", page 48) suitable for propane.
BA, BG, GR, HR, LU
LPG B/P
(G30)
After conversion (see Chapter 9 "Converting the boiler to a different gas
type", page 48) suitable for butane, propane and mixtures thereof.
Tab. 11 Burner factory settings