Instructions for High Altitude Conversion

9

We reserve the right to make any changes due to technical modifications!

Instructions for High Altitude Conversion for Sealed Combustion Gas Boiler  GA244 • Issue 02/2004

Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de

10.

Check manifold pressure.  Set the manifold pressure 
according to the values in Table 3.  To adjust the 
manifold pressure (Fig. 8, 

Pos. 5

) remove the 

capscrew from the gas control.  Turn the pressure 
regulating adjusting screw clockwise to increase, or 
counterclockwise to decrease the manifold 
pressure.  This adjustment must be made while the 
boiler is in operation.

11.

After adjustment, record pressure in the start-up 
procedure, and install the capscrew on the gas 
control (Fig. 8, 

Pos. 5

).

12.

Observe the pilot flame (Fig. 9, 

Pos. 2

) through 

viewing port (Fig. 7, 

Pos. 1

) in the burner cover 

plate.  The flame should envelop the flame sensor ½ 
- 1-½ inch, see (Fig. 9, 

Pos. 1

). If the pilot flame is 

satisfactory then go to step 13.  If the pilot flame is 
too small or too large, adjust the pilot using pilot 
adjustment.  Turn the inner adjustment screw 
(Fig. 8, 

Pos. 4

) clockwise to decrease, or 

counterclockwise to increase the pilot flame. After 
adjustment, replace the cover screw and tighten 
firmly (Fig. 8, 

Pos. 4

). 

13.

Observe the main burner flame (Fig. 10, 

Pos. 1

through the viewing port (Fig. 7, 

Pos.

1) in the 

burner cover plate.  The flame should have a 
smooth, firm contour and must be mostly blue in 
color.  If the main flame is satisfactory, go to step 14.  
If the main burner flame is lazy, yellow, or lifting off 
the burners, turn the gas control knob (Fig. 8, 

Pos. 1

) clockwise to “OFF“. Shut off the main gas 

piping shutoff valve.  Disconnect all electric power to 
the appliance and call your service technician or gas 
supplier.

14.

The ignition safety shut-off must be tested.  Test the 
safety shut-off by shutting off the main gas piping 
shut-off valve.
The main burner and pilot flame (Fig. 9, 

Pos. 2

) will 

extinguish. Within six (6) seconds the gas control 
main gas solenoid should close and make an 
audible sound.  The ignition will spark.
After 90 seconds, the module should go into lock out 
mode and the spark should stop.  Disconnect the 
electric power to the appliance.  Open the main gas 
shutoff valve.  Turn on the electric power to the unit.  
A normal operating sequence should occur.  If the 
gas control functions satisfactorily then go to step 
15.  If the gas control does not function satisfactorily, 
immediately turn the gas control knob (Fig. 11, 

Pos. 1

) clockwise to "OFF".  

GA244

Natural gas

[inch W.C.]

Propane

[inch W.C.]

37

3.77

8.03

44

3.65

7.63

53

3.73

8.11

62

3.77

6.15

Table. 3  Required manifold pressure

Fig. 9

Proper pilot flame

Item. 1:

1/2“ to1 1/2“

Item. 2:

Flame

1

2

Fig. 10

Main burner

Item. 1:

Main burner flame

1

Содержание Logano GA244-37

Страница 1: ...n kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction and in accordan...

Страница 2: ...rsion data plate to be filled out and affixed to the appliance Conversion instructions Technical documents WARNING DANGER Denotes a possible severely dangerous situation where without proper caution b...

Страница 3: ...Turn off all electric power to the appliance and set the thermostat to its lowest setting 3 Remove jacket panel screws Fig 1 Pos 1 from left and right side tilt forward top of the front panel Fig 1 Po...

Страница 4: ...4 Pos 2 and remove this cover plate Fig 4 Pos 2 Fig 3 Gas control valve Item 1 Gas control valve knob set to ON 1 WARNING DANGER For explosion due to gas z Wait five 5 minutes to clear out any gas Th...

Страница 5: ...If the boiler has not been placed in operation follow the installation instructions in GA244 Installation Operation and Maintenance Manual supplied with the boiler If the boiler has been in operation...

Страница 6: ...g 6 Pos 3 from the gas control Install a test fitting and hook up a manometer to measure the manifold pressure 14 Open the main gas piping shut off valve and measure the supply pressure of the boiler...

Страница 7: ...air it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service...

Страница 8: ...the pilot The pilot should light and then the main burners should light If the main burners do not light shut off the main gas piping shutoff valve Shut off all electric power to the appliance and ca...

Страница 9: ...main burner flame Fig 10 Pos 1 through the viewing port Fig 7 Pos 1 in the burner cover plate The flame should have a smooth firm contour and must be mostly blue in color If the main flame is satisfa...

Страница 10: ...ifold pressure tabs in the gas control and replace the plugs 19 Repeat steps 1 to 6 and 13 to place the appliance back in operation Check the plugs in the gas control with a soap and water solution If...

Страница 11: ...rve the right to make any changes due to technical modifications Instructions for High Altitude Conversion for Sealed Combustion Gas Boiler GA244 Issue 04 2004 Buderus Heiztechnik GmbH http www heizte...

Страница 12: ...entworth Avenue Londonderry NH 03053 Tel 603 552 1100 Fax 603 421 2719 www buderus net Buderus Hydronic Systems reserves the right to make changes without notice due to continuing engineering and tech...

Отзывы: