12
Installation and maintenance instructions Logano G124X II/SP special gas-fired boiler • Issue 04/2005
We reserve the right to make any changes due to technical modifications.
Placing the boiler
6
6
Placing the boiler
This chapter explains how to place the boiler and
position it in the boiler room.
The boiler is very heavy when full. Check that the floor
can bear the weight before installation.
6.1
Clearances
A space of at least 33 inches is required in front of the
boiler with the door open to allow sufficient access
space for operation and maintenance. When the door is
closed, a minimum clearance of 2 inches is required at
the front and sides, 2 inches clearance is also required
for the flue pipe and 30 inches clearance to the ceiling.
The installation location and the base must be smooth
and horizontal. The boiler may be installed on a
flammable base, but not on carpet.
6.2
Leveling the boiler
z
Screw the four rubber feet 0.25 to 1.0 inches into the
bottom rails.
z
Place boiler on the feet.
z
Level boiler horizontally and vertically by screwing
the feet in and out.
CAUTION!
SYSTEM DAMAGE
through frost.
z
Place the boiler in a frost-free room.
Fig. 8
Required clearances in the boiler room
1
Door closed
2
Door open
3
Flue pipe
min.
2"
min. 2"
min.
2"
1
2
33"
min.
6"
3
Fig. 9
Unscrewing screw-in feet