Commissioning the heating system
5
Logamax plus GB162-65/80/100 - Subject to modifications resulting from technical improvements!
17
5.2.3 Frost protection
The boiler has an integrated frost protection system.
This means that no further frost protection facilities
should be installed on the boiler.
The frost protection switches on the boiler at a CH
(boiler) flow temperature of 7 °C and switches it off at a
CH (boiler) flow temperature of 15 °C.
The heating system is not protected against frost.
5.2.4 Setting the room controller
Make the settings on the room controller (e. g. RC35,
fig. 18). We advise you to check and/or set the
following:
– automatic operation mode
– required room temperature
– required DHW temperature
– required heating programme.
fig. 18
RC35 room controller
The user manual of the room controller
(e. g. RC35) describes how to make these
settings and which benefits they will bring.
You should read and observe the
instructions in the room controller user
manual.