Technical service bulletin

Logamatic R2107 Quick Start Guide

Bulletin Number: TBG-21 | Model: Logamatic R2107 Controls

Introduction

This bulletin is intended to address basic applications for the 

Logamatic R2107. For more advanced applications and 

functionality, please refer to the Logamatic R2107 Operating 

Instructions, Installation and Service Instructions and Applications 

Manual.

Procedure - Level 1 - Basic Settings

•  To set day:

       

Hold 

1...7

 and turn dial 

 until proper day is selected. 

•  To set time:

 Hold 

 and turn dial 

 clockwise until proper time 

      is selected.

•  To set Warm Weather Shutdown (WWSD) temp:

Hold 

 and turn dial 

 to appropriate 

     temperature.

•  For 24 hour Domestic Hot Water:

Hold 

 and turn dial 

 until "

DHW PROD

" appears.

     Release 

 and then press 

.  Then re-hold 

 and 

     turn the dial back to “

CIRCUIT 1”

.

   

When using hydro-air systems, you must also change  

             day/night temp.

•  To change day temp:

 Hold 

 and turn dial 

 clockwise to 

86° F

.

•  To change night temp:

 Push 

 then hold 

 and turn dial 

 clockwise  

to 

84° F

.

Procedure - Level 2 - Programming Settings

Hold together  

1...7

,  

,  

  then release.

Turn dial 

 five clicks clockwise.  This brings you to 

BLR TEMP

”.

Then push 

  and turn the dial 

 appropriately to 

reach the settings below:

FREEZE TEMP

 - 41°F (default)

BUILDING RESP

 - Change from default (2) to (1) for wood frame 

 construction

PUMP LOGIC

 - 104° F (default)

MAX TEMP

 - Must change to 194°F

•  To change BUILDING RESP:

 While on the 

BUILDING RESP

 setting, hold 

 and turn 

dial 

 counter-clockwise.

•  To change MAX TEMP:

 While on the 

MAX TEMP

 setting, hold 

 and turn 

dial 

 clockwise to 194° F.

Push  

  then turn dial 

 clockwise once to 

CIRCUIT 1

”.

Then push 

  and turn the dial 

 appropriately to 

reach the following settings on the next page: