DHW data
12
Logamatic 4323 - Subject to technical modifications.
87
12.12 Set the time of day for thermal disinfection
You can set the time of day when thermal disinfection should be carried out via
the "Time Therm. disinfect" function.
.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "DHW" appears.
Press "Display" to call up a submenu (here: "DHW").
The display shows the selected submenu.
Turn the rotary selector until submenu "time Therm. disinfect" appears.
The display shows the selected submenu.
Hold down "Display" and turn the rotary selector until the required value appears
(here: "18:00").
The display shows the set value.
Release "Display" to save your input.
Press "Back" to return to the next level up.
USER INFORMATION
The "Time Therm. disinfect" function is not displayed if thermal disinfection
was previously set using the "External contact WF 1/3" function.
+
+
DHW DATA
yes
DHW
DHW DATA
01:00
Therm. disinfect
time
+
DHW DATA
18:00
Therm. disinfect
time
Input range
Factory setting
Thermal disinfection time
00:00 – 23:00
01:00