2
Product information
Logalux – 6721829955 (2020/12)
43
H
Notices for the target group
These installation instructions are intended for gas,
plumbing, heating and electrical contractors. All
instructions must be observed. Failure to comply with
instructions may result in material damage and
personal injury, including danger to life.
▶ Read the installation, service and commissioning
instructions (heat source, heating controller,
pumps, etc.) before installation.
▶ Observe the safety instructions and warnings.
▶ Follow national and regional regulations, technical
regulations and guidelines.
▶ Record all work carried out.
H
Handover to the user
When handing over, instruct the user how to operate
the heating system and inform the user about its
operating conditions.
▶ Explain how to operate the heating system and draw
the user's attention to any safety relevant action.
▶ In particular, point out the following:
– Alterations and repairs must only be carried out
by an approved contractor.
– Safe and environmentally compatible operation
requires inspection at least once a year and
responsive cleaning and maintenance.
▶ Point out the possible consequences (personal
injury, including danger to life or material damage)
of non-existent or improper inspection, cleaning
and maintenance.
▶ Point out the dangers of carbon monoxide (CO) and
recommend the use of CO detectors.
▶ Leave the installation instructions and the
operating instructions with the user for
safekeeping.
2
Product information
2.1
Intended use
Enamelled DHW cylinders (cylinders) are designed for heating and
storing potable water. Please observe the applicable country-specific
regulations, guidelines and standards for potable water.
Only install the enamelled DHW cylinder (cylinder) in sealed unvented
DHW heating systems.
All other use is considered unsuitable. Any damage that results from
such use is excluded from liability.
Table 47 Requirement for potable water
2.2
Scope of delivery
• Hot water cylinder
• Technical documentation
2.3
Product description
Table 48 Product description (
Fig. 1, page 66/Fig. 11, page 70)
Requirements for
potable water
Unit
Value
Water hardness
ppm CaCO3
grain/US gallon
°dH
°fH
> 36
> 2.1
> 2
> 3.6
pH value
-
≥ 6.5... ≤9.5
Conductivity
μS/cm
≥130... ≤1500
Pos.
Description
1
DHW outlet
2
Cylinder flow
3
Sensor pocket for temperature sensor, heat source
4
DHW circulation connection
5
Cylinder return
6
Solar flow
7
Sensor pocket for temperature sensor, solar
8
Solar return
9
Cold water inlet
10
Lower heat exchanger for solar thermal heating, smooth
enamelled tubing
11
Inspection aperture for maintenance and cleaning at the front
12
Female connection (Rp 1 ½") for installation of an immersion
heater
13
Upper heat exchanger for reheating by wall mounted boiler,
smooth enamelled tubing
14
Storage cylinder, enamelled steel
15
Magnesium anode
16
Casing lid
17
Outer casing
Содержание Logalux SM310.5 E
Страница 38: ...6 Logalux 6721829955 2020 12 38 6 6 1 10 bar 6 2 6 2 60 C 44 44 7 16 17 72 18 72 19 72 8 Bosch...
Страница 66: ...Logalux 6721829955 2020 12 66 1 0010036157 001 1 10 11 12 13 14 15 16 17 4 7 8 9 2 3 5 6...
Страница 69: ...Logalux 6721829955 2020 12 69 5 6 7 8...
Страница 70: ...Logalux 6721829955 2020 12 70 9 10 11 0010036175 001 T 9 1 6 8 2 5 3 7 p1 p2 p1 p2 DN20 10 bar...
Страница 71: ...Logalux 6721829955 2020 12 71 12 13 1 2 0010009754 001 0010032885 001 14 15 0010032886 001 2 1 2 0010032887 001...