Applications manual
| 5
Panel Radiator
Design Manual
Panel Radiator Design Manual | 12.2009
Technical specifications are subject to change without prior notice
1.
General information
1.1. This manual
This application manual is intended for engineers,
architects, contractors, and installers. It provides
specification on panel radiator and towel rack models,
sizing information, and system layout assistance for
hydronic heating systems with panel radiators.
This manual describes the basic operation of the Buderus
panel radiators and towel racks, thermostatic controls and
piping accessories. It also provides rough in dimensions
and installation procedures.
Radiator heating capacities are listed by model, height and
length and are based on different supply water
temperatures.
For added savings Buderus recommends running panel
radiator systems at reduced temperatures. When using a
condensing boiler, the system should be designed so that
the return water temperature makes the boiler condense
except on the coldest days of the year.
Dew point flue gases:
• Natural Gas: 130°F (55°C)
• #2 Fuel Oil: 118°F (48°C)
General guide lines are discussed with respect to sizing
and radiator selection. The design and radiator selection
process for one and two pipe heat distribution systems are
provided including examples. Quick and easy “rules of
thumb” for trouble free installation and operation are
presented.
1.2. Standards, regulations and directives
It is the responsibility of the installer to ensure that the
system corresponds to all current regulations and rules.