3
1,2 m
m
6
4
5
8
8 m (PIR/US)
5 m (PIR/US)
3 m
(PIR/
US)
≈ 6 m
(PIR/
US)
067226 HD/HC/HS4658
L/N/NT4658N
574048
574098 AM5658
Height
Performance
• BMSO4001 - 088230:
advanced configuration remote control
• BMSO4003 -088235:
simplified configuration remote control
When the sensor receives an IR command from a configuration remote control, it
beeps to confirm that the modification has been acquired.
For more information on the parameters please refer to the technical info sheet of the
remote control BMSO4001.
Restoring the factory settings:
1
st
press: Briefly press LEARN, the LED will blink slowly.
2
nd
press: Press and hold LEARN for 10 seconds until the LED flashes quickly.
Small movements
Large movements
PIR+US flush-mounted SCS Green Switch
MQ00473-f-EN
09/06/2014
If a movement is detected for a time of less than 20 s, the sensor will decrease
the set time delay to 3 minutes. If the set delay time set is already less than three
minutes, it will remain as such.
Eco
The load is switched on manually while switching off is automatic:
- if no movement is detected at the end of the set delay time.
After switching off the load, if any movement is detected within 30 s, the load is
automatically switched back on (retrigger function on). At the end of this time
interval, the load must be switched back on manually.
Detection mode
Set of technologies used for detection.
Initial:
set of technologies used for the first detection.
Holding:
set of technologies used after the first detection.
Retrigger:
set of technologies used for the Retrigger function.
After switching off, any new detection within 30 seconds will cause the load to switch
back on automatically. After 30 seconds, the load must be switched back on manually.
Available only in Eco mode.
Alarm:
before switching off the load the sensor emits an audible warning signal.
Intervals: 1 minute, 30 seconds, and 10 seconds.
Advanced mode:
Calibration
To calibrate the sensor, it is necessary to measure the lighting level present using
a lux meter and send the value to the sensor using a configuration remote control
(BMSO4001).
Calibration procedure:
Step 1: with only artificial light.
Switch the load on at maximum intensity and close the shutters (if you cannot do
this then wait for sunset).
Measure the level of lighting and send it to the sensor via the remote control.
Step 2: with only natural light.
Turn off the load and open the shutters.
Adjustment
This function allows the sensor to switch off the load 10 minutes (plus a safety
threshold to avoid inappropriate switching off) after the lighting level exceeds the
brightness threshold, even though movement has been detected.
Contribution of light:
amount of supplementary light supplied by switching on the
load.
When the contribution of light parameter is set to "auto" the sensor automatically
calculates the contribution of light.
Modification of the parameters using the configuration remote controls