Operation
4.5 PARALLEL USE OF BATTERIES
•
MD48-50-2U and MD48-100-3U support multi machine parallel connection to
increase capacity. They support up to 15 parallel units respectively.
•
For parallel connection between batteries and communication cascade
between batteries, the original cable of BST must be used.
•
Conditions for parallel connection of multiple batteries: the SOC is the same,
and the voltage difference between batteries is less than 1V.
•
It is recommended that the output current of the single battery be lower than
0.5C.
•
When the total output current is less than 100A, a single cable connection shall
be adopted, and the power cable must be output from the top and bottom
batteries respectively. As shown in Figure 4.5.1 below.
•
When the total output current is greater than 100A and less than 200A, the
two-wire cable shall be used for connection, and the power cable must be
output from the top and bottom batteries respectively. As shown in Figure 4.5.2
below.
13
Figure 4.5.1
Figure 4.5.2