CBX ELECTRICAL CONNECTIONS
47
4
4.3 ID-NET™ INTERFACE
CBX100/500 Function
Shield
Network Cable Shield
ID+
ID-NET™ n
ID-
ID-NET™ network -
REF Network
Reference
4.3.1 ID-NET™
Cables
The following instructions are referred to Figure 33, Figure 34 and Figure 35.
The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
Cable Shield MUST be connected to earth ground ONLY at the Master.
NEVER use ID-NET™ cable shield as common reference.
The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).
For Common Power Connections use only 2 wires (ID+ and ID-).
-
DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not
put it together with AC cable):
-
Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8
Volts.
-
Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops
between them).
Scanner's chassis may be connected to earth.
Network inside the same building.
Baudrate Table
Baud Rate
125 kbps
250 kbps
500 kbps
1Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic Automation representative for details.
NOTE
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Datalogic Automation personnel only.
Содержание BSR00034
Страница 1: ...DS4800 Reference Manual BSR idware GmbH Jakob Haringer Str 3 A 5020 Salzburg Web www bsr at...
Страница 5: ...v INDEX 115...
Страница 27: ...RAPID CONFIGURATION 13 1 b Operating mode selection and definition c Digital Outputs configuration...
Страница 51: ...INSTALLATION 37 3 Figure 20 Positioning with U Shape Mounting Bracket Pitch Skew 0 15 45 45 15 alignment marks...
Страница 63: ...CBX ELECTRICAL CONNECTIONS 49 4 Figure 33 ID NET Network Connections with isolated power blocks...
Страница 64: ...DS4800 REFERENCE MANUAL 50 4 Figure 34 ID NET Network Connections with Common Power Branch Network...
Страница 65: ...CBX ELECTRICAL CONNECTIONS 51 4 Figure 35 ID NET Network Connections with Common Power Star Network...
Страница 78: ...DS4800 REFERENCE MANUAL 64 5 Figure 55 DS4800 Multidrop Connection to a Multiplexer...
Страница 81: ...25 PIN CABLE ELECTRICAL CONNECTIONS 67 5 Figure 57 ID NET Network Connections with isolated power blocks...
Страница 82: ...DS4800 REFERENCE MANUAL 68 5 Figure 58 ID NET Network Connections with Common Power Branch Network...
Страница 83: ...25 PIN CABLE ELECTRICAL CONNECTIONS 69 5 Figure 59 ID NET Network Connections with Common Power Star Network...
Страница 133: ...www automation datalogic com...