background image

Direct bypassing only slows the inevitable, the bonnet/plenum
temperature will get too hot or cold and eventually shut down the
equipment. Barometric Bypassing to an open ceiling or open foyer
is another option. With this type of zoning system, there are some
other options to Barometric Bypassing.
“Controlled Leakage” is a way to divert air to otherwise closed
zones if the smallest zone is the only one open. Each damper motor
has a setscrew to allow a MIN setting. By not allowing the damper
to close all the way, we have created a controlled leakage. This
works great for retrofit application, when ductwork may not be
able to be oversized as much as needed.
“Out Zones” are another alternative to eliminating excess air. This
principle works from the duct temperature. If the bonnet/plenum
becomes too hot or cold, the system will open an “Out Zone”.
Bottom Line: If the smallest zone plus any controlled leakage can
not handle 60 percent of the nominal CFM, then some type of
“Bypassing Option” must be considered. It may not be used very
often, based on patented damper movement (the system tries to
achieve setpoints in all the zones at the same time). When
designing with comfort in mind, rarely will only one zone be open,
while the others are closed. Bypass Determination will be
completed in Step 5 of the Duct Sizing Worksheet.
Installation of the Bypass Damper can either be a “Direct-Return”
or “Dump-Zone”. (See Fig. 2 and Fig. 3.)
Location of the Bypass Damper is very important. Listed below are
a few guidelines for proper location.

1. Location must be accessible for inspection and mainte-

nance.

2. Location must be in an area that has allowed the airflow on

the supply side to become smooth and allows bypassed air
to mix with return-air, before entering the equipment.

3. The leaving air temperature (LAT) must be installed up-

stream (ahead of) from the bypass inlet.

4. Do not locate too closely to an open return. The bypassed

air could cause the return to become positively pressured.

5. Consult Bypass Damper Installation Instruction for more

information.

B.

Task 6–Explanation of the Duct Sizing Worksheet

The Duct Sizing Worksheet will help size the supply ductwork for
a zoning system. Traditional methods, whether zoning was being
applied or not, have been to design duct work at .1 in. wc supply

and .08 in. wc return. But not everyone knew that this was based
on 100 ft of equivalent ductwork. Factoring in the equivalent
lengths of fittings could cause the Total Equivalent Length (TEL)
to go past 100 ft This could leave the ductwork undersized.

When zoning was to be applied to the system, we recommend 25
percent overissuing of the ductwork to handle the varying condi-
tions of airflow in the system. Some distributors/dealers have a
built-in “safety-factor” by designing the system with 30 percent
oversizing. Other manufacturers of zoning products have recom-
mended as much as 50–75 percent oversizing. In most cases, the
oversizing took care of any TEL’s over 100 ft.

The reason for this new Design Guide Worksheet is to help ease
the fear of designing a zoning system. The way the worksheet is
put together was to look at as many scenarios as possible, then
apply three design techniques to each example. Each scenario was
designed at:

1. 25 percent oversizing at .1 in. wc supply

2. 25 percent oversizing at .08 in. wc supply (to compensate

for TEL over 100’)

3. 30 percent oversizing at .1 in. wc supply (to compensate for

TEL over 100’)

In 99 percent of the applications, the ductwork sizes “crunched
out” to the same size.

So, if you have designed a zoning system in the past, use this guide
to see if the sizes match. If this if your first zoning design, have
faith that the sizes are not too large. Our patented damper
movement will adjust the airflow to where it’s needed. If you are
applying zoning to an existing duct system, compare what you
have to what you need. Then make the necessary adjustments to
the ductwork.

You should have completed Tasks 1–5 of the Duct Sizing
Worksheet by following Tasks 1–5.

NOTE:

The use of good take-offs and fittings are critical to the

TEL of any ductwork system. Take-off and fitting Total Equiva-
lent Length (TEL) examples are further explained in the Residen-
tial Air System Design (Catalog #791–443).

IV.

REFERENCE FOR DUCT SIZING WORKSHEET:

(SEE STEP 6 OF DUCT SIZING WORKSHEET, PAGE 9)

Using Table 1 determine the minimum Main Duct square inches
and the minimum Total Branch square inches by locating the
desired Zone CFM (from Task 3) along the left-verticle column. If
your desired Zone CFM falls between the listed CFM’s, use the
one closest to your calculated CFM. Follow the desired Zone CFM
across until you reach the Equipment Capacity, along the top,
required for your application. Write these values for each zone in
the area provided in Task 6.

NOTE:

If two or more zones share a main duct (see Fig. 6) then

add the zone CFM’s together and use that CFM to size the Main
Duct. Then as each zone is “branched-off”, it becomes the zone
“Main Branch” and would be sized based on the individual zone
square inches.

The listed areas (square inches) will provide a maximum zone duct
pressure drop of approximately 0.1 in. wc / 100 ft and a maximum
of 900 fpm for main ducts and 700 fpm for branch ducts for sheet
metal ductwork. For “Duct board”, multiply areas by 1.1, or for
“flex-duct” multiply areas by 1.25 to maintain same duct pressure
drop and fpm. If CFM in Step 3 is based on cooling and the design
is NOT based on 400 CFM/ton, divide that CFM by 400. Multiply
the areas by this number (Example: a system design of 350
CFM/ton of airflow, multiply areas by: 350/400 = .88).

NOTE:

The “grey-shaded” boxes represent zone CFM’s of less

than 20 percent of the total CFM. The square inches were
increased approximately 10 percent to help deal with situations
where limited zones may be open.

Fig. 2–Direct Return Installation

A00190

BYPASS

LEAVING AIR
TEMPERATURE
SENSOR

INDOOR
UNIT

SUPPLY AIR DUCTWORK

RETURN AIR DUCTWORK

—4—

Содержание ZONE PERFECT PLUS

Страница 1: ...oint and maintains the overall space at a predetermined humidity set point In addition to meeting these basic goals Zone Perfect Plus is designed to Direct conditioned air proportionately based on the needs of each zone so that the zone s with the greatest demand receive relatively more conditioned air Keep the sound produced by the system low enough that occupants will not find it objectionable C...

Страница 2: ...et provided in the Appendix Follow these guidelines Provide the rough dimensions of each area or room Indicate the location and relative size of doors windows and skylights In particular identify any large glass areas exceed ing 30 percent of the wall area Indicate any equipment that may add a sensible latent load Light Commercial computers copiers and waiting rooms Residential hot tubs etc Indica...

Страница 3: ...lso used to size the zone dampers and ductwork B Task 4 Size heating and cooling equipment Zone Perfect Plus is designed for use with residential furnaces fan coils and light commercial products Whenever possible a ther mostatic expansion valve TXV should be used Zone Perfect Plus is designed to operate with equipment in a range of 1 5 to 12 5 tons in cooling mode How to determine the appropriate ...

Страница 4: ...ed as much as 50 75 percent oversizing In most cases the oversizing took care of any TEL s over 100 ft The reason for this new Design Guide Worksheet is to help ease the fear of designing a zoning system The way the worksheet is put together was to look at as many scenarios as possible then apply three design techniques to each example Each scenario was designed at 1 25 percent oversizing at 1 in ...

Страница 5: ...g as the total of the Branch Duct area meets or exceeds the required amount APPENDIX The following appendix provides worksheets for you to copy and use when designing a Zone Perfect Plus installation Owner Survey Floor Plan Worksheet Duct Sizing Worksheet Examples We will show three examples of the zoning design guide Example 1 Light Commercial Doctor s Office Heating Load 125 000 Btu Cooling Load...

Страница 6: ...at might require extra cooling or heating 4 What areas if any in your home office that are used infrequently such as a formal dining meeting room or that are unoccupied for large periods of time during the day or night 3 Describe the typical usage of the various areas of your home office throughout the day During what times of the day do you typically entertain How many people do you usually enter...

Страница 7: ...in your present home 4 What do you like about your present heating and cooling system What do you dislike 8 Are there any times when you want significantly different temperatures in all or part of your home If so in what areas or rooms How quickly do you want the temperature change to occur 10 What do you expect from your indoor comfort system 1 Are there any areas or rooms in your home office tha...

Страница 8: ...A98347 Floor Plan Worksheet 8 ...

Страница 9: ..._____ ____________ ____________ _____________ ____________ ____________ ____________ ____________ _____________ ____________ ____________ ____________ ____________ _____________ Highest CFM determined from Heat Cool Btuh Step 3 Zone CFM totals Zone 1 ____________ CFM Zone 5 _____________CFM Zone 2 ____________ CFM Zone 6 _____________CFM Zone 3 ____________ CFM Zone 7 _____________CFM Zone 4 _____...

Страница 10: ...ze __ Qty ___ Area from Table 2B ________________ Size __ Qty ___ Area from Table 2B ________________ ________________ Total Sq In Zone 5 Main Duct sq in ____________________ Main Duct Size ____________ Branch sq in _______________________ Size __ Qty ___ Area from Table 2B ________________ Size __ Qty ___ Area from Table 2B ________________ ________________ Total Sq In Zone 6 Main Duct sq in ____...

Страница 11: ...00121 Waiting Room Room 1 Room 2 Room 3 Room 4 Office Office Lab Bath Bathrooms Fig 5 Light Commercial Application Doctor s Office zoned A00122 Room 1 Room 2 Room 3 Room 4 Office Office Lab Bath Bathrooms Waiting Room Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 11 ...

Страница 12: ..._____ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ Highest CFM determined from Heat Cool Btuh...

Страница 13: ...23 Branch 165 165 165 165 165 165 165 179 179 179 179 600 Main 123 123 123 123 123 123 123 123 133 133 133 Branch 198 198 198 198 198 198 198 198 208 208 208 700 Main 143 143 143 143 143 143 143 143 154 154 Branch 231 231 231 231 231 231 231 231 246 246 A00133 Zone 1 2 Main Duct Square Inches __ 123 ____ Main Duct Size___8x18____ Branch Square Inches_____179__ Size__10 ___Qty___2___ Area from Tabl...

Страница 14: ...30 Size __ Qty ___ Area from Table 2B ________________ _____________330 Total Sq In Zone 7 Main Duct sq in ____________________ Main Duct Size ____________ Branch sq in _______________________ Size __ Qty ___ Area from Table 2B ________________ Size __ Qty ___ Area from Table 2B ________________ ________________ Total Sq In Zone 8 Main Duct sq in ____________________ Main Duct Size ___________ Bra...

Страница 15: ...n Family Room Laundry Bedroom 3 Bedroom 2 Bath Master Bedroom Master Bath Fig 8 Residential Application House Floor Plan zoned into four areas A00187 Kitchen Family Room Laundry Bedroom 3 Bedroom 2 Bath Master Bedroom Master Bath Dining Room Living Room Bedroom 4 Zone 1 Zone 2 Zone 3 Zone 4 15 ...

Страница 16: ..._______ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ ____________ ___________ ____________ ____________ _____________ Highest CFM determined from Heat Cool Btuh Step 3 Zone CFM totals Z...

Страница 17: ...132 132 140 140 140 500 Main 113 113 113 113 113 113 113 123 123 Branch 165 165 165 165 165 165 165 179 179 600 Main 123 123 123 123 123 123 123 123 133 Branch 198 198 198 198 198 198 198 198 208 700 Main 143 143 143 143 143 143 143 143 Branch 231 231 231 231 231 231 231 231 Step 7 Main Trunk Table 2A and Branch Duct Table 2B Sizes Zone 1 Main Duct sq in __________________86 Main Duct Size _______...

Страница 18: ...2 155 210 24 165 215 Branch Square Inches_____231__ Size__6 ___Qty___2___ Area from Table 2B ___56___ Size__8 ___Qty___3___ Area from Table 2B __180___ __236___Total Sq In Table 2B Branch Duct Area Sq In Duct Diameter in Quantity 5 6 7 8 10 1 20 28 38 60 79 2 40 56 76 135 180 3 60 84 114 180 330 4 80 112 152 235 465 5 100 140 190 300 530 6 120 168 228 365 660 7 140 196 266 430 760 8 160 224 304 50...

Страница 19: ...q In Branch Area__289____Sq In Zone 5 CFM __________Main Duct _________Sq In Branch Area_________Sq In Zone 6 CFM __________Main Duct _________Sq In Branch Area_________Sq In Zone 7 CFM __________Main Duct _________Sq In Branch Area_________Sq In Zone 8 CFM __________Main Duct _________Sq In Branch Area_________Sq In Step 7 Main Trunk Table 2A and Branch Duct Size Table 2B Sizes Zone 1 Main Duct S...

Страница 20: ..._124____ Main Duct Size ___8x18___ Branch Square Inches ___206____ Size_______Qty_______ Area from Table 2B ________ Size__8 ___Qty___4___ Area from Table 2B __235___ __235___Total Sq In Zone 3 Main Duct Square Inches___96____ Main Duct Size ___8x14___ Branch Square Inches ___138____ Size_______Qty_______ Area from Table 2B ________ Size__7 ___Qty___4___ Area from Table 2B __152___ __152___Total S...

Страница 21: ...4 214 214 214 214 214 214 Branch 396 396 396 396 396 396 396 396 396 1300 Main 227 227 227 227 227 227 227 227 Branch 429 429 429 429 429 429 429 429 1400 Main 241 241 241 241 241 241 241 241 Branch 462 462 462 462 462 462 462 462 1500 Main 254 254 254 254 254 254 254 Branch 495 495 495 495 495 495 495 1600 Main 269 269 269 269 269 269 269 Branch 528 528 528 528 528 528 528 1700 Main 284 284 284 2...

Страница 22: ...79 113 154 201 2 40 56 76 135 180 365 565 760 3 60 84 114 180 330 530 795 825 4 80 112 152 235 465 730 825 5 100 140 190 300 530 825 6 120 168 228 365 660 7 140 196 266 430 760 8 160 224 304 500 825 9 180 252 342 565 10 200 280 380 630 11 220 308 418 660 12 240 336 456 726 13 260 364 494 795 14 280 392 532 15 300 420 570 Two 8 pipes have approximately the same volume of five 6 pipes To keep static...

Страница 23: ... 23 ...

Страница 24: ... 2000 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 24 Printed in U S A ap17 5 Catalog No 809 651 ...

Отзывы: