WET COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE

Unit 583B024-060 (Deduct 10% for 208 Volts)

*Air delivery values are without air filter.

NOTE: Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting.

230 AND 460 VOLT

Unit

583B

Motor

Speed

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

279

282

280

277

276

CFM

882

801

738

674

604

Med

Watts

373

367

361

356

351

CFM

936

868

797

719

626

High

Watts

463

452

439

428

CFM

956

878

794

702

030

Low

Watts

243

244

242

CFM

885

842

786

Med

Watts

353

339

333

330

326

320

CFM

1195

1134

1070

997

911

818

High

Watts

443

436

426

416

406

397

CFM

1230

1145

1061

977

888

786

036

Low

Watts

490

463

446

432

418

403

389

378

CFM

1431

1398

1347

1281

1205

1118

1024

921

Med

Watts

513

501

488

474

459

443

428

CFM

1491

1426

1351

1267

1175

1077

976

High

Watts

645

636

627

616

605

593

583

CFM

1484

1410

1330

1243

1147

1044

936

042

Low

Watts

634

618

608

598

583

562

534

502

473

454

457

CFM

1669

1599

1545

1498

1448

1391

1326

1257

1189

1132

1101

Med

Watts

733

704

672

638

604

574

550

536

CFM

1746

1688

1630

1566

1492

1399

1279

1120

High

Watts

797

773

751

727

696

CFM

1727

1632

1537

1423

1308

048

Low

Watts

591

578

573

568

559

544

524

500

CFM

1554

1523

1496

1467

1432

1387

1332

1269

Med

Watts

755

737

719

699

678

653

627

602

579

562

556

CFM

1834

1802

1758

1706

1648

1585

1520

1455

1392

1332

1276

High

Watts

890

858

828

801

777

756

734

709

CFM

1943

1870

1793

1711

1624

1531

1433

1329

060

Low

Watts

589

576

569

566

559

541

499

CFM

1946

1891

1836

1779

1718

1651

1577

Med

Watts

750

733

715

695

673

648

623

598

577

CFM

2189

2097

2021

1952

1883

1809

1727

1635

1530

High

Watts

879

850

821

795

772

750

728

701

CFM

2337

2159

2050

1974

1905

1824

1722

1597

LEGEND

Ewb –

Entering Wet-Bulb

kW

Total Unit Power Input

SHC –

Gross Sensible Heat Capacity (1000 Btuh)

TC

Gross Cooling Capacity (1000 Btuh)

NOTES:
1. Ratings are gross; they do not account for the effects
     of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

2

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

2

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

BF     –

Bypass Factor

4. Determine Net Cooling Capacity using the following formula:

     Net Capacity = Gross Cooling Capacity – Indoor Fan Motor Heat
Indoor Fan Motor Heat is determined by the following formula:

          Indoor Fan Motor Heat = Indoor Fan Motor Watts x (3,413 Btuh/Watts)

The Indoor Fan Motor Watts are determined from the Wet Coil Air Delivery 
table depending on the desired CFM and speed setting.

Содержание PURON 583B

Страница 1: ...it for propane conversion is available for all units 583B units with an N in the thirteenth position of model are dedicated Low NOx units designed for California installa tions These models meet the California maximum oxides of ni trogen NOx emissions requirement of 40 nanograms joule or less as shipped from the factory and MUST be installed in Cali fornia Air Quality Management Districts where a ...

Страница 2: ...p easy Downflow operation is easily provided in the field to allow ver tical ductwork connections The basepan utilizes knockout style seals on the bottom openings to ensure a positive seal in the horizontal airflow mode Integrated Gas Control IGC board provides safe and efficient control of heating and simplifies trouble shooting through its built in diagnostic function Cabinets are constructed of...

Страница 3: ... 35 000 12 0 7 2 042060 042090 3 1 2 1400 41 000 12 0 7 3 048090 048115 048130 4 1600 48 000 12 0 7 8 060090 060115 060130 5 1750 59 000 12 0 7 6 LEGEND dB Decibels db Dry Bulb SEER Seasonal Energy Efficiency Ratio wb Wet Bulb Air Conditioning Refrigeration Institute Rated in accordance with U S Government DOE Department of Energy test procedures and or ARI Standard 210 240 89 Tested in accordance...

Страница 4: ...24040 030040 40 000 31 000 20 50 80 1 024060 030060 036060 042060 60 000 46 000 46 000 46 000 47 000 35 65 35 65 25 55 20 50 78 4 78 4 78 7 78 7 036090 042090 048090 060090 88 000 90 000 90 000 90 000 70 000 71 000 70 000 70 000 45 75 35 65 25 55 25 55 79 9 79 9 78 6 78 6 048115 060115 115 000 92 000 35 65 81 1 048130 060130 130 000 104 000 103 000 40 70 80 3 M A N U F A C T U R E R CERTIFIED TO A...

Страница 5: ... 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 EVAPORATOR COIL Rows fins in Face Area sq ft 3 15 3 7 3 15 3 7 3 15 3 7 3 15 3 7 3 15 3 7 3 15 3 7 3 15 4 7 3 15 4 7 EVAPORATOR BLOWER Nominal Airflow Cfm Size in Motor Hp 800 10 x 10 1 4 800 10 x 10 1 4 800 10 x 10 1 4 1000 10 x 10 1 4 1200 10 x 10 1 2 1200 10 x 10 1 2 1400 11 x 10 3 4 1400 11 x 10 3 4 FURNACE SECTION Burner Orifice...

Страница 6: ... 1 4 1100 3300 22 1 4 1100 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows fins in Face Area sq ft 4 15 4 7 4 15 4 7 4 15 4 7 4 15 4 7 4 15 4 7 4 15 4 7 EVAPORATOR BLOWER Nominal Airflow Cfm Size in Motor Hp 1600 11 x 10 3 4 1600 11 x 10 3 4 1600 11 x 10 3 4 1750 11 x 10 1 0 1750 11 x 10 1 0 1750 11 x 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill Size Natural Gas Burner Orifice No Qty ...

Страница 7: ...shot applications Thermostats provide control for the system heating and cooling functions Thermostat models are available in both programma ble and non programmable versions Crankcase heater provides anti floodback protection for low load cooling applications LP liquid propane conversion kit allows for conversion from natural gas to liquid propane fuel Low ambient kit Motormaster II control allow...

Страница 8: ... 8 Filter Rack DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL Manual Outside Air Damper Economiser ...

Страница 9: ...ES in mm Between units power entry side 42 1066 8 Unit and ungrounded surfaces power entry side 36 914 Unit and block or concrete walls and other grounded surfaces control box side 42 1066 8 LEGEND CG Center of Gravity COND Condenser EVAP Evaporator NEC National Electrical Code REQ D Required Note Dimensions are in in mm UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN MM A CENTER OF GRA...

Страница 10: ...EL 36 00 914 4 NEC REQUIRED CLEARANCES MILLIMETERS IN BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 FLUE HOOD UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN MM A CENTER OF GRAVITY IN MM lb kg X Y Z 583B042060 090 208 230 1 60 208 230 3 60 46...

Страница 11: ...ial field supplied Cant strip field supplied Provided with roofcurb Roof Duct work field supplied Insulation field supplied Roofcurb Wood nailer Gasketing inner flange Flashing Detail Supply opening 11 x 16 1 2 clear Long Support Side End 28 3 4 44 5 16 Return opening 11 X 16 1 2 clear 17 3 8 Insulated deck pan Short Support Long Support 11 Typ 44 5 16 13 13 28 3 4 Roof opening for supply duct Roo...

Страница 12: ... OF UNIT TO PROVIDE DESIGN CONDITION REQUIREMENT In the Heating Capacities and Efficiencies table on page 4 note that the unit 48GX036090 will provide 71 910 Btuh with an input of 88 000 Btuh IV DETERMINE FAN SPEED AND POWER REQUIRE MENTS AT DESIGN CONDITIONS Before entering the air delivery tables calculate the total static pressure required From the given example the Wet Coil Pressure Drop Table...

Страница 13: ...21 8 11 5 3 75 18 6 18 6 3 71 20 2 16 6 3 84 22 7 12 8 3 91 20 1 20 1 3 94 21 0 18 9 4 09 23 2 13 9 4 14 583B030 COOLING PERFORMANCE TABLE Temp F Outdoor Air Entering Condenser Evaporator Air CFM BF 750 0 08 1000 0 11 1250 0 15 Evaporator Air Ewb F 62 67 72 62 67 72 62 67 72 75 TC SHC kW 29 5 25 7 2 11 32 8 21 9 2 14 34 9 17 5 2 15 31 4 30 0 2 28 34 0 24 3 2 32 35 7 18 6 2 33 32 8 32 8 2 46 34 6 2...

Страница 14: ...SHC kW 22 7 22 7 4 48 25 3 19 6 4 59 27 7 15 2 4 61 25 0 25 0 4 71 26 3 22 6 4 79 28 3 16 6 4 84 26 4 26 4 4 98 26 9 25 0 5 09 28 6 17 1 5 15 583B042 COOLING PERFORMANCE TABLE Temp F Outdoor Air Entering Condenser Evaporator Air CFM BF 1050 0 10 1500 0 13 1750 0 17 Evaporator Air Ewb F 62 67 72 62 67 72 62 67 72 75 TC SHC kW 41 8 36 0 2 93 45 5 30 1 2 97 48 9 23 9 2 99 44 0 41 5 3 20 47 7 33 7 3 2...

Страница 15: ...Temp F Outdoor Air Entering Condenser Evaporator Air CFM BF 1500 0 05 1750 0 06 2000 0 07 2500 0 08 Evaporator Air Ewb F 62 67 72 62 67 72 62 67 72 62 67 72 75 TC SHC kW 60 1 52 7 4 63 66 7 44 6 4 69 72 4 35 6 4 75 62 2 57 7 4 67 68 5 47 9 4 71 74 2 37 5 4 78 64 2 62 1 4 68 70 0 51 1 4 73 75 6 39 3 4 80 67 5 67 5 4 70 72 1 56 8 4 75 77 5 42 6 4 84 85 TC SHC kW 56 9 51 3 5 06 63 3 43 2 5 17 69 4 34...

Страница 16: ...554 1523 1496 1467 1432 1387 1332 1269 Med Watts 755 737 719 699 678 653 627 602 579 562 556 CFM 1834 1802 1758 1706 1648 1585 1520 1455 1392 1332 1276 High Watts 890 858 828 801 777 756 734 709 CFM 1943 1870 1793 1711 1624 1531 1433 1329 060 Low Watts 589 576 569 566 559 541 499 CFM 1946 1891 1836 1779 1718 1651 1577 Med Watts 750 733 715 695 673 648 623 598 577 CFM 2189 2097 2021 1952 1883 1809 ...

Страница 17: ...PRESSURE DROP 024 036 0 20 042 060 0 25 UNIT 583B Frequency Hz 024 030 036 042 048 060 63 44 8 48 0 50 0 49 1 51 4 53 7 125 60 4 58 2 60 4 63 9 65 2 62 6 250 58 3 59 2 61 6 65 2 69 7 65 9 500 64 8 65 8 66 9 67 9 72 7 70 6 1000 66 9 67 7 67 8 66 7 72 9 71 6 2000 64 3 64 8 64 6 63 8 69 8 68 2 4000 59 8 61 8 60 7 60 2 65 8 65 8 8000 51 8 53 6 52 8 50 7 57 9 58 3 ...

Страница 18: ...ough your Bryant distributor ALTITUDE ft INPUT Btuh OUTPUT Btuh ORIFICE NUMBER 0 2000 40 000 31 000 44 60 000 46 000 38 90 000 70 000 38 115 000 92 000 33 130 000 103 000 31 2001 4500 33 290 25 800 49 49 930 38 300 43 74 900 58 270 43 95 700 76 560 38 108 180 85 680 36 4501 6000 31 310 24 270 50 46 970 36 030 44 70 450 54 810 44 90 020 71 300 40 101 760 80 590 37 ALTITUDE ft INPUT Btuh OUTPUT Btuh...

Страница 19: ...OR THERMOSTAT DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LINE NEC NATIONAL ELECTRICAL CODE ROOF RETURN AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB ...

Страница 20: ...vers to seal the horizontal discharge openings in the unit Units installed in horizontal discharge orientation do not require duct covers Airflow Units are draw thru in the Cooling mode and blow thru in the Heating mode Maximum cooling airflow To minimize the possibility of condensate blow off from the evaporator airflow through the units should not exceed 450 cfm per ton Minimum cooling airflow T...

Страница 21: ...ection RLA Rated Load Amps NOTES 1 In compliance with NEC National Electrical Code requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent protective device for the unit shall be Power Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire If other than 60 C wire is used...

Страница 22: ... 22 TYPICAL WIRING SCHEMATIC 208 230 1 60 SHOWN ...

Страница 23: ... 23 TYPICAL WIRING SCHEMATIC 208 230 3 60 SHOWN ...

Страница 24: ... 24 TYPICAL WIRING SCHEMATIC 460 3 60 SHOWN ...

Страница 25: ...it wire Y and blow er relay coil BR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and complete the circuit through compressor motor COMP to con denser outdoor fan motor OFM Both motors start instantly The set of normally open contacts of energized relay BR close and complete the circuit through evaporator blower indoor f...

Страница 26: ... 26 ...

Страница 27: ...door air cavity section 5 Unit shall have a field supplied condensate trap C Fans 1 The evaporator fan shall be 3 speed direct drive as shown on equipment drawings 2 Fan wheel shall be made from steel and shall be double inlet type with forward curved blades with corrosion resistant finish Fan whell shall be dynamically balanced 3 Condenser fan shall be direct drive propeller type with aluminum bl...

Страница 28: ...od nailer for flash ing and shall be installed per manufacturer s instruc tions 4 Manual Outdoor Air Damper Package shall consist of damper birdscreen and rain hood which can be preset to admit outdoor air for year round ventilation 5 Thermostat To provide for one stage heating and cooling in addition manual or automatic changeover and indoor fan control 6 Natural to Propane Conversion Kit Shall b...

Отзывы: