WET COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE
Unit 583B024-060 (Deduct 10% for 208 Volts)
*Air delivery values are without air filter.
NOTE: Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting.
230 AND 460 VOLT
Unit
583B
Motor
Speed
External Static Pressure (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
024
Low
Watts
279
282
280
277
276
—
—
—
—
—
—
CFM
882
801
738
674
604
—
—
—
—
—
—
Med
Watts
—
—
—
373
367
361
356
351
—
—
—
CFM
—
—
—
936
868
797
719
626
—
—
—
High
Watts
—
—
—
—
—
463
452
439
428
—
—
CFM
—
—
—
—
—
956
878
794
702
—
—
030
Low
Watts
243
244
242
—
—
—
—
—
—
—
—
CFM
885
842
786
—
—
—
—
—
—
—
—
Med
Watts
353
339
333
330
326
320
—
—
—
—
—
CFM
1195
1134
1070
997
911
818
—
—
—
—
—
High
Watts
—
—
—
443
436
426
416
406
397
—
—
CFM
—
—
—
1230
1145
1061
977
888
786
—
—
036
Low
Watts
490
463
446
432
418
403
389
378
—
—
—
CFM
1431
1398
1347
1281
1205
1118
1024
921
—
—
—
Med
Watts
—
513
501
488
474
459
443
428
—
—
—
CFM
—
1491
1426
1351
1267
1175
1077
976
—
—
—
High
Watts
—
—
645
636
627
616
605
593
583
—
—
CFM
—
—
1484
1410
1330
1243
1147
1044
936
—
—
042
Low
Watts
634
618
608
598
583
562
534
502
473
454
457
CFM
1669
1599
1545
1498
1448
1391
1326
1257
1189
1132
1101
Med
Watts
—
—
—
733
704
672
638
604
574
550
536
CFM
—
—
—
1746
1688
1630
1566
1492
1399
1279
1120
High
Watts
—
—
—
—
—
—
797
773
751
727
696
CFM
—
—
—
—
—
—
1727
1632
1537
1423
1308
048
Low
Watts
591
578
573
568
559
544
524
500
—
—
—
CFM
1554
1523
1496
1467
1432
1387
1332
1269
—
—
—
Med
Watts
755
737
719
699
678
653
627
602
579
562
556
CFM
1834
1802
1758
1706
1648
1585
1520
1455
1392
1332
1276
High
Watts
—
—
—
890
858
828
801
777
756
734
709
CFM
—
—
—
1943
1870
1793
1711
1624
1531
1433
1329
060
Low
Watts
589
576
569
566
559
541
499
—
—
—
—
CFM
1946
1891
1836
1779
1718
1651
1577
—
—
—
—
Med
Watts
750
733
715
695
673
648
623
598
577
—
—
CFM
2189
2097
2021
1952
1883
1809
1727
1635
1530
—
—
High
Watts
—
879
850
821
795
772
750
728
701
—
—
CFM
—
2337
2159
2050
1974
1905
1824
1722
1597
—
—
LEGEND
Ewb –
Entering Wet-Bulb
kW
–
Total Unit Power Input
SHC –
Gross Sensible Heat Capacity (1000 Btuh)
TC
–
Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are gross; they do not account for the effects
of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
sensible capacity (Btuh)
t
= t
2
ldb
edb
1.10 x cfm
t
= Wet-bulb temperature corresponding to enthalpy of air leaving
lwb
evaporator coil (h
)
lwb
total capacity (Btuh)
h
= h
2
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
BF –
Bypass Factor
4. Determine Net Cooling Capacity using the following formula:
Net Capacity = Gross Cooling Capacity – Indoor Fan Motor Heat
Indoor Fan Motor Heat is determined by the following formula:
Indoor Fan Motor Heat = Indoor Fan Motor Watts x (3,413 Btuh/Watts)
The Indoor Fan Motor Watts are determined from the Wet Coil Air Delivery
table depending on the desired CFM and speed setting.