Page 6
represents a multiple of 30 seconds from the Dry Con-
tact closure.
For example, 1 = turn on 30 seconds after
Dry Contact closure, 2 = turn on 60 seconds after clo-
sure, 3 = turn on 90 seconds after closure, and so on.
See
page 4, Step 13,
to configure the thermostat for
Soft Start.
• DUAL SET POINT BEHAVIOR — The adjustable set
point range is: 35 to 99 degrees in Fahrenheit and 7 to
35 degrees in Celsius. When in the modes Heat or
Cool, this adjustable range is unhampered.
When adjusting any Auto mode, including program-
ming Occupied and Unoccupied periods, the thermo-
stat will not allow the Heat set point to get closer to the
Cool set point than the value programmed as the mini-
mum difference in
Step 5, page 4.
When entering the Auto mode from Cool, the Heat and
Cool set point temperatures will remain spread apart
by the amount that they were adjusted, prior to enter-
ing Auto.
For example: If the Cool set point was set to 80 while
in the Cool mode and the Heat set point was adjusted
to 70 while in the Heat mode, upon entering the Auto
mode the Heat and Cool set points would be 80 and
70.
Both
set points would then move up and down
together, (in this example spread by 10 degrees), by
pressing the up or down buttons.
To move the Heat and Cool set points closer together,
enter the Cool or Heat mode by pressing the Mode
button, then adjust the set point(s) closer together.
Heat is limited to how close it can come to Cool by
Step 5, page 4
.
• REMOTE SENSORS
(Optional Accessory)
— When
connected to terminals RS+5, RS, and GND on the
back of the thermostat, the thermostat will read the
temperature from the Remote Sensor and ignore the
temperature sensor inside the thermostat. The thermo-
stat automatically recognizes when a Remote Sensor
is connected. When reading the temperature from the
remote, the degree icon
above the room tempera-
ture blinks once a second.
The Override button
on
the Remote Sensor works
slightly different than the
Override button on the
front panel. Each press of
the ‘External’ Override
button adds 2 hours to the
override timer. If the timer
was already active,
the first button press will round the
runtime to either
2:00 or 4:00.
Subsequent button presses will not wraparound as the
Override button on the thermostat does, so the second
or greater button press will set the runtime to 4:00. The
Locked feature has no effect on the external Override
button. The
wired
Remote Sensor is connected to the
thermostat with
up to 500 ft of 20 ga. or 300 ft of
18 ga.
thermostat wire
.
See the Remote Sensor
instructions for further details.
• FACTORY DEFAULTS — Before restoring factory
defaults, set thermostat to OFF mode. If, for any rea-
son it is desirable to return all stored settings back to
the factory default settings, press the Mode button.
While holding the Mode button in, press the Fan button
for 5 sec. All icons will appear. Press and hold in the
Fan button until
Fd
appears. This resets all factory set-
tings.
To calibrate room temperature,
press the Up
and Down buttons at the same time twice. At this point
use the Up and Down buttons to calibrate room tem-
perature, if needed. Press the Mode button to return to
normal operation.
Optional
Remote Sensor
Optional Sensor
OVER
RIDE
OVER
RIDE