43
Option 99 — Reset to Factory Defaults
Use this capability to reset the Thermidistat Control to “out of the box”
conditions. BEWARE! All configuration settings, program settings, clock, and
calendar which have been manually entered will be lost!
When this option is selected, the configuration number (99), will appear on the
left and 10 will appear on the right. To perform the reset, first use the MODE key
to move the box from the 99 to the 10 (programmable model) or to flash the 10
(non--programmable model). Then press and hold the DOWN key. The 10 will
start counting down toward zero. If the DOWN key is kept pressed until the
count reaches zero, the reset will be performed. When the value reaches zero, the
heat setpoint shall display ----. The cool setpoint shall display -- and the room air
temperature shall display Fd. When the factory defaults have been restored, the
Thermidistat Control will act as if power was cycled and return to normal
operation. If the DOWN key is released early, the number will return to 10 and
the reset will not occur.
SYSTEM START--UP AND CHECKOUT
The Thermidistat Control is designed with a built--in installer test capability. It
allows easy operation of equipment without delays or setpoint adjustments to
force heating or cooling. To enable installer test mode, press and hold the fan
button for 15 seconds. After 10 seconds, the Thermidistat Control will enter
Configuration Mode. Continuing to hold the Fan button through 15 seconds will
cause the Thermidistat Control to enter Installer Test Mode. Pressing the Mode
button will change the system operating mode to test the heating and cooling
equipment. Auto Mode is not available during Installer Test Mode. If no buttons
are pressed for 15 minutes, the installer test mode will be terminated. Pressing
DONE at any time will exit installer test mode.