ACCESSORY USAGE GUIDELINE

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F)

REQUIRED FOR

LONG LINE

APPLICATIONS*

(Over 80 Ft.)

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Accumulator

Standard

Standard

Standard

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Motor Master

®

Control or

Low---ambient Pressure Switch

Standard

Standard

Standard

Support Feet

Recommended

No

Recommended

Liquid Line Solenoid Valve

No

See Long---Line Ap-

plication Guideline

No

Ball Bearing Fan Motor

Standard

Standard

Standard

* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to Long---Line Application Guideline.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMaster

r

is used.

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the

following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

7. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is

to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in

the heating mode. See Long Line Guideline.

8. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in

order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient

temperatures down to 0

_

F when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55

_

F (12.8

_

C).

9. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the

saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

--12

_

C).
Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when

cooling operation is used at outdoor temperatures
below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

265A

Содержание PREFERRED 265A

Страница 1: ...Quiet Operation S AeroQuiet System IIt for sound as low as 69 dBA S Quiet mount split post compressor grommets S External AeroQuiet muffler S Exclusive AeroQuiet Top design S 8 Pole PSC ball bearing c...

Страница 2: ...STAR guidelines for energy efficiency Refer to the combination ratings in Product Data for system combinations that meet Energy Star guidelines STANDARD FEATURES Feature 018 B 024 B 030 B 036 B 042 B...

Страница 3: ...ical separation is 200 ft when outdoor unit is above indoor unit and 80 ft when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Long Lin...

Страница 4: ...age Heat 1 Stage Cool TSTATBBNHP01 C Thermostat Auto Changeover Non Programmable F C 2 Stage Heat 1 Stage Cool TSTATBBSHP01 Standard Programmable Thermostat Manual Changeover 5 2 Day Programmable F C...

Страница 5: ...chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Evaporator Freeze Thermostat An SP...

Страница 6: ...int Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 13 Sound Hood Wraparound sound reducing cover for the compressor Reduces the sound level by ab...

Страница 7: ...e for 10 AWG or smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel...

Страница 8: ...8 DIMENSIONS 265A...

Страница 9: ...UILDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 23 4 kW 265ANA024 A FX4CNF030 265ANA030 A FX4CNF030 265ANA036 A FX4CNF042 265ANA042 A FX4CNF048 265ANA048 A...

Страница 10: ...V 13 50 10 80 18 000 3 54 10 900 2 28 8 1 CSPH 2412A 17 600 TDR TXV 15 00 12 00 17 600 3 54 10 300 2 34 8 1 315 A J AV036070 CSPH 2412A 17 700 TDR TXV 15 00 12 00 17 600 3 58 10 300 2 34 8 2 315 A J A...

Страница 11: ...66 13 800 2 48 8 4 315 A J AV048090 CSPH 2412A 23 000 TDR TXV 15 00 12 50 23 200 3 64 13 900 2 46 8 3 315 A J AV060110 CSPH 2412A 23 000 TDR TXV 15 00 12 50 23 200 3 64 13 800 2 46 8 4 315 A J AV0661...

Страница 12: ...66135 CNPH 3617A 29 000 TDR TXV 15 50 13 00 28 800 3 72 16 800 2 50 8 4 315 A J AV066155 CNPH 3617A 28 800 TDR TXV 15 00 12 50 28 800 3 68 16 800 2 46 8 3 355AAV042040 CNPH 3617A 28 800 TDR TXV 15 50...

Страница 13: ...33 000 3 54 19 200 2 40 7 8 315 A J AV060110 CAP 3621A 34 400 TDR TXV 14 50 12 00 33 000 3 48 19 300 2 36 7 7 355AAV042080 CAP 3621A 34 400 TDR TXV 15 00 12 50 33 000 3 50 19 300 2 38 7 7 355AAV060080...

Страница 14: ...TXV 15 00 12 50 33 000 3 62 19 400 2 42 7 8 355AAV060120 CSPH 3612A 34 600 TXV 14 00 11 50 34 200 3 60 20 400 2 38 7 7 CSPH 4212A 34 800 TDR TXV 15 00 12 50 33 200 3 64 19 500 2 42 7 8 315 A J AV03607...

Страница 15: ...2 355AAV042060 CNPH 4821A 41 000 TDR TXV 14 00 12 00 41 000 3 54 25 200 2 52 8 2 355AAV042080 CNPH 4821A 41 500 TDR TXV 14 50 12 00 41 000 3 58 25 200 2 54 8 2 355AAV060080 CNPH 4821A 41 500 TDR TXV...

Страница 16: ...3 355AAV060100 CAP 6021A 48 000 TXV 14 00 12 00 48 500 3 74 30 800 2 54 8 4 CAP 6024A 48 000 TDR TXV 15 00 12 50 47 000 3 74 29 600 2 60 8 3 315 A J AV066135 CAP 6024A 48 000 TDR TXV 15 00 12 50 47 00...

Страница 17: ...XV 13 00 10 80 60 000 3 56 37 800 2 50 8 0 CAP 6021A 58 000 TDR TXV 13 50 11 20 59 000 3 52 36 400 2 52 8 0 315 A J AV060110 CAP 6021A 58 000 TXV 13 50 11 20 59 000 3 52 36 600 2 52 7 9 CAP 6024A 58 5...

Страница 18: ...15 39 1 67 14 50 14 50 1 87 13 54 13 54 2 09 675 72 22 22 12 10 1 18 21 12 11 69 1 32 19 98 11 27 1 49 18 77 10 83 1 67 17 48 10 37 1 87 16 10 9 87 2 09 67 20 16 15 23 1 18 19 14 14 80 1 33 18 07 14 3...

Страница 19: ...003 0 99 0 95 FX4CNF024 0 98 0 99 FY4ANF024 0 97 1 06 FY4ANF030 0 97 1 06 CAP 2414A 0 97 1 09 CAP 2417A 0 97 1 09 CAP 3014A 0 98 1 07 CAP 3017A 0 98 1 07 CNPF 2418A 0 97 1 09 CNPH 2417A 0 97 1 06 CNPH...

Страница 20: ...99 1 08 CAP 3614A 0 96 1 00 CAP 3617A 0 99 1 03 CAP 3621A 0 99 1 03 CNPF 3618A 0 99 1 03 CNPH 3017A 0 99 1 03 CNPH 3617A 0 99 1 03 CNPV 3014A 0 99 1 03 CNPV 3017A 0 99 1 03 CNPV 3617A 0 99 1 03 CNPV 3...

Страница 21: ...A 0 96 1 07 CNPH 3617A 0 96 1 04 CNPH 4221A 0 97 1 06 CNPV 3617A 0 96 1 04 CNPV 3621A 0 96 1 04 CNPV 4221A 0 97 1 06 CSPH 3612A 0 96 1 04 CSPH 4212A 0 97 1 01 CAP 3614A 0 93 0 97 315 A J AV036070 CNPH...

Страница 22: ...SPH 4212A 0 98 1 06 CSPH 4812A 0 99 1 07 CNPH 4221A 0 96 1 00 315 A J AV036070 CNPH 4821A 0 98 1 02 315 A J AV036070 CSPH 4212A 0 96 1 00 315 A J AV036070 CSPH 4812A 0 98 1 02 315 A J AV036070 CAP 481...

Страница 23: ...1 00 1 00 FE4ANB006 1 00 1 00 FE4ANF005 1 00 1 04 FV4BNB006 1 00 1 00 FV4BNF005 1 00 1 04 FX4CN B F 048 1 00 1 04 FY4ANB060 1 00 1 08 FY4ANF048 1 00 1 16 CAP 4817A 0 98 1 06 CAP 4821A 1 00 1 08 CAP 4...

Страница 24: ...48 16 4 82 56 81 46 67 5 30 53 32 45 13 5 83 49 59 43 48 6 40 45 51 41 66 7 02 62 62 50 61 84 4 37 59 65 59 65 4 81 56 86 56 86 5 31 53 91 53 91 5 84 50 70 50 70 6 42 47 12 47 12 7 05 57 62 26 62 26...

Страница 25: ...5 21 52 21 52 1 55 24 88 24 88 1 64 75 525 5 64 5 19 1 21 7 65 7 03 1 27 9 76 8 90 1 34 12 02 10 68 1 40 14 49 13 19 1 48 17 31 17 31 1 58 20 37 20 37 1 70 23 77 23 77 1 84 600 5 75 5 29 1 21 7 76 7 1...

Страница 26: ...07 CNPF 2418A 1 01 1 05 CNPH 2417A 1 01 1 05 CNPH 3017A 1 01 1 06 CNPV 2414A 1 01 1 05 CNPV 2417A 1 01 1 05 CNPV 3014A 1 01 1 06 CNPV 3017A 1 01 1 06 CSPH 2412A 1 01 1 05 CSPH 3012A 1 01 1 06 Heating...

Страница 27: ...1 02 1 06 CNPV 3017A 1 02 1 06 CNPV 3617A 1 02 1 06 CNPV 3621A 1 02 1 06 CSPH 3012A 1 02 1 05 CSPH 3612A 1 02 1 02 CAP 3014A 0 98 1 02 315 A J AV036070 CAP 3614A 0 95 0 98 315 A J AV036070 CNPH 3017A...

Страница 28: ...CSPH 4212A 1 01 1 04 CAP 3614A 0 98 1 06 315 A J AV036070 CNPH 3617A 0 97 1 05 315 A J AV036070 CNPH 4221A 0 98 1 03 315 A J AV036070 CSPH 3612A 0 97 1 01 315 A J AV036070 CSPH 4212A 0 98 1 01 315 A...

Страница 29: ...3 315 A J AV036070 CSPH 4812A 0 98 1 04 315 A J AV036070 CAP 4817A 0 98 1 02 315 A J AV048090 CNPH 4221A 0 96 1 04 315 A J AV048090 CNPH 4821A 0 98 1 03 315 A J AV048090 CSPH 4212A 0 96 1 02 315 A J A...

Страница 30: ...04 FY4ANB060 1 02 1 08 FY4ANF048 1 00 1 09 CAP 4817A 0 99 1 08 CAP 4821A 1 01 1 09 CAP 4824A 1 01 1 09 CAP 6021A 1 01 1 08 CAP 6024A 1 01 1 08 CNPF 4818A 0 98 1 11 CNPH 4821A 1 01 1 09 CNPH 6024A 1 01...

Страница 31: ...9 51 27 12 4 18 35 83 32 67 4 38 42 51 37 75 4 59 49 79 45 31 4 83 58 34 58 34 5 06 66 67 66 67 5 35 75 53 75 53 5 68 2000 24 01 22 09 4 03 29 99 27 56 4 20 36 35 33 14 4 38 43 07 38 26 4 58 50 52 45...

Страница 32: ...hase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped...

Отзывы: