PURON

R

 (R

410A) QUICK REFERENCE GUIDE

S

 Puron refrigerant operates at 50

70 percent higher pressures than R

22. Be sure that servicing equipment and replacement

components are designed to operate with Puron

S

 Puron refrigerant cylinders are rose colored.

S

 Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S

 Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating

S

 Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low

side retard.

S

 Use hoses with 700 psig service pressure rating.

S

 Leak detectors should be designed to detect HFC refrigerant.

S

 Puron, as with other HFCs, is only compatible with POE oils.

S

 Vacuum pumps will not remove moisture from oil.

S

 Do not use liquid

line filter driers with rated working pressures less than 600 psig.

S

 Do not leave Puron suction line filter driers in line longer than 72 hours.

S

 Do not install a suction

line filter drier in liquid line.

S

 POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

 POE oils may cause damage to certain plastics and roofing materials.

S

 Wrap all filter driers and service valves with wet cloth when brazing.

S

 A factory approved liquid

line filter drier is required on every unit.

S

 Do NOT use an R

22 TXV.

S

 If indoor unit is equipped with an R

22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.

S

 Never open system to atmosphere while it is under a vacuum.

S

 When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.

S

 Do not vent Puron into the atmosphere.

S

 Do not use capillary tube coils.

S

 Observe all 

warnings

cautions

, and 

bold 

text.

S

 All indoor coils must be installed with a hard shutoff Puron TXV metering device.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

E

2015 Bryant Heating & Cooling Systems 

D

 7310 W. Morris St. 

D

 Indianapolis, IN  46231                    Edition Date: 03/15

Replaces: II226A-04

Catalog No. II226A-05

226A

Содержание PREFERRED 226A Series

Страница 1: ...a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing...

Страница 2: ...luding adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service en...

Страница 3: ...n 914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft...

Страница 4: ...be BEFORE bolting adapter to valve This helps prevent overheating and damage to plastic washer or o ring For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing Th...

Страница 5: ...isconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or...

Страница 6: ...Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on t...

Страница 7: ...ff Cooling With first stage cooling Y and O are powered on and with second stage cooling Y2 Y and O are powered on The O energizes the reversing valve switching it to cooling position The Y signal sen...

Страница 8: ...E IN HIGH STAGE ONLY Factory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit To properly check or adjust charge conditions...

Страница 9: ...s and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fil...

Страница 10: ...install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all...

Отзывы: