Bryant PREFERRED 124ANS Скачать руководство пользователя страница 2

2

INSTALLATION

IMPORTANT

: Effective January 1, 2015, all split system and

packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
Puron (R

410A) refrigerant systems operate at higher

pressures than standard R

22 systems. Do not use R

22

service equipment or components on Puron refrigerant

equipment.

PERSONAL INJURY AND EQUIPMENT DAMAGE

HAZARD

Failure to follow this caution may result in personal injury

and / or equipment damage.

DO NOT

 operate the unit without a filter or with grille

removed.

CAUTION

!

COMPLETE PRE

INSTALLATION CHECKS 

Unpack Unit

Move the unit to final location. Remove unit from carton, being

careful not to damage service valves and grilles.

Inspect Shipment

File a claim with the shipping company if shipment is damaged or

incomplete. Check the unit nameplates to ensure units match job

requirements.

Consider System Requirements

Consult local building codes and NEC for special installation

requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant

piping, and servicing unit. Locate unit so that condenser airflow is

unrestricted on both sides.
Unit may be mounted on a level pad directly on base legs or

mounted on raised pads at support points.

RIG AND MOUNT UNIT

Mounting on Ground

Mount unit on a solid, level concrete pad. Position unit so water or

ice from roof does not fall directly onto unit.  Use field

provided

snow stand or ice rack where prolonged subfreezing temperatures

or heavy snow occurs.
If conditions or local codes require unit be fastened to a pad, 6

field

supplied tie

down bolts should be used and fastened through

slots provided in unit mounting feet.

Mounting on Roof

Mount unit on a level platform or frame at least 6 in. (152.4 mm)

above roof surface. Isolate unit and tubing from structure.

Clearance Requirements

Single Unit Applications: With coil facing wall: Allow 6” (152.4

mm) minimum clearance on coil side and coil end and 20” (504.0

mm) minimum clearance on fan side. Allow 24” (609.6 mm)

minimum clearance on compressor end for service.  

With fan facing wall: Allow 8” (203.2 mm) minimum clearance on

fan side and coil end and 20” (504.0 mm) minimum clearance on

coil side. Allow 24” (609.6 mm) minimum clearance on

compressor end for service when units are stacked or there is less

than 40” (1016 mm) of clearance above the unit. If there is 40”

(1016 mm) clearance above unit and the top panel is accessible for

removal allow 8” (203.2 mm) minimum clearance on compressor

end for service.

Multi

unit Applications: Allow 24” (609.6 mm) minimum

clearance between fan and coil sides of multiple units. Arrange

units so discharge of one does not enter inlet of another. Allow 24”

(609.6 mm) minimum clearance on compressor end when units are

stacked or there is less than 40” (1016 mm) of clearance above the

unit. If there is 40” (1016 mm) clearance above unit and the top

panel is accessible for removal allow 8” (203.2 mm) minimum

clearance on compressor end for service.   

When two units are installed end to end with the coil ends facing

each other allow 12” (304.8 mm) minimum clearance between

units.

IMPORTANT

: When installing multiple units, ensure the

discharge air from one unit is not drawn into another unit. When

installing single or multiple units in an alcove, roof well, or

partially enclosed area, ensure there is adequate ventilation to

prevent recirculation of discharge air.

Operating Ambient

Minimum outdoor operating ambient in cooling mode is 55

_

F

(13

_

C), maximum 125

_

F (52

_

C).

Rigging

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this caution may result in personal injury

and/or equipment damage.
Be sure unit panels are securely in place prior to rigging.

CAUTION

!

Keep the unit upright and lift unit using a sling. Use cardboard or

padding under the sling, and spreader bars to prevent sling damage

to the unit. See Fig. 2. Install the unit so that the coil does not face

into prevailing winds. If this is not possible and constant winds

above 25 mph are expected, use accessory wind baffle. See

installation instructions provided with the accessory kit.

NOTE

:  Accessory wind baffles should be used on all units with

accessory low ambient temperature control.
Field

fabricated snow or ice stands may be used to raise unit when

operation will be required during winter months. Units may also be

wall mounted using the accessory wall mounting kit.

A07396

Fig. 2

 - 

Lifting Unit with Sling

Содержание PREFERRED 124ANS

Страница 1: ...teratureand attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand th...

Страница 2: ...n coil side and coil end and 20 504 0 mm minimum clearance on fan side Allow 24 609 6 mm minimum clearance on compressor end for service With fan facing wall Allow 8 203 2 mm minimum clearance on fan side and coil end and 20 504 0 mm minimum clearance on coil side Allow 24 609 6 mm minimum clearance on compressor end for service when units are stacked or there is less than 40 1016 mm of clearance ...

Страница 3: ... system is exposed to the atmosphere Only use factory specified liquid line filter driers with rated working pressures less than 600 psig NOTE Do not install a suction line filter drier in liquid line Make Piping Sweat Connections EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak te...

Страница 4: ...hed indoor unit START UP PRELIMINARY CHECKS 1 Check that all internal wiring connections are tight and that all barriers covers and panels are in place 2 Field electrical power source must agree with unit name plate rating 3 All service valves must be open 4 Belly band crankcase heater must be tight on compressor crankcasefor those units with belly band heaters EVACUATE AND DEHYDRATE Field piping ...

Страница 5: ...accepted heat sink material on the valve before brazing The service valve cannot be field repaired therefore only a complete valve or valve stem seal and service port caps are available for replacement Refrigerant Charging WARNING PERSONAL INJURY AND OR EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result in personal injury and or equipment damage Wear safety glasses and gloves when...

Страница 6: ...d outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical separation See Residential Piping and Long Line Guideline for special charging requirements MAINTENANCE WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main elec...

Отзывы: