Bryant LEGACY PURON 704D Series Скачать руководство пользователя страница 23

23

Table 7 – Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, or high--

pressure, loss--of--charge or low--pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

Thermostat setting too low/too high

Reset thermostat setting

Compressor will not start but condenser fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

Determine cause

Low input voltage

Determine cause and correct

Three--phase scroll compressor (size 030--

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the

060 unit) has a low pressure differential

3--phase power leads to the unit

Compressor cycles (other than normally

satisfying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

Thermostat temperature set too low

Reset thermostat setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

Insufficient coil airflow

Check filter–replace if necessary

Temperature too low in conditioned area

Reset thermostat setting

Outdoor ambient below 55

°

F (13

°

C)

Install low--ambient kit

Filter drier restricted

Replace

704D

Содержание LEGACY PURON 704D Series

Страница 1: ...f this equipment can be hazardous due to mechanical and electrical components Only trained and qualified personnel should install repair or service this equipment Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on this equipment observe precautions in the literatu...

Страница 2: ...Adequate ventilation and outdoor air must be provided The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille Be sure that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a normal house overhang is 48 in 1219 2 mm above...

Страница 3: ...3 A08584 Fig 2 704D024 036 Unit Dimensions 704D ...

Страница 4: ...4 A08585 Fig 3 704D042 060 Unit Dimensions 704D ...

Страница 5: ... Insulate d deck pan Short Support CTyp G E F G D E A05308 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704D024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 CPRFCURB007A00 14 356 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1167 704D042 060 CPRFCURB008A00 8 203 16 3 16 411 17 3 8 441 40 1 4 1022 41 ...

Страница 6: ...event the rigging straps from damaging the unit If the skid is not available use a spreader bar of sufficient length to protect the unit from damage 2 Remove 4 screws in unit corner posts 3 Attach each of the 4 metal rigging brackets under the panel rain lip See Fig 5 Use the screws removed in step 2 above to secure the brackets to the unit PROPERTY DAMAGE HAZARD Failure to follow this warning cou...

Страница 7: ... is installed use fireproof canvas or similar heat resistant material connector between ductwork and unit discharge connection If flexible duct is used insert a sheet metal sleeve inside duct Heat resistant duct connector or sheet metal sleeve must extend 24 in 609 59 mm from electric heater element 3 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater op...

Страница 8: ...in accordance with NFPA 70 NEC latest edition in Canada Canadian Electrical Code CSA C22 1 and local electrical codes WARNING UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NFPA 70 NEC latest edition and local electrical codes governing such wiring In Canada all electrical connections...

Страница 9: ...ire Gage AWG color coded insulated 35 C minimum wires to make the control voltage connections between the thermostat and the unit If the thermostat is located more than 100 ft 30 5 m from the unit as measured along the control voltage wires use no 16 AWG color coded insulated 35 C minimum wires STANDARD CONNECTION Locate the six low voltage thermostat leads in 24 volt splice box See Fig 11 for con...

Страница 10: ...0 10x10 254x254 1 2 1050 1200 11x10 279 4x254 3 4 1000 1400 11x10 279 4x254 3 4 1075 1600 1750 11x10 279 4x254 11x10 279 4x254 1 0 1075 1 0 1040 HIGH PRESSURE SWITCH psig Cut out Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRES SURE SWITCH Liquid Line psig cut out Reset auto 20 5 45 10 RETURN AIR FILTERS Throwaway Size in Throwaway Size mm 20x20x1 508x508x25 20x24x1 508x610x25 24x30x1 610x762x25 2...

Страница 11: ...ant from system and evacuate to 500 microns if no additional leaks are found 5 Charge unit with Puron R 410A refrigerant using a volumetric charging cylinder or accurate scale Refer to unit rating plate for required charge Step 2 Start Up Cooling Section And Make Adjustments Complete the required procedures given in the Pre Start Up section before starting the unit Do not jumper any safety devices...

Страница 12: ...peed ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before changing blower speed WARNING The fan speed of the unit is connected to the HIGH terminal on the interface fan board IFB See Fig 12 13 14 and 15 The unit is factory shipped with a fan speed as noted in Table 4 There are 4 additi...

Страница 13: ... 1980 1945 1905 1864 1793 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 704D060 Med Low Pink CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium1 Red CFM 1962 1915 1880 1843 1794 1753 1711 1675 1628 Med High Orange CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785 High Black CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874 Air delivery values are without air filter and are for dry...

Страница 14: ...14 A08050 Fig 13 Wiring Diagram 208 230 1 60 704D ...

Страница 15: ...15 A08051 Fig 14 Wiring Diagram 208 230 3 60 704D ...

Страница 16: ...16 A08007 Fig 15 Wiring Diagram 460 3 60 704D ...

Страница 17: ...17 A08490 Fig 16 Cooling Charging Chart 704D ...

Страница 18: ...esult in personal injury or death 1 Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit 2 Use extreme caution when removing panels and parts 3 Never place anything combustible either on or in contact with the unit WARNING UNIT OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Erro...

Страница 19: ... fins from inside to outside the unit On units with an outer and inner condenser coil be sure to clean between the coils Be sure to flush all dirt and debris from the unit base Inspect the drain pan and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain trough with clear water Do not splash wa...

Страница 20: ...ystem under pressure it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists If switch must be removed remove and recover all system charge so that pressure gauges read 0 psi 0 Pa Never open system without breaking vacuum with dry nitrogen HIGH PRESSURE SWITCH The high pressure switch is located in the discharge line and protects agains...

Страница 21: ...0 x 10 ft 3 x 3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills prevent run offs and protect drop cloth from tears caused by tools or components 3 Place terry cloth shop towel inside unit immediately under component s to be serviced and prevent lubricant run offs through the louvered openings in the unit base 4 Perform required servic...

Страница 22: ... with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Only use factory specified liquid line filter driers with rated working pressures no less than 600 psig S Do not install a suction line filter drier in liquid line S POE oils absorb moistu...

Страница 23: ...ve compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filte...

Страница 24: ...HTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB PRESSURES REFRIGERANT SUCTION ___________PSIG SUCTION LINE TEMP _________...

Отзывы: