47
Fig. 55 — RTU Open SW3 DIP Switch Settings
Fig. 56 — RTU Open Address Switches
Fig. 57 — Network Wiring
LOCAL ACCESS
Wall Mounted Equipment Touch —The Equipment Touch is a
wall mounted interface used to connect to the RTU Open to ac-
cess the control information, read sensor values, and mainte-
nance. This is an accessory interface that does not come with the
RTU Open controller. Wire the Equipment Touch to the RTU
Open’s J13 local access port. There are 2 password protected
levels in the display (User and Admin). See the Equipment
Touch Installation and Setup Guide for more information. See
Appendix A in the guide for navigation and screen content.
Field Assistant — Field Assistant is a computer program in-
cluded with the purchase of the Tech Tool Kit (USB-TKIT).
This is a field Tech Tool to set-up, service, or download applica-
tion software to the RTU Open controller and includes a USB
Link Cable. The link cable connects a USB port to the J12 local
access port. See Fig. 58.
RTU Open Troubleshooting — Troubleshooting is accom-
plished by viewing the communication LEDs, see Fig. 40. The
LEDs indicate if the controller is speaking to the devices on the
network. The LEDs should reflect communication traffic based
on the baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 23.
NOTE: Refer to the RTU Open Multi-Protocol Controller Con-
trols, Start-Up, Operation, and Troubleshooting manual for
complete configuration of RTU Open, operating sequences and
troubleshooting information. Refer to the RTU Open v3 Integra-
tion Guide for details on configuration and troubleshooting of
connected networks. Have a copy of these manuals available at
unit start-up.
UNU
S
ED
(OFF)
(ON)
COMM
OPTION
PORT
S
ET TO M
S
TP
(MA
S
TER)
S
ET TO
38
.4k
BAUD
PROTOCOL
S
ELECTOR DIP
S
WITCHE
S
Baud Rate Selection
BAUD RATE
DS2
DS1
9,600
OFF
OFF
19,200
ON
OFF
38,400
OFF
ON
76,800
ON
ON
SW3 PROTOCOL SELECTION
LEGEND
NOTE: BACnet MS/TP SW3 example shown.
PROTOCOL
DS8
DS7
DS6
DS5
DS4
DS3
DS2
DS1
BACnet MS/TP (Master)
Unused
OFF
OFF
OFF
ON
OFF
Select Baud
Select Baud
Modbus (Slave)
Unused
OFF
OFF
ON
ON
OFF
Select Baud
Select Baud
N2 Slave
Unused
OFF
OFF
OFF
ON
ON
OFF
OFF
LonWorks
Unused
ON
ON
OFF
ON
OFF
OFF
ON
DS
— DIP Switch
0
1
2
3
4
5
6
7
8
9
MSB
LSB
SW1
SW2
0
1
2
3
4
5
6
7
8
9
J19
NET+
NET
-
S
HLD
Содержание LEGACY 580J*20M Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing 24 and 28 Size Unit cont...
Страница 8: ...8 Fig 4 Unit Dimensional Drawing 30 Size Unit...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing 30 Size Unit cont...
Страница 13: ...13 Fig 8 Roof Curb Details 17 and 20 Size Units 17 20...
Страница 14: ...14 Fig 9 Roof Curb Details 24 and 28 Size Units 24 28...
Страница 15: ...15 Fig 10 Roof Curb Details 30 Size Units 30...
Страница 25: ...25 Fig 33 Typical Perfect Humidity Adaptive Dehumidification System Humidistat Wiring...
Страница 40: ...40 Fig 41 Typical RTU Open System Control Wiring Diagram...
Страница 41: ...41 Fig 42 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System...