48
APPENDIX A
Air Conditioner & Heat Pump with PURON
®
—
Quick Reference Guide
S
Puron
®
(R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are
designed to operate with Puron
®
.
S
Puron
®
refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400
psig, DOT 4BA400 or DOT BW400.
S
Puron
®
systems should be charged with liquid
refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with
compressor operating.
S
Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
S
Use hoses with 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC
refrigerant.
S
Puron
®
, as with other HFCs, is only compatible with
POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
S
Do not install a suction-line filter drier in liquid-line.
S
POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
S
POE oils may cause damage to certain plastics and
roofing materials.
S
Wrap all filter driers and service valves with wet cloth
when brazing.
S
A factory approved, liquid-line filter drier is required on
every unit.
S
Do not use an R-22 TXV.
S
If indoor unit is equipped with a TXV, it must be
changed to a Puron
®
TXV.
S
Never open system to atmosphere while it is under a
vacuum.
S
When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
S
Always replace filter drier after opening system for
service.
S
Do not vent Puron
®
into the atmosphere.
S
Do not use capillary tube coils.
S
Observe all
warnings
,
cautions
, and
bold
text.
S
All Puron
®
heat pumps must have indoor TXV.
S
Do not leave Puron
®
suction line driers in place for
more than 72 hours.
APPENDIX B
Wiring Diagram List
569J* Size
Electrical Characteristics
Diagram Number
07A/B
208/230---3---60
38AU500320
460---3---60
38AU500432
575---3---60
38AU500337
08A/B
208/230---3---60
38AU500320
460---3---60
38AU500432
575---3---60
38AU500337
12A/B
208/230---3---60
38AU500320
460---3---60
38AU500432
575---3---60
38AU500337
14A/B
208/230---3---60
38AU500107
460---3---60
38AU500432
575---3---60
38AU500337
12D/E
208/230---3---60
38AU500562
460---3---60
38AU500563
575---3---60
38AU500564
14D/E
208/230---3---60
38AU500562
460---3---60
38AU500563
575---3---60
38AU500564
569J
Содержание LEGACY 569J
Страница 26: ...26 C10913 Fig 21 569J 07A B Charging Chart Novation C10914 Fig 22 569J 08A B Charging Chart Novation 569J ...
Страница 27: ...27 C10915 Fig 23 569J 12A B Charging Chart Novation C10916 Fig 24 569J 14A B Charging Chart Novation 569J ...
Страница 28: ...28 C10917 Fig 25 569J 12D E Charging Chart Novation 569J ...
Страница 29: ...29 C10918 Fig 26 569J 14D E Charging Chart Novation 569J ...
Страница 30: ...30 C10919 Fig 27 569J 07A B Charging Chart RTPF C10920 Fig 28 569J 08A B Charging Chart RTPF 569J ...
Страница 31: ...31 C10921 Fig 29 569J 12A B Charging Chart RTPF C11093 Fig 30 569J 14A B Charging Chart RTPF 569J ...
Страница 32: ...32 C10923 Fig 31 569J 12D E Charging Chart RTPF 569J ...
Страница 33: ...33 C11094 Fig 32 569J 14D E Charging Chart RTPF 569J ...
Страница 34: ...34 C10925 Fig 33 Typical 569J A B Wiring Diagram 569J ...
Страница 35: ...35 C10926 Fig 34 Typical 569J D E Wiring Diagram 569J ...
Страница 51: ...51 569J 07 08A B 569J 12A B 569J 14A B C11098 Fig 46 569J 07 14A B Motormaster Sensor Location RTPF 569J ...
Страница 52: ...52 569J 12D E 569J 14D E C11099 Fig 47 569J 12 14D E Motormaster Sensor Location RTPF 569J ...
Страница 53: ...53 D K J H G F E C B A C10800 Fig 48 Wind Baffles 569J ...