21

Shorting the jumpers for a period of 5 to 20 seconds bypasses

the remaining continuous run period and places the unit in a

Forced Defrost mode. If the controlling DFT is closed when

this mode is initiated, the unit will complete a normal defrost

period that will terminate when the controlling DFT opens or

the 10 minute defrost cycle limit is reached. If the controlling

DFT is open when this mode is initiated, the Defrost cycle will

run for 30 seconds. Both modes end at the end of the Defrost

cycle.

Fig. 37 — DIP Switch Settings - Defrost Board

UNIT WITHOUT THRU-BASE CONNECTION KIT
Pass the thermostat control wires through the bushing on the

unit end panel. Route the wire through the snap-in wire tie and

up  to  the web  bushing  near  the  control  box.  Route  the  wire

through the bushing and into the bottom left side of the control

box after removing one of the two knockouts in the corner of

the box.  Using  a connector at  the  control box to  protect  the

wire as it passes into the control box. Pull the wires over to the

terminal strip at the upper left corner of the Central Terminal

Board  (CTB).  Use  the  connector  at  the  control  box  and  the

wire tie to ensure that the thermostat wire is tight and will not

be damaged by contact with the condenser coil. See Fig. 38.

NOTE: If thru-the-bottom connections accessory is used, refer to

the accessory installation instructions for information on routing

power and control wiring.

Fig. 38 — Thermostat Wire Routing

HEAT ANTICIPATOR SETTINGS
Set heat anticipator settings at 0.14 amp for the first stage and

0.14 amp for second-stage heating, when available.
ELECTRIC HEATERS
The 549J units may be equipped with field-installed accessory

electric heaters. The heaters are modular in design, with heater

frames holding open coil resistance wires strung through ce

-

ramic insulators, line-break limit switches and a control con

-

tactor. One or two heater modules may be used in a unit.

Heater modules are installed in the compartment below the in

-

door (supply) fan outlet. Access is through the indoor access

panel.  Heater  modules  slide  into  the  compartment  on  tracks

along the bottom of the heater opening. See Fig. 39.

CAUTION

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

Not  all  available  heater  modules  and  single  point  boxes

may be used in every unit. Use only those heater modules

that are UL listed for use in a specific size unit. Refer to the

label on the unit cabinet for the list of approved heaters and

single point boxes.

Содержание Legacy 549J 12 Series

Страница 1: ...NG DIAGRAMS EconoMi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS S BUS SENSOR WIRING CO2 SENSOR WIRING INTERFACE OVERVIEW SETUP...

Страница 2: ...wer switch to unit and install lock s and lockout tag s Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate Unit may have more than one power swi...

Страница 3: ...Indoor Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N Precoat Al Cu Al Cu Louvered Hail...

Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 12 Units...

Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 12 Units cont...

Страница 6: ...ITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance Minimum clearance B 42 in 1067 mm...

Страница 7: ...om O ring Install the fitting body and torque to 96 10 in lb 10 9 1 Nm Do not exceed 106 in lb 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following checks before installation 1 C...

Страница 8: ...ME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required to suit spe cific installation plan Step 3 Inspect Unit Inspect...

Страница 9: ...9 Fig 6 Roof Curb Details REV 50TM500827...

Страница 10: ...al information Lifting holes are provided in base rails as shown in Fig 8 Re fer to rigging instructions on unit Before setting the unit onto the curb recheck gasketing on curb Rigging materials under...

Страница 11: ...iguration using accessory CRDUCTCV001A00 To convert to horizontal configuration remove screws from side duct opening covers see Fig 10 and remove covers Discard the supply duct cov er Install accessor...

Страница 12: ...to the basepan and remove In order to remove the screws it may be nec essary to remove the panel underneath the two position damper Locate and cut the 2 plastic tie wraps securing the assembly to the...

Страница 13: ...rflow configuration does not deter mine which drain connection to use Either drain connection can be used with vertical or horizontal applications When using the standard side drain connection ensure...

Страница 14: ...disconnects be sure to use 1 2 in screws to mount the disconnect directly to the end panel following the instruc tions on the Field Disconnect Warning label see Fig 25 In either case set the disconnec...

Страница 15: ...2 0 AWG copper only per pole Provide a ground fault and short circuit over current protection device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Ma...

Страница 16: ...he pointer to be 3 75 to 3 88 in 95 to 99 mm for 80A and 100A NFD and 3 43 to 3 56 in 87 to 90 mm for 200A NFD 7 Tighten the locking screw to secure the shaft to the NFD 8 Turn the handle to the OFF p...

Страница 17: ...t side of the disconnect Be sure to create a drip loop at least 6 in long Fig 31 Powered Convenience Outlet Wiring Duty Cycle The unit powered convenience outlet has a duty cycle limita tion The trans...

Страница 18: ...duit between disconnect and control box 2 Install power lines to terminal connections as shown in Fig 26 FIELD CONTROL WIRING The 549J unit requires an external temperature control device This device...

Страница 19: ...ycle de mand is received Once de energized at the start of a Heating cy cle the reversing valves will remain de energized until the next cooling stage is initiated Compressor control The DFB receives...

Страница 20: ...see Fig 37 and Table 7 The de fault run period is 60 minutes for size 12 units Table 6 549J Defrost Board I O and Jumper Configurations POINT NAME TYPE OF I O CONNECTION PIN NUMBER UNIT CONNECTION NOT...

Страница 21: ...tie to ensure that the thermostat wire is tight and will not be damaged by contact with the condenser coil See Fig 38 NOTE If thru the bottom connections accessory is used refer to the accessory insta...

Страница 22: ...t Use the wiring procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange and a brown control wire Conne...

Страница 23: ...ory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temperature switch between second and...

Страница 24: ...24 Fig 42 Typical 549J Control Wiring Diagram...

Страница 25: ...25 Fig 43 Typical 549J Power Wiring Diagram 208 230 3 60 unit shown...

Страница 26: ...26 Fig 44 RTU Open Controller System Wiring Diagram...

Страница 27: ...are available with bus sensors User Interface The interface provides status for normal operation setup pa rameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display...

Страница 28: ...ft Terminal Block IAQ 2 10 2 10 VDC Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 VAC Air Quality Sensor 24 VAC Source ACT 2 10 2 10 VDC Damper Actuator Outp...

Страница 29: ...the list of menus Fig 49 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Advanced Settings Checkout tests and Alarms 1 Navigate to the desired menu 2 Press...

Страница 30: ...L HEAT HEAT PUMP MODE Displays COOL or HEAT when system is set to heat pump Non conventional COOL Y1 IN OFF ON OFF FIRST STAGE COOLING DEMAND Y1 IN Y1 I signal from space thermostat or unitary control...

Страница 31: ...F 43 C to 27 C increment by 1 F COMPRESSOR LOW TEMPERATURE LOCKOUT Set point determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor locko...

Страница 32: ...e capacity of the RTU The value is found on the nameplate label for the specific unit AUX1 OUT NONE NONE ERV EXH2 SYS Select OUTPUT for AUX1 O relay NONE not configured output is not used ERV Energy R...

Страница 33: ...n damper to the full open position Exhaust fan contacts enable during the DAMPER OPEN test Make sure to pause in the mode to allow exhaust contacts to energize due to the delay in the system DAMPER CL...

Страница 34: ...ce actuator if damper is movable and supply voltage is between 21 6 V and 26 4 V Check actuator count on STATUS menu FREEZE ALARM N A N A Check if outdoor temperature is below the LOW Temp Lockout on...

Страница 35: ...2 Sensor 1 Speed Fan DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMI...

Страница 36: ...On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Off VENTMIN to Full Open Closed to Full Open Above Set No Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX C...

Страница 37: ...ll Open Closed to Full Open On On High DELAY 24 v On 0 v Off MIN POS H to Full Open Closed to Full Open Table 21 Enthalpy Operation with Demand Controlled Ventilation DCV CO2 Sensor 2 Speed Fan DCV OU...

Страница 38: ...ation wiring dia grams For checkout review the Status of each configured pa rameter and perform the Checkout tests For information about menu navigation and use of the keypad see Interface Overview on...

Страница 39: ...n air smoke detectors are ar ranged for vertical return configurations only All components necessary for operation are factory provided and mounted The unit is factory configured for immediate smoke d...

Страница 40: ...ols Connec tions Board at terminals marked Smoke Shutdown Cut jumper JMP 3 when ready to energize unit ECONOMI ER IV OCCUPANCY SWITCH See Fig 53 for general EconoMi er IV wiring External occu pancy co...

Страница 41: ...the fan to increase ten sion Ensure the blower shaft and motor shaft are parallel to each other pulleys aligned Tighten all bolts securely when finished BELT TENSION METHOD Requires belt tension gage...

Страница 42: ...rves the right to change at any time specifications and designs without notice and without obligations Replaces II549J 12 02 2020 Carrier Cat No 04 53549013 01 Edition Date 6 2020 Printed in U S A For...

Страница 43: ...N _____ Verify that unit is level Y N _____ Check fan wheels and propeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are prop...

Страница 44: ..._ L3 _____________ Supply Fan Amps L1 _____________ L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _______...