—12—

 

ACCESSORY LIST

ACCESSORY KITS DESCRIPTION

SUGGESTED AND REQUIRED USE

 

1.

 

Disconnect Kit 

 

The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely. 

SUGGESTED USE: FE4 units with 3- through 10-kW electric resistance heaters and cooling controls.

2.

 

Downflow Conversion Kit 

 

Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water 
drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils.

 

REQUIRED USE:

 

 This kit must be used whenever FE4 fan coils are used in downflow applications.

3.

 

Downflow Base Kit 

 

This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides 
a gap free seal with the floor.

 

REQUIRED USE:

 

 This kit must be used whenever FE4 fan coils are used in downflow applications.

4.

 

Single-Point Wiring Kit 

 

The single-point wiring kit acts as a jumper between L1 and L3 lugs, and between L2 and L4 lugs. This allows the installer to run 2 heavy-gage, 
high-voltage wires into the fan coil rather than 4 light-gage, high-voltage wires. 

SUGGESTED USE: FE4 fan coils with 15- and 20-kW fused heaters only.

5.

 

Air Cleaner 240-Volt Conversion Kit 

 

The AIRA electronic air cleaner comes ready for 115-v operation. 

 

REQUIRED USE: 

 

This kit is required when running 240-volt circuit to air cleaner.

6.

 

Airflow Sensor Kit (Air Cleaner) 

 

The airflow sensor kit ensures the FE4 fan coil and electronic air cleaner work as a system. 

 

REQUIRED USE: 

 

This kit is required whenever an electronic air cleaner is used with an FE4 fan coil.

7.

 

Fan Coil Filter 

 

Kit shipped from factory with 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents 
them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system. 

SUGGESTED USE: For replacing factory-supplied filters (same filters).

8.

 

Condensate Drain Trap Kit 

 

This kit consists of 50 PVC condensate traps. Each trap is pre-formed and ready for field installation. This deep trap helps the system make and 
hold proper condensate flow even during blower initiation. 

SUGGESTED USE: FE4 fan coils.

9.

 

Downflow/Horizontal Conversion Gasket Kit 

 

This kit provides the proper gasketing of units when applied in either a Downflow or Horizontal application.

 

REQUIRED USE:

 

 F

E

4 fan coils.

 

ITEM

ACCESSORY PART NO.

FAN COIL SIZE USED WITH FE4A

 

Disconnect Kit

KFADK0201DSC 

Cooling controls and heaters through 10-kW

Downflow Conversion Kit (Slope)

KFADC0201SLP

003

Downflow Conversion Kit (A-coil)

KFADC0401ACL

002, 005, 006

Downflow Base Kit

KFACB0201CFB

002

KFACB0301CFB

003, 005

KFACB0401CFB

006

Filter Kit (12 Pack)

KFAFK0212MED

002

KFAFK0312LRG

003, 005

KFAFK0412XXL

006

Single-Point Wiring Kit

KFASP0101SPK

Only with 15- and 20-kW Fused Heaters

Airflow Sensor Kit (Air Cleaner)

KEAAC0101AAA

All

Air Cleaner 240-Volt Conversion Kit

KEAVC0201240

All

PVC Condensate Drain Trap Kit (50 Pack)

KFAET0150ETK

All

Downflow/Horizontal Conversion Gasket Kit

KFAHD0101SLP

All

Содержание FE4A

Страница 1: ...unds from sudden changes in airflow are reduced for worry free comfort When used in continuous fan mode the FE4A can operate quietly at very low levels of airflow for gentle reduction of temperature differences between areas of the home and within each individual room from floor to ceiling In addition when used in conjunction with Bryant air cleaners the FE4A provides continual cleansing of the ai...

Страница 2: ...igorous than Air Conditioning and Refrigeration Institute requirements Super thick insulation with vapor barrier Galvanized pre painted cabinet Installation flexible multipoise units Horizontal hanging provisions on cabinet Factory supplied cleanable and reusable filter Newly improved filter rack filter insulation added for an improved air seal No tools required to service filter 5 through 30 kw a...

Страница 3: ...NT Puron R 410A Refr Metering Device TXV Size 2 Ton 3 Ton 4 Ton 4 Ton COIL Type A Slope A A Rows Fins In 3 14 5 Face Area sq ft 3 46 3 46 5 93 7 42 MATCHES OUTDOOR UNIT SIZES Nominal Cooling Tons 1 5 2 2 5 3 2 2 5 3 3 5 2 5 3 3 5 4 3 3 5 4 5 FAN Upflow Downflow Horizontal Air Discharge CFM TON Nominal 350 MOTOR HP ECM 1 2 1 2 1 2 3 4 FILTER 21 1 2 x 16 3 8 21 1 2 x 18 7 8 21 1 2 x 18 7 8 21 1 2 x ...

Страница 4: ...H J In In In In In In In FE4A 002 42 11 16 17 5 8 15 3 4 15 5 8 10 3 4 003 53 7 16 21 1 8 19 1 4 19 1 8 19 3 16 19 005 53 7 16 21 1 8 19 1 4 19 1 8 19 1 2 006 59 3 16 24 11 16 22 3 4 22 11 16 25 1 4 34 1 16 A02321 DIMENSIONS ...

Страница 5: ...2322 DIMENSIONS Continued UNIT SIZE F G COIL CONFIGURATION SHIPPING WEIGHT In In SLOPE A Lb FE4A 002 18 9 16 18 1 4 Yes 135 003 26 15 16 27 1 2 Yes 150 005 27 1 4 26 15 16 Yes 172 006 32 15 16 32 5 8 Yes 207 ...

Страница 6: ...rflow at a rate that is requested by the Integrated System User Interface during Air Conditioning or Heat Pump Heating without electric heat modes The nominal airflow for both heating and cooling modes is 350 cfm ton nominal refrigeration size of the outdoor unit installed The airflow actually requested by the User Interface is modified by its internal algorithms for zoning comfort or efficiency c...

Страница 7: ... 018 024 030 036 625 650 675 850 1000 650 650 775 950 1050 825 900 1050 1125 1025 1125 1225 003 Heater Only 024 030 036 042 675 675 850 1025 1150 725 875 950 1075 1200 850 1100 1150 1300 1100 1150 1275 1400 005 Heater Only 030 036 042 048 675 850 1025 1150 1325 725 950 1075 1200 1325 850 1100 1150 1300 1400 1100 1150 1275 1400 1500 1400 1600 006 Heater Only 036 042 048 060 1050 1150 1150 1325 1650...

Страница 8: ...IC PRESSURE IN W C TOO HIGH RETURN STATIC PRESSURE DIFFICULT TO MAKE TRAP ACCEPTABLE RANGE A96052 Acceptable Duct Conditions For satisfactory operation specifically making dry secondary trap subject fan coils must be installed with duct systems which fall within the Acceptable Range illustrated above ...

Страница 9: ...0 36 29 40 25 23 0 25 35 39 42 32 36 38 29 32 33 26 28 29 22 23 23 1400 80 67 54 73 59 46 64 49 38 54 39 32 43 28 27 0 27 38 43 47 35 39 43 32 36 37 28 32 32 24 26 27 005 750 61 49 39 55 43 33 48 37 27 41 29 20 33 21 17 0 04 27 27 28 24 25 25 21 22 22 18 18 18 15 15 15 950 74 60 48 67 53 40 59 45 33 50 35 25 39 24 21 0 06 32 34 35 29 30 31 25 26 27 22 23 23 18 18 19 1150 89 72 57 79 63 48 69 52 38...

Страница 10: ...IONS OCTAVE BAND CENTER FREQUENCY CFM ESP 63 125 250 500 1000 2000 4000 FE4 002 400 0 25 63 0 59 0 55 0 52 0 50 0 48 0 44 0 600 0 25 64 7 60 7 56 7 53 7 51 7 49 7 45 7 800 0 25 66 0 62 0 58 0 55 0 53 0 51 0 47 0 1000 0 25 67 0 63 0 59 0 56 0 54 0 52 0 48 0 1200 0 25 67 8 63 8 59 8 56 8 54 8 52 8 48 8 1400 0 25 68 4 64 4 60 4 57 4 55 4 53 4 49 4 FE4 003 1400 0 25 63 0 59 0 55 0 52 0 50 0 48 0 44 0 ...

Страница 11: ...en that component or condition is used The remaining external static pressure will be available for the duct system HEATER KW ELEMENTS STATIC PRESSURE CORRECTION in wc Sizes 002 005 Size 006 0 0 02 03 5 1 01 02 8 10 2 0 0 9 15 3 02 03 20 4 04 06 18 24 30 6 06 10 MODEL FE4A CFM 400 600 800 1000 1200 1400 1600 1800 2000 002 0 020 0 044 0 048 0 072 0 100 003 0 020 0 035 0 051 0 070 0 092 005 0 035 0 ...

Страница 12: ... Cleaner The airflow sensor kit ensures the FE4 fan coil and electronic air cleaner work as a system REQUIRED USE This kit is required whenever an electronic air cleaner is used with an FE4 fan coil 7 Fan Coil Filter Kit shipped from factory with 12 fan coil framed filters These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the ...

Страница 13: ...8 230 1 4 3 5 4 14 15 003 208 230 1 4 3 5 4 14 15 005 208 230 1 4 3 5 4 14 15 006 208 230 1 6 8 8 5 14 15 HEATER PART NO KW 240V VOLTS PHASE STAGES KW OPERATING INTERNAL CIRCUIT PROTECTION FAN COIL SIZE USED WITH HEATING CAP 230V INTELLIGENT HEAT CAPABLE KW OPERATING KFCEH0501N05 5 230 1 5 None All 15 700 KFCEH0901N10 10 230 1 10 None All 31 400 KFCEH3001F15 15 230 1 5 15 Fuses All 47 100 5 10 15 ...

Страница 14: ... 53 5 8 6 10 10 50 60 54 87 9 6 8 3 None 18 8 20 8 32 0 34 5 8 8 10 10 35 35 83 85 KFCEH0901N10 10 7 5 1 None 36 2 40 0 53 8 58 5 6 6 10 10 60 60 78 80 KFCEH2601C10 10 7 5 1 Ckt Bkr 36 2 40 0 53 8 58 5 6 6 10 10 60 60 78 80 KFCEH3001F15 15 11 3 1 Fuse 54 2 59 9 36 2 40 0 18 1 20 0 76 3 83 4 53 8 58 5 22 7 25 0 4 4 6 6 10 10 8 8 10 10 10 10 80 90 60 60 25 25 88 89 78 80 75 76 KFCEH3101C15 15 11 3 1...

Страница 15: ... 15 ...

Страница 16: ...NSTALLATION INSTRUCTIONS Cancels New Form PDS FE4A 18 1 2003 Bryant Heating Cooling Systems 7310 W Morris St Indpls IN 46231 PRINTED IN U S A Catalog No 12FE 4A0 12 03 MATCHED SYSTEM ELECTRONIC AIR CLEANER VENTILATOR PLUS ZONE PERFECT PLUS EQUIPMENT CONTROLLER HEAT PUMP HUMIDIFIER FAN COIL A02295 ...

Отзывы: