44
6.3.5.
Heat Source Lockout
First touch
SETUP
, then touch
HEAT SOURCE LOCKOUTS
to set up the
parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the lockout
temperatures below the which only the hydronic coil will operate, and the lockout
temperature above which the hydronic coil will not operate. After the selections are
made, touch
SAVE
.
A12149
S
HP Lockout:
Adjustable from --20 to 55
_
F (--28 to 13
_
C) or None
d
Default = None
S
Furnace, Electric Heat or Hydronic Lockout:
Adjustable from 15 to 55
_
F
(--9 to 13
_
C) or None
d
Default = None
S
Defrost with Furnace, Electric Heat or Hydronic:
Yes or No
d
Default = Yes
6.3.6. Stages / Latch for Evolution V
For Evolution V heat pumps, the cooling and heating stage/latch can be changed.
Select cooling or heating next to stages/latch. The maximum stage and the
minimum stage can be selected. The minimum selected stage can be locked--in or
set based upon the outside temperature. See screen shots below.