manualshive.com logo in svg
background image

SYSTXBBECW01--A, SYSTXBBECN01--A

& SYSTXBBECC01--A

Evolution

r

Connex

t

Control

Installation Instructions

A12479

NOTE

: Read the entire instruction manual before starting the installation.

The features and functions outlined in the Installation Instructions reflect Version 11

software. See the Evolution Connex product page on the HVACPartner.com
website or the Downloads section of the www.MyEvolutionConnex.Bryant.com

website for the latest software release.

US Patents: Carrier U.S. Pat No. 7,243,004, Carrier U.S. Pat No. 7,775,452, pointSET

t

U.S.

Pat No. 7,415,102

Содержание Evolution Connex SYSTXBBECC01-A

Страница 1: ...tion The features and functions outlined in the Installation Instructions reflect Version 11 software See the Evolution Connex product page on the HVACPartner com website or the Downloads section of the www MyEvolutionConnex Bryant com website for the latest software release US Patents Carrier U S Pat No 7 243 004 Carrier U S Pat No 7 775 452 pointSETt U S Pat No 7 415 102 ...

Страница 2: ......

Страница 3: ...me Zone 4 3 1 3 Enable Time Synchronization 4 3 2 Set Dealer Information 5 4 Installation 6 4 1 Overview 6 4 2 Check Equipment 6 4 3 Location 7 4 3 1 Wall Control 7 4 3 2 Remote Room Sensors 8 4 3 2 1 Remote Room Sensor Averaging 8 4 3 3 Smart Sensors for zoning applications 9 4 4 Wiring Considerations 9 4 4 1 Shielded Wire 12 4 4 2 Damper Control Module 13 ...

Страница 4: ...earching for Outdoor Unit 17 5 3 Indoor Evaporator Selection 18 5 4 Electric Heater Selection 18 5 4 1 Hydronic Heat Application 19 5 5 Searching SAM Module If Applicable 20 5 6 Searching for Zones If Applicable 20 5 7 Filter Type Selection 21 5 8 Humidifier Installation 21 5 9 Ultraviolet Lights Installation 21 5 10 Equipment Summary 21 5 11 Airflow Verification Check 22 5 12 Duct Assessment zoni...

Страница 5: ...up 28 6 3 1 2 Heat Cool Deadband 28 6 3 1 3 Offsets 28 6 3 1 4 Reset factory defaults 29 6 3 1 5 Scheduling Enable 29 6 3 1 6 Smart Recovery Enable 29 6 3 2 Fan Coil 29 6 3 2 1 Airflow 30 6 3 2 2 Altitude 31 6 3 2 3 Fan Coil Dehumidification 31 6 3 2 4 Fan Coil G Terminal 32 6 3 2 5 Fan Coil G Terminal Alert 32 6 3 2 6 Fan Coil G Terminal Label 33 ...

Страница 6: ...nace Off Delay 37 6 3 3 6 Altitude 37 6 3 3 7 Furnace Dehumidifier Drain 38 6 3 3 8 Furnace G Terminal 38 6 3 3 9 Furnace G Terminal Alert 39 6 3 3 10 Furnace G Terminal Alert Label 39 6 3 4 AC Heat Pump 40 6 3 4 1 Latching 40 6 3 4 2 Cooling Lockout 41 6 3 4 3 Defrost Interval 42 6 3 4 4 Low Ambient Cooling 42 6 3 4 5 Quiet Shift 42 6 3 4 6 AC Heat Pump RPM Max 42 6 3 4 7 Defrost Fan Delay 43 ...

Страница 7: ...oning If Applicable 45 6 3 7 1 Zoning Disable 45 6 3 7 2 Zone Offsets 46 6 3 7 3 Zone Airflow Limits 46 6 3 7 4 Duct Assessment Time 46 6 3 8 Accessories 47 6 3 8 1 Filter 47 6 3 8 2 Humidifier 48 6 3 8 3 Ultraviolet Lights 48 6 3 8 4 Ventilator 48 6 3 9 Utility Curtailment 49 6 3 10 Hydronic Airflow 49 6 4 Check out 50 6 4 1 Electric Heat 51 6 4 2 Furnace 51 ...

Страница 8: ...tilator 55 6 4 9 Zoning If Applicable 55 6 4 9 1 Airflow Limits 55 6 4 9 2 Damper Sensor Check 55 6 4 9 3 Zone Duct Assessment 56 6 4 9 4 Sensor Type 56 6 5 Service Information 56 6 5 1 Advanced Diagnostics 57 6 5 2 Fan Coil Status 57 6 5 3 Furnace Status 58 6 5 4 AC Status 58 6 5 5 Heat Pump Status 59 6 5 6 Zoning Status 59 6 5 7 Last 10 System Events 60 ...

Страница 9: ... 2 Pump down 64 6 6 3 Evacuation 64 6 7 Refrigerant Charging Evolution V 65 6 7 1 Charging 66 6 7 2 Pump down 67 6 7 3 Evacuation 67 6 7 4 EXV Position 68 6 8 Dealer Logo 68 6 9 Utility Event Setup 69 7 Wireless Setup 70 7 1 SYSTXBBECC01 A Model only 71 7 2 SYSTXBBECW01 A Model only 74 8 Appendix A Wiring Diagrams 79 NOTE See the Owner s Manual for information regarding software upgrades ...

Страница 10: ......

Страница 11: ...A 70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in s...

Страница 12: ...need for separate wall control When using conventional single stage outdoor units the Evolution furnace or fan coil provides the 24 volt signals needed to control them Also the Evolutionr Network Interface Module P N SYSTXBBNIM01 allows connection of a Bryant HRV or ERV without the need for separate wall control All system components are controlled through the wall mounted Evolution Connex Control...

Страница 13: ...just Time and Date d To set the HOUR MINUTE MONTH DAY or YEAR touch the feature you wish to change d Use the Up Y and Down B buttons to make the appropriate changes d When you have completed all of the settings touch SAVE A14216 ...

Страница 14: ...lect the time zone for the location Time zones for both US and Canada are included A14217 3 1 3 Enable Time Synchronization After setting up the time zone the time synchronization can then be done Both setting the time zone and enabling time synchronization must be done in order to enable time synchronization ...

Страница 15: ...ication save it to a standard USB drive See Section 6 7 S Touch the SERVICE icon for about 10 seconds then touch DEALER LOGO UPLOAD S Place the USB drive into the USB port on the bottom of the Evolution Connex Control and follow the on screen prompts S More detailed information can be found on HVACPartners com under the Product tab Thermostats Controls SYSTXBBECW01 Documents Downloads Marketing Mi...

Страница 16: ...ng the system once all physical components are installed Special screen prompts and start up capabilities are provided in the Evolution System to simplify and automate the initial commissioning of the system S Install the Evolution Connex Control according to this instruction S Install indoor unit outdoor unit and accessories according to their instructions S Wire complete system according to this...

Страница 17: ... user For accurate temperature measurement the following guidelines should be followed The Evolution Connex Control and Remote Room Sensors SHOULD be mounted S Approximately 5 ft 1 5 m from the floor S Close to or in a frequently used room preferably on an inside partitioning wall S On a section of wall without pipes or ductwork The Evolution Connex Control and Remote Room Sensors SHOULD NOT be mo...

Страница 18: ...al block connectors labeled S1 and S2 at the control s backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Evolution Connex Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor 4 3 2 1 Remote Room Sensor Averaging Typically one remote sensor is used but multiple sensors may be used and averaged in some applications...

Страница 19: ... per zone They cannot be averaged like Remote Room Sensors If a Smart Sensor is used in a zone a Remote Room Sensor may also be used in the same zone The Remote Room Sensor has priority over the Smart Sensor The Smart Sensor will display the Remote Room Sensor temperature NOTE Smart Sensors must be addressed to identify which zone it will control See Smart Sensor Installation Instructions for deta...

Страница 20: ...ed ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B C White 24VAC Com D Red 24VAC Hot A B C D A03193 It is not mandatory that the above color code be used but each ABCD connector in the system MUST be wired consistently NOTE Some outdoor units provide their own low voltage power source and do not require the C 24VAC common and D 24...

Страница 21: ...connect wires from existing control d Discard or recycle old control S NOTE Mercury is a hazardous waste if existing control contains any mercury it MUST be disposed of properly The Evolution Connex Control does not contain mercury S Select Evolution Control mounting plastic backplate and decorative backplate if desired S Route wires through large hole in mounting plastic Level rear plastic agains...

Страница 22: ...d Wire If the thermostat wiring will be located near or in parallel with high voltage wiring radio TV or Ethernet wiring then four conductor twisted pair shielded cable can be used to reduce or eliminate potential interference The shield wire should be connected to the C terminal or ground at the indoor unit The shield wire should NOT be connected to any terminal at the user interface Connecting t...

Страница 23: ...sation The cover must be installed to prevent damage from other sources Do not locate where it will be accessible to children It may be mounted in either vertical or horizontal position Remember that wiring access is likely the most important consideration PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury To prevent possible damage to the Damper Control Module DO ...

Страница 24: ... bend or break the interlocking tabs when removing 4 5 1 Decorative Backplate Sold separately a thin decorative backplate is available to hide any marks screw holes left from the previous thermostat This decorative backplate or beauty ring is used by snapping it onto the back of the mounting plate before securing the plate to the wall ...

Страница 25: ...Bypass Humidifier A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals The Evolution Control Connex will automatically energize the HUM output during a call for humidification 4 6 2 Fan Powered Humidifiers Most fan powered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure For this application a 24VAC N O Isolatio...

Страница 26: ...oil with a 2 stage air conditioner heat pump including Hybrid Heatr dual fuel system 5 1 Searching for Indoor Unit The Evolutionr Connex Control will light up and begin the commissioning process by displaying Searching for indoor unit This includes Evolutionr small packaged products SPP with UI Version 8 0 software or later A12177 NOTE If the Evolution compatible indoor equipment furnace or fan co...

Страница 27: ...utdoor unit not found S Select the appropriate unit installed then touch NEXT d AC1Stage 1 stage air conditioner d AC2Stage 2 stage air conditioner d HP1Stage 1 stage heat pump d HP2Stage 2 stage heat pump d None No outdoor unit installed NOTE For small packaged products SPP the selection screen is not needed and will not appear S The installer will first be instructed to select the appropriate si...

Страница 28: ...y calculate the refrigerant charge required while in the heat pump charging screens under the Heat Pump Checkout menu See Pg 54 Select other for non Bryant evaporators 5 4 Electric Heater Selection If the indoor equipment is a fan coil the control will display Searching for heater until one is found If the electric heater is not self identifying the select heater screen will appear Touch the appro...

Страница 29: ...iant hot water heat In either application a Hydronic Heat kit should be installed in place of an electric heater See FE fan coil Product Data for accessory part number The system will self identify that hydronic heat has been installed during electric heater selection The system will treat the hot water coil as either auxiliary heat in a heat pump application or the sole heat source Setup options ...

Страница 30: ...on of the application specification entitled Carrier Communicating HVAC System Version 2 or later available on HVACpartners com or the System Access Module Installation Instructions 5 6 Searching for Zones If Applicable This function is not available with the 986T furnace Zoning Searching will appear on the screen to determine if any zones are present The screen will show Zone 1 Zone 2 etc and ind...

Страница 31: ...er 5 8 Humidifier Installation Next the installer will be prompted to select whether a humidifier is installed in the system Select YES or NO then touch NEXT 5 9 Ultraviolet Lights Installation Next the installer will be prompted to select whether ultraviolet lights are installed in the system Select YES or NO then touch NEXT 5 10 Equipment Summary The equipment summary screen will appear after ac...

Страница 32: ...ng will appear but equipment operation and the TrueSenset dirty filter detection operation will not be affected When the airflow verification check is complete touch NEXT NOTE The airflow verification check occurs only at initial installation or when INSTALL is run in the INSTALL SERVICE menu 5 12 Duct Assessment zoning applications only The duct assessment screen will be displayed next for zoning...

Страница 33: ...ll then close all zones and open one zone at a time taking a static pressure measurement for each zone The system will then close all zones and take a pressure measurement getting a value for the duct leakage up to and through the dampers With these static pressure measurements the system will calculate the relative size of each zone as well as the percent leakage through the dampers At the end of...

Страница 34: ...uch and hold the SERVICE icon for at least ten seconds The following screens are available in installation and service To return to the previous screen touch BACK To exit the Service menus touch DONE NOTE See the Owner s Manual for information regarding software upgrades NOTE The user selection of temperature units affects the user screens only The service screens use degree F only The user select...

Страница 35: ... the Service menus touch DONE Example SPP Equipment Summary Screen A13128 6 2 Installation Touch INSTALLATION to perform the start up process in order to learn all equipment in system Press right side button to initiate the process Touch NEXT to begin the process Touch Airflow Verification Test to perform a duct assessment This can be done if duct modifications have been made since installation of...

Страница 36: ...ection 6 4 and Service Section 6 5 For PAC AC Indoor and OAC HP Indoor follow Fan Coil instructions For Gas PAC Indoor and Gas PHP Indoor follow Furnace instructions For all PAC Outdoor follow AC Heat Pump instructions 6 3 Set up A13130 NOTE Depending upon the equipment installed the following options will be displayed ...

Страница 37: ...or S Outdoor d AC Heat pump d PAC AC outdoor d PAC HP outdoor d GAS PAC outdoor d GAS PHP outdoor Once the equipment has been selected the appropriate menus will be displayed 6 3 1 Thermostat First touch SETUP then touch THERMOSTAT to set up the parameters for the Evolutionr Connex Control A13233 ...

Страница 38: ...en Fahrenheit _F and Celsius _C Ex A 2_ deadband will be 2_F or 2_C and does not change with units _F and _C This can allow one setting to push the other to maintain this difference When the correct deadband is set touch SAVE S Deadband Adjustable from 0 to 6_ F d Default 2_ 6 3 1 3 Offsets This option allows calibration or deliberate miscalibration of the temperature and humidity sensors These of...

Страница 39: ...6 3 1 5 Scheduling Enable This option lets the installer allow programming features After the selection is made touch SAVE S Scheduling On or Off d Default On 6 3 1 6 Smart Recovery Enable Applies to programmable operation only Will start recovery 90 minutes prior to schedule change in both heating and cooling mode After the selection is made touch SAVE S Smart Recovery On or Off d Default On NOTE...

Страница 40: ...airflow used to achieve specified ratings no dehumidification airflow reduction is performed This is nominally 325 CFM ton but will vary if a 2 stage outdoor unit is used The EFF350 airflow is a fixed airflow used to achieve specified ratings no dehumidification airflow reduction is performed This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used The MAX airflow is a fixed 4...

Страница 41: ...water The fan will only be turned off if a dehumidify demand existed at the start of or during the cooling cycle The Electric Reheat option enables the electric heat to be used while cool to dehumidify is running This will allow the cool to dehumidify function to run longer greatly improving humidity control in cooling mode Accumulated electrical energy used while reheating in kilowatt hours is sh...

Страница 42: ...inal is energized Use the alert function to select the contact state for an alert Select Normally Open or Normally Closed and then save your selection Shutdown shuts off fan and equipment when initiated After the selections are made touch Save A13229 6 3 2 5 Fan Coil G Terminal Alert Use the alert function to select the contact state for an alert Select Normally Open or Normally Closed and then sa...

Страница 43: ... for shutdown Select Normally Open or Normally Closed and then save your selection A13231 6 3 2 6 Fan Coil G Terminal Alert Label Once the G Terminal Alert label has been entered it is shown both on the main screen and in the notification email when the alert becomes active ...

Страница 44: ...34 A14224 6 3 3 Furnace First touch SETUP then touch FURNACE to set up the parameters for the furnace unit A14225 ...

Страница 45: ...ing airflow that the system can safely run typically 300 CFM ton Use this setting if duct noise is a severe problem Note that duct sweating in high humidity environments could become an issue at low airflows The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings This selection enables the full dehumidify and comfort capabilities of the system The EFF325 a...

Страница 46: ...l vary based on the furnace installed SYSTEM setting will allow the Evolutionr Zone Control to determine furnace staging FURNACE setting will allow the furnace to determine staging LOW will only run the low stage of furnace heat LOW MED will run the low and medium stages 2 stages of heat MED will only run the medium stage of heat MED HIGH will run the medium and high stages 2 stages of heat HIGH w...

Страница 47: ...is option denotes the amount of time the blower will continue to run after heating has shut off After the selection is made touch SAVE S Furnace Off Delay 90 120 150 or 180 seconds d Default 120 seconds 6 3 3 6 Altitude For gas de rating this setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions...

Страница 48: ... circuit changes state on the furnace control board depending on setup Under the function option FAN turns on fan to selected fan speed when G terminal is energized SHUTDOWN shuts off fan and equipment when initiated After the selections are made touch SAVE S Function Disabled Fan or Shutdown d Default Disabled S Fan Speed Low Med or High d Default Low S Shutdown d Normally Open d Normally Closed ...

Страница 49: ...ur selection A13230 Shutdown This setup option selects the change of state required for shutdown Select Normally Open or Normally Closed and then save your selection 6 3 3 10 Furnace G Terminal Alert Label Once the G Terminal Alert label has been entered it is shown both on the main screen and in the notification email when the alert becomes active A14224 ...

Страница 50: ...40 6 3 4 AC Heat Pump First touch SETUP then touch AC HEAT PUMP to set up the parameters for the AC Heat Pump unit A14227 6 3 4 1 Latching High Cool Latch A13227 ...

Страница 51: ...only run in low stage cooling High Heat Latch A13228 S System in Control d The system will decide which stage should be running to satisfy the heating demand S High Cool d Temperature below which only the high stage of heating will be energized S Only Low Heat d The system will only run in low stage heating 6 3 4 2 Cooling Lockout Outside temperature below which cooling will not be provided After ...

Страница 52: ...efrost 6 3 4 4 Low Ambient Cooling Selecting YES will enable the low ambient cooling operation in the outdoor unit This setting is only available with communicating outdoor units and with Cooling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units After the selection is made touch SAVE S Low Ambient Cooling Yes or No d Default No 6 3 4 5 Quiet Shift This option tur...

Страница 53: ...econds This helps to reduce any nuisance refrigerant noise caused by the switching reversing valve This setup is only available on communicating heat pumps After the selection is made touch SAVE S Defrost Fan Delay Yes or No d Default No 6 3 4 8 Brownout Disable This option turns off the high voltage brownout detection function in the outdoor unit control This setup is only available on communicat...

Страница 54: ...h SAVE A12149 S HP Lockout Adjustable from 20 to 55_F 28 to 13_C or None d Default None S Furnace Electric Heat or Hydronic Lockout Adjustable from 15 to 55_F 9 to 13_C or None d Default None S Defrost with Furnace Electric Heat or Hydronic Yes or No d Default Yes 6 3 6 Stages Latch for Evolution V For Evolution V heat pumps the cooling and heating stage latch can be changed Select cooling or heat...

Страница 55: ...TUP then touch ZONING to set up the parameters for the zoning system if applicable A12191 6 3 7 1 Zoning Disable This option allows the installer to enable or disable zoning After the selection is made touch SAVE S Disable Zoning Yes or No d Default No ...

Страница 56: ...f maximum assessed airflow MEDIUM means 176 of maximum assessed airflow MED HIGH means 214 of maximum assessed airflow HIGH means 250 of maximum assessed airflow and NO LIMIT means the equipment does not stage down CFM associated for each limit is shown on the screen Compare this value with the equipment s low stage CFM value to ensure that equipment will run for each zone Assessed airflow is dete...

Страница 57: ...er has the option of selecting pressure monitoring the type of filter installed and the time interval for cleaning After the selections are made touch SAVE S Pressure Monitoring not available with Electric Air Cleaner Enable or Disable d Default Enable S Clean Interval Selectable from 1 to 18 months d Default 3 months S Filter Type Air Filter Electric Air Cleaner or Air Purifier d Filter type is s...

Страница 58: ... No 6 3 8 3 Ultraviolet Lights With this option the installer has the option of selecting whether ultraviolet lights are installed and the time interval for changing the ultraviolet lights After the selections are made touch SAVE S UV Lights Installed Yes or No d UV Lights selection made during installation otherwise default no S Change Interval Selectable from 1 to 48 months d Default 12 months 6...

Страница 59: ... DISABLED means that the curtailment function is not active TURN OFF means the outdoor unit is to be turned off when the curtailment function is active LOW STAGE means the outdoor unit will run in lows stage when the curtailment function is active After the selections are made touch SAVE A12193 S Cooling Disabled Low Stage or Turn off d Default Disabled S Heat Pump Disabled Low Stage or Turn off d...

Страница 60: ...ring hydronic heating is a fixed value it does not vary S Blower On Delay Selectable from 0 to 240 seconds d Default 30 seconds S Blower Off Delay Selectable from 0 to 240 seconds d Default 0 seconds 6 4 Check out Touch CHECKOUT to view the equipment installed in the system Perform checkout test to make sure each piece of equipment is operating properly ...

Страница 61: ...ctions are made touch START S Low Heat Selectable from 0 to 120 minutes d Default 5 minutes S Medium Heat Selectable from 0 to 120 minutes d Default 5 minutes S High Heat Selectable from 0 to 120 minutes d Default 5 minutes 6 4 2 Furnace Make sure the furnace is properly installed This option allows the furnace to be exercised First a low heat run time and high heat run time are selected The furna...

Страница 62: ...g This option allows the air conditioner to be exercised With a 2 stage AC unit a low cool and a high cool run time are independently selectable to exercise The display will change to show the AC operating status After the selections are made touch START For Evolution V heat pumps you can select the stage at which the heat pump will exercise During the checkout the stage and time can be changed by...

Страница 63: ...me can be changed by pressing the Change button on the checkout status screen After the selections are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings To view airflows for normal air conditioning cooling mode exit the CHECKOUT screen and apply a heating demand to the system S Low Heat Run Time Selectable from 0 ...

Страница 64: ...ctions are made touch START NOTE Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings To view airflows for normal air conditioning cooling mode exit the CHECKOUT screen and apply a heating demand to the system S Low Cool Run Time Selectable from 0 to 120 minutes d Default 5 minutes S High Cool Run Time Selectable from 0 to 120 minutes d D...

Страница 65: ...selected in SETUP ZONING Airflow Limits If the airflow noise is objectionable the installer can select a lower airflow noise limit If the noise is not objectionable the installer should leave HIGH selected or even NO LIMIT NOTE Selecting a lower airflow noise limit may decrease the homeowner s comfort in that zone Touch the Left or Right buttons to change the desired zones Once the proper airflow ...

Страница 66: ...to return to the ZONING CHECKOUT menu 6 4 9 3 Zone Duct Assessment This function is not available with the 986T furnace This screen shows the results from the previous duct assessment The duct assessment is performed at initial start up and at 1 P M or the installer selected time each day If another duct assessment is desired the service technician should perform a re install of the system NOTE A ...

Страница 67: ...es for the most recent fault NOTE This feature is only available with compatible models Those models are currently the FE fan coil the modulating furnace and the modulating heat pump 6 5 2 Fan Coil Status The fan coil status screen displays relevant information about the fan coil operation To return to the previous screen touch BACK To exit the Service menus touch DONE ...

Страница 68: ... about the furnace operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12198 6 5 4 AC Status The AC status screen displays relevant information about the AC operation To return to the previous screen touch BACK To exit the Service menus touch DONE ...

Страница 69: ...t the heat pump operation To return to the previous screen touch BACK To exit the Service menus touch DONE A12200 6 5 6 Zoning Status The zoning status screen displays relevant information about the zoning operation To return to the previous screen touch BACK To exit the Service menus touch DONE ...

Страница 70: ...has the time and date incident recorded These events are stored in the memory of the control and are resettable in the THERMOSTAT SETUP screen under the RESET FACTORY DEFAULT selection Each entry shows the equipment that generated the event To return to the previous screen touch BACK To exit the Service menus touch DONE A12151 ...

Страница 71: ...nit has performed S Run Times Lifetime hours of operation in heating cooling and how long the unit has been powered A12202 6 5 9 Model Serial Numbers This menu item allows the installer to view the model number serial number if available and control software version if available of all communicating pieces of equipment in the system including the wall control This information resides in the origin...

Страница 72: ... and phone number that the homeowner can call for future service of the system This name and phone number will appear to the homeowner whenever a service reminder pop up message is displayed i e Change Filter etc To return to the previous screen touch BACK To exit touch DONE See Section 6 7 ...

Страница 73: ...iameter After the selections are made touch NEXT S Lineset Selectable from 5 to 200 feet S Vapor line Selectable with various diameters by using the up and down buttons Next the installer will enter the WEIGH IN screen to verify the current total charge is accurate Once the installer has confirmed touch DONE Next the installer will enter the SERVICE VALVE SUBCOOL screen This screen will show the c...

Страница 74: ... Select mode to pump down in COOL or HEAT COOL mode allows refrigerant to be isolated in outdoor unit HEAT mode allows the refrigerant to be isolated in indoor coil and lineset Set desired time period d Default time period for procedure is 120 minutes S Touch START to begin the pump down process Unit will begin running in selected mode after a brief delay 6 6 3 Evacuation Because this system has a...

Страница 75: ...system Enter the menu from the service screens by touching REFRIGERANT CHARGING A14232 6 7 1 Charging Within the CHARGING COOLING or HTG CHECK screens the installer will have the ability to enter the LINESET length and the VAPOR LINE diameter After the selections are made touch NEXT S Lineset Selectable from 5 to 200 feet S Vapor line Selectable with various diameters by using the up and down butt...

Страница 76: ...t be available Next the installer will enter the SERVICE VALVE INFORMATION screen The current liquid line subcool target stabilization time mode and speed in rpm EXV position in percent indoor airflow in CFM outdoor coil temperature in _F indoor temperature in _F outdoor temperature in _F compressor discharge pressure in psig and accumulator suction pressure in psig are displayed on this screen On...

Страница 77: ...nning in selected mode after a brief delay 6 7 3 Evacuation Because this system has an EXV for the heating expansion device additional steps must be taken to open the EXV if the heat pump unit must be evacuated for service reasons If the EXV is not open when pulling a vacuum or recovering refrigerant from the heat pump unit extended evacuation time may be required and or inadequate vacuum obtained...

Страница 78: ...AC software download available on www MyEvolutionConnex Bryant com is required to properly format the dealer logo and contact information for use on the wall control Along with the dealer logo if any three lines of dealer information are provided on the wall control Dealer name 50 characters max Dealer phone number 20 characters max Dealer URL 50 characters max The wall control dealer information ...

Страница 79: ... upload the dealer logo Once complete you will receive a confirmation that your upload was successful If the information was not stored properly on the USB device you will receive an error message that the dealer logo was not found Refer back to the PC MAC software application instructions and try again Once the upload is complete touch NEXT If you have problems contact your distributor service ma...

Страница 80: ...an existing Evolution System Wi Fi network If the in home Wi Fi is found to be incompatible with SYSTXBBECC01 A an Evolution Wireless Access Point SYSTXXXGWR01 or any other compatible wireless router can be installed to establish Wi Fi connectivity Please call 1 800 428 4326 for support with Wi Fi set up and connection to the MyEvolution Server The ability to remotely access and adjust the setting...

Страница 81: ...gs of the Evolution Connex Control will not be negatively affected by the network related modifications upgrades or similar activity of the user s Internet service provider or mobile device carrier service NOTE See the Owner s Manual for information regarding software upgrades 7 1 SYSTXBBECC01 A Models only To establish Wi Fi connectivity to the Evolution Connex Control using the in home router or...

Страница 82: ...e outlined in faint blue Then select NEXT A13236 S The selected network will show Choose an appropriate Wi Fi security Usually auto detect will correctly identify the type of security used If the network has no security it will show as on the left but a secured network will prompt for the Wi Fi security key ...

Страница 83: ...security key area and the keyboard will appear d Use the on screen keyboard to enter the Wi Fi security key then touch NEXT S The control will inform you if the connection is successful If so touch DONE d If the connection is unsuccessful verify that the proper information has been entered before you touch RETRY The control will go through the process again A13238 ...

Страница 84: ...s been established the status screen will show Connected for both Wi Fi and the server Connected Not Connected A13239 7 2 SYSTXBBECW01 A Models only To establish the Wi Fi connectivity to the Evolution Connex Control through the Evolution System Wireless Access Point TP LINKR Device connect the WAN BLUE port connection of TP LINK Wireless Access Point to the home s existing router LAN port using t...

Страница 85: ...Touch SETUP A WI FI CONNECTION to begin the process S Next touch SCAN FOR AVAILABLE ACCESS POINTS A12115 S Select the myHVACxxxxxx connection from the list then touch NEXT myHVAC is followed by the last 6 digits of your Wireless Access Point s MAC address see the label on the bottom of the TP LINK Wireless Access Point ...

Страница 86: ...can to the next screen to find myHVACxxxxxx A12116 S Use the on screen keyboard to enter the Wi Fi security key then touch NEXT d Touch in the security key area and the keyboard will appear d The security key can be found on the back of the TP LINK Wireless Ac cess Point ...

Страница 87: ...trol has connected to the network go to www MyEvolutionConnex Bryant com to register the unit and begin remote access This requires the MAC address and serial number of the EvolutionR Connext Wall Control NOT the Wireless Access Point To find the serial number and MAC address of the Evolution Connex Wall Control click on Menu Down Arrow Wireless and View My Evolutionr Info This screen will provide...

Страница 88: ...please contact your servicing dealer S When the connection to the MyEvolution web server has been established the status screen will show Connected fo both Wi Fi and the server TP LINK is a trademark of TP LINK Technologies Co Ltd ...

Страница 89: ...Yellow White Red OAT Sensor Optional Variable Speed Furnace Fan Coil NOTE Some outdoor units do not require the C and D connections See outdoor unit Installation Instructions NOTE For SPP products ABCD connection between Indoor and Outdoor control boards are pre wired at the factory NOTE For new SPP installations in which the OAT Sensor is required please refer to the SPP Installation Instructions...

Страница 90: ...Communicating AC Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM COM 24V Humidifier Connection Y Y2 S2 S1 OAT OAT Sensor Variable Speed Furnace Fan Coil A12354 Connection Diagram for Furnace or FE Fan Coil with 1 Stage Air Conditioning ...

Страница 91: ...municating HP Green Data A Yellow Data B White COM Red 24VAC Optional Remote Room Sensor HUM C Humidifier Connection Y S2 S1 W2 Y O C R O R W OAT OAT Sensor Variable Speed Fan Coil G A12355 Connection Diagram for FE Fan Coil with Non communication 1 Stage Heat Pump ...

Страница 92: ...n Yellow White Red OAT HUM COM 24V Humidifier Connection A B C D OAT Sensor Optional A B C D A B C D Damper Control module A B C D Indoor Unit Communicating AC or HP A04018 Zoning Connection for Communicating Indoor Unit with 2 Stage Communicating Outdoor Unit ...

Страница 93: ...reen Yellow White Red OAT HUM COM 24V Humidifier Connection OAT Sensor A B C D A B C D Damper Control module A B C D Indoor Unit C Y 1 Stage AC Y Y2 A04019 Zoning Connection Diagram for Furnace or FE Fan Coil with Non Communicating 1 Stage Air Conditioning ...

Страница 94: ...Green Yellow White Red A B C D A B C D Damper Control module A B C D Variable Speed Fan Coil 1 Spd HP HUM C Y W2 Y O C R O R W OAT OAT Sensor Humidifier Connection G A07149 Zoning Connection diagram for FE Fan Coil with Non communicating 1 Stage Heat Pump ...

Страница 95: ...85 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...

Страница 96: ...86 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...

Страница 97: ...87 NOTES ...

Страница 98: ...88 NOTES Cont ...

Страница 99: ......

Страница 100: ...n EAR99 E2014 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 03 14 997 011280 25 R Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II SYSTXBBEC 05 Replaces II SYSTXBBEC 04 ...

Отзывы: