35
—
Table 16 — EconoMi$erIV Input/Output Logic
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply air sensor signal.
††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply air sensor
signals, between minimum position and either maximum position
(DCV) or fully open (supply air signal).
†††Modulation is based on the greater of DCV and supply air sensor
signals, between closed and either maximum position (DCV) or fully
open (supply air signal).
INPUTS
OUTPUTS
Demand Control
Ventilation (DCV)
Enthalpy*
Y1
Y2
Compressor
N Terminal†
Outdoor
Return
Stage
1
Stage
2
Occupied
Unoccupied
Damper
Below set
(DCV LED Off)
High
(Free Cooling LED Off)
Low
On
On
On
On
Minimum position
Closed
On
Off
On
Off
Off
Off
Off
Off
Low
(Free Cooling LED On)
High
On
On
On
Off
Modulating** (between min.
position and full-open)
Modulating** (between
closed and full-open)
On
Off
Off
Off
Off
Off
Off
Off
Minimum position
Closed
Above set
(DCV LED On)
High
(Free Cooling LED Off)
Low
On
On
On
On
Modulating†† (between min.
position and DCV maximum)
Modulating†† (between
closed and DCV
maximum)
On
Off
On
Off
Off
Off
Off
Off
Low
(Free Cooling LED On)
High
On
On
On
Off
Modulating***
Modulating†††
On
Off
Off
Off
Off
Off
Off
Off
Fig. 46 — EconoMi$erIV Functional View
Содержание DURAPAC PLUS SERIES 542J
Страница 27: ... 27 Fig 40 Typical Wiring Diagram 542J150 208 230 3 60 V Shown ...
Страница 28: ... 28 Fig 41 Typical Component Arrangement 542J150 208 230 3 60 V Shown ...
Страница 33: ... 33 Fig 44 Troubleshooting Chart Heating Cycle ODT Outdoor Temperature ...
Страница 34: ... 34 Fig 45 Troubleshooting Chart Cooling Cycle ...
Страница 38: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 5354 203 ...
Страница 39: ......