A95218

Fig. 5—Two-Stage or Variable-Speed Furnace with

2-Speed Heat Pump

Y/Y2

W/W1

R

24 VAC HOT

FAN

FURNACE

COMPRESSOR
HI

RVS COOLING

COMPRESSOR
LO

DUAL FUEL

THERMOSTAT

TWO-SPEED

HEAT PUMP

24 VAC COM

RVS HEATING

RVS SENSING

OUTDOOR

SENSOR

CONNECTION

S2

S1

L

B

G

R

R

Y2

G

C

C

C

O/W2

Y1/W2

TWO-STAGE OR

VARIABLE SPEED

FURNACE

W2

O

SEE NOTES 1 AND 2

W/W1

Y/Y2

O

Y1

W2

Y1

W3

OUTDOOR

TEMPERATURE

SENSOR

WIRING DIAGRAM NOTES:

1. Underlined letter on dual terminal indicates its usage.

For Example: O/W2 means O, O/W2 means W2.

Outdoor Temperature Sensor must be attached in all dual
fuel installations.

Jumper wire between O/W2 and L thermostat terminals
MUST be present.

2. Y1 and O connections to 2-stage furnaces MAY NOT

EXIST, or may be only a wire rather than a screw terminal.

—6—

Содержание DUAL FUEL THERMOSTAT TSTAT

Страница 1: ...irements Fore most is that furnace and HP must not be allowed to operate at same time except during HP defrost A second is to have furnace complete a heating cycle once it is turned on A third is the need to have HP not operate at all when outdoor temperatures are below a certain value Finally HP and furnace must work together properly to provide an efficient and comfortable defrost These requirem...

Страница 2: ...P heating call to operate compressor at high speed and adjust blower for high speed HP operation HEATING OPERATION SINGLE STAGE FURNACE W W1 causes furnace to operate Furnace controls its own blower at heating speed HEATING OPERATION TWO STAGE FURNACE THERMOSTAT CONTROL Low fire W W1 causes furnace to operate at low fire Furnace controls its own blower at low heating speed High fire Y1 W2 is added...

Страница 3: ...e will arrive at the programmed temperature at the programmed time TO SET OFF for smart recovery This is the factory default ON for normal recovery SWITCH C DISABLE LOW AMBIENT COOLING Use to allow or prevent cooling operation below an outdoor temperature of 55 F Prevention of cooling below 55 F adds to compressor reliability If outdoor temperature sensor fails or is disconnected cooling is allowe...

Страница 4: ...lter 1200 to 1600 hours or electronic air cleaner 1600 to 2400 hours of blower operation TO SELECT 1 Enter configuration mode 2 Press RESET FILTER button to display OF off or digits 1 through 9 3 Use up and down buttons to move between selections Total hours equals 400 times the displayed number OF off turns feature off 4 During the selection process the CLEAN FILTER icon will remain on even if OF...

Страница 5: ...m is entered VIII CHECKLIST 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner Fig 2 Single Stage Furnace with Single Speed Heat Pump A95215 Y Y2 W W1 R 24 VAC HOT FAN FURNACE COMPRESSOR RVS COOLING N A DUAL FUEL THERMOSTAT SINGLE SPEED HEAT PUMP 24 VAC COM RVS HEATING RVS SENSING OUTDOOR SENSOR CONNECTION G R R W Y Y G C...

Страница 6: ...1 W2 TWO STAGE OR VARIABLE SPEED FURNACE W2 O SEE NOTES 1 AND 2 W W1 Y Y2 O Y1 W2 Y1 W3 OUTDOOR TEMPERATURE SENSOR WIRING DIAGRAM NOTES 1 Underlined letter on dual terminal indicates its usage For Example O W2 means O O W2 means W2 Outdoor Temperature Sensor must be attached in all dual fuel installations Jumper wire between O W2 and L thermostat terminals MUST be present 2 Y1 and O connections to...

Страница 7: ...ge is restored If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will be displayed in place of room temperature The thermostat will continue to operate but will only use furnace in HEAT mode AUXILIARY HEAT ICON This icon is displayed when the furnace is operating SMART RECOVERY With Smart Recovery selecte...

Страница 8: ... 1995 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 8 tstat06 Catalog No 92 33TS TA28B ...

Отзывы: