2

A05086

Fig. 1 -- Furnace in Upflow Orientation

ama

REGISTERED

ISO 9001:2000

CERTIFIED

Installing and servicing heating equipment can be hazardous due to

gas and electrical components.

Only trained and qualified

service agency personnel should install, repair, or service

heating equipment. Untrained personnel can perform basic

maintenance functions described in User’s Information

Manual such as cleaning and replacing air filters.

All other

operations must be performed by trained service personnel. When
working on heating equipment, observe precautions in the

literature, on tags, and on labels attached to or shipped with the
unit and other safety precautions that may apply.
Follow all safety codes including the National Fuel Gas Code

(NFGC) NFPA 54--2006/ANSI Z223.1--2006 in the USA, CSA
B149.1--05 National Standard of Canada, Natural Gas and Propane

Installation Codes (NSCNGPIC) in Canada, and the Installation
Standards, Warm Air Heating and Air Conditioning Systems

(NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and work

gloves. Have a fire extinguisher available during start--up and
adjustment procedures and service calls.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage to

furnace.
Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and dangerous

operation.

CAUTION

!

GENERAL

This furnace can be installed as a direct vent (2--pipe) or non--direct
vent (1--pipe) condensing gas furnace. These instructions are

written as if the furnace is installed in an upflow application. An

upflow furnace application is where the blower is located below
the combustion and controls section of the furnace, and

conditioned air is discharged upward. Since this furnace can be
installed in any of the 4 positions shown in Fig. 2, you may need to

revise your orientation to component location accordingly.

UPFLOW

DOWNFLOW

HORIZONTAL

LEFT

AIRFLOW

AIRFLOW

AIRFLOW

AIRFLOW

HORIZONTAL

RIGHT

A93041

Fig. 2 -- Multipoise Orientation

ELECTROSTATIC DISCHARGE (ESD)

PRECAUTIONS

UNIT DAMAGE HAZARD

Failure to follow this caution may damage furnace

components.
Electrostatic discharge can affect electronic components.

Take precautions during furnace installation and servicing

to protect the furnace electronic control. Precautions will

prevent electrostatic discharges from personnel and hand

tools which are held during the procedure. These

precautions will help to avoid exposing the control to

electrostatic discharge by putting the furnace, the control,

and the person at the same electrostatic potential.

CAUTION

!

1. Disconnect all power to the furnace. DO NOT TOUCH

THE CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL PRIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.

2. Firmly touch a clean, unpainted, metal surface of the fur-

nace chassis which is close to the control. Tools held in a

340AA

V

Содержание Deluxe 340AAV

Страница 1: ...potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or produ...

Страница 2: ... operation CAUTION GENERAL This furnace can be installed as a direct vent 2 pipe or non direct vent 1 pipe condensing gas furnace These instructions are written as if the furnace is installed in an upflow application An upflow furnace application is where the blower is located below the combustion and controls section of the furnace and conditioned air is discharged upward Since this furnace can b...

Страница 3: ...the label attached to the furnace WARNING The minimum maintenance that should be performed on this equipment is as follows 1 Check and clean or replace air filter each month as needed 2 Check blower motor and wheel for cleanliness annually 3 Check electrical connections for tightness and controls for proper operation each heating season Service as necessary 4 Check for proper condensate drainage C...

Страница 4: ...nfiguration Shown with Blower Access Panel Removed 1 Turn off electrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disp...

Страница 5: ... CAUTION g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 9 Reassemble motor and blower wheel by reversing items 8b through 8f Ensure wheel is positioned for proper rotation Be sure to reattach ground wire Tighten setscrew to 140 to 160 in lb torque NOTE Be sure to attach ground wire to blower housing 10 Reinstall blower assembly in furnace 11 Reinstall control box...

Страница 6: ...move screws attaching burner assembly in burner box NOTE Use care when removing and reinstalling burners not to strike the hot surface igniter IGNITER WIRES MUST BE PLACED IN THIS SLOT A05074 Fig 7 Igniter Wire Placement 12 Remove burner assembly from burner box NOTE All burners are attached to burner bracket and can be removed as one assembly 13 Clean burners with soft brush and vacuum 14 Reinsta...

Страница 7: ...sconnect wires or connectors to flame rollout switch gas valve igniter and flame sensor 4 Disconnect combustion air intake pipe from intake hous ing 5 Remove the pressure switch tube from intake housing 6 Remove screws attaching intake housing to burner box and rotate intake housing away from burner box for removal 7 Using backup wrench disconnect gas supply pipe from fur nace gas control valve 8 ...

Страница 8: ...n made specifically for the detection of leaks to check all connections WARNING 18 Replace main furnace door Secondary Heat Exchangers NOTE The condensing side inside of the secondary heat exchangers CANNOT be serviced or inspected A small number of bottom outlet openings can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removin...

Страница 9: ...onnection as shown 3 HORIZONTAL LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap Refer to the Installation Instructions for further details NOTE 324999 201 REV C FIELD INSTALLED FACTORY SUPPLIED DRAINTUBE COUPLING RIGHT DRAIN OPTION BURNER ENCLOSURE PRESSURE REFERENCE TUBE ASSEMBLY BURNER ENCLOSURE PRESSUR...

Страница 10: ...triking the igniter on surrounding parts Note that the igniter bracket has a handle that extends to the front of the burner box to aid in handling See Fig 13 d Inspect igniter for signs of damage or failure UNIT DAMAGE HAZARD Failure to follow this caution may result in premature failure of the igniter The igniter is fragile DO NOT allow it to hit burner box parts while removing or replacing it CA...

Страница 11: ...se to blow If fuse replacement is required use ONLY a fuse of identical size The furnace control LED will flash status code 24 when fuse needs to be replaced With power to the unit disconnected check all electrical connections for tightness Tighten all screws on electrical connections If any smoky or burned connections are found disassemble the connection clean all parts strip wire and reassemble ...

Страница 12: ... same type or equivalent wire W Y GND THERMOSTAT TERMINALS 1 2 3 A02174 Fig 15 Field Wiring BLW NUETRAL STATUS CODE LED SEC 2 SEC 1 EAC 2 L2 FUSE 3 AMP 0 5 AMP 24VAC HUM TEST TWIN G Com W Y R 24V 120 180 90 150 BLOWER OFF DELAY PLT 1 COOL HEAT SPARE 1 SPARE 2 EAC 1 1 AMP 115VAC PR 1 L1 PL2 1 24 V THERMOSTAT TERMINALS 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 115 VAC L2 NEUTRAL CONNECTIONS COOL HEA...

Страница 13: ...omotive type CAUTION 6 Replace drain connection cap and clamp to inducer housing 7 Replace main furnace door 8 Propylene glycol need not be removed before restarting fur nace WIRING DIAGRAMS See Fig 21 for wiring diagram A07911 Fig 17 Freeze Protection TROUBLESHOOTING Use the troubleshooting guide the status code LED on the furnace control and the component test to isolate furnace operation proble...

Страница 14: ... COM 24v terminals are jumpered longer than 2 sec LED will flash rapidly and ignore component test request A99119 Fig 19 Funnel in Drain Tube and Antifreeze Running Through Trap Component test sequence for single stage furnace is as follows a LED will display status code 11 four times b Inducer motor starts and continues to run until Step f of component test sequence c After 7 sec the hot surface ...

Страница 15: ...T CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low inducer voltage 115VAC Defective pressure switch Inadequate combustion air supply Restricted vent Disconnected or obstructed pressure tubing Low inlet gas pressure if LGPS used If it opens during blower on delay period blower wil...

Страница 16: ...AFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR J2 COOLING OFF DELAY JUMPER JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES RED LGPS LOW GAS PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 11 CIRCUIT PCB CONNECTOR P...

Страница 17: ...est sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to W...

Страница 18: ... switch open Restricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected...

Страница 19: ...heory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Package...

Страница 20: ...hange at any time specifications or designs without notice and without incurring obligations E2008 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 12 08 Replaces SP05 72 Catalog No SM340AAV 01 340AAV ...