Bryant DE LUXE 12 SEER 552A Скачать руководство пользователя страница 7

 

—7—

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

 

10.

 

Low-Ambient Pressure Switch

 

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure 
within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 
0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
11.

 

MotorMaster® Control

 

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing 
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 
100°F ± 10°F (37.8°C ± 5.6°C).

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

All commercial installations.

12.

 

Outdoor Air Temperature Sensor

 

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat. 

SUGGESTED USE: All Bryant programmable thermostats.
13.

 

Piston Body

 

This piston body is to be used as a replacement for the FK4C Fan Coil R-22 thermostatic expansion valve when used with Puron® (R-410A) air conditioner 
units. Use piston and piston ring shipped with outdoor unit for installations under 50 ft. 

SUGGESTED USE: All Puron® air conditioner installations matched with FK4C Fan Coils.
14.

 

Support Feet

 

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, 
minimizing corrosion. 

SUGGESTED USE: For improved sound ratings.

Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.

15.

 

Thermostatic Expansion Valve (TXV)

 

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the 
evaporator. Kit includes valve and adapter tubes.  

SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

16.

 

Time-Delay Relay

 

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. 

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

17.

 

Winter Start Control

 

An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load 
conditions. 

SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.

 

SOUND POWER (A-wtd., non-pure tone corrected.)

 

NOTE: 

 

Tested in accordance with ARI Standard 270.95. (Not listed with ARI.)

 

UNIT

SIZE-SERIES

SOUND

LEVEL

(dBA)

OCTAVE BAND CENTER FREQUENCY (Hz)

125

250

500

1000

2000

4000

8000

 

018-F

72

67.0

69.0

69.0

67.0

63.0

55.5

49.5

024-F

69

54.0

60.5

63.5

63.0

59.0

55.5

48.5

024-G

74

57.0

66.0

68.0

67.0

65.0

62.0

51.5

030-F

70

57.0

61.5

64.5

65.0

63.0

59.5

53.0

036-F, G

73

60.0

64.0

66.5

68.5

66.0

62.0

53.5

042-F

73

57.5

63.5

67.0

68.0

65.5

62.0

55.0

048-F

76

63.0

66.0

67.0

70.5

67.0

62.5

55.0

060-F

78

63.0

67.5

69.5

72.5

68.5

64.5

58.5

Содержание DE LUXE 12 SEER 552A

Страница 1: ...of the system and componentry The reliability of the existing Quantum Plus models has been proven to provide the lowest incidence of warranty service of any product in the Bryant family in the past fe...

Страница 2: ...M A99067 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 F 33 13 16 22 1 2 27 1 2 4 1 8 7 1 8 21 15 16 28 3 8 5 8 8 3 16 12 1 2 14 15 1 2 2...

Страница 3: ...P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY S...

Страница 4: ...00 2400 2400 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0701SML KAACF0801MED KAACF0701SML KAACF0801MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater...

Страница 5: ...anch Circuit Fuse or Circuit Breaker Size Amps 40 40 60 COMPRESSOR REFRIGERANT Compressor Type Scroll Temperature Current Protection Internal Line Break Refrigerant Type Puron R 410A Amount Lb 5 43 5...

Страница 6: ...6 Cycle Protector Solid state timing device which prevents compressor rapid recycling Control provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason...

Страница 7: ...ther debris to be flushed from the unit base minimizing corrosion SUGGESTED USE For improved sound ratings Coastal installations Windy areas or where debris is normally circulating Rooftop installatio...

Страница 8: ...A024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 024 F CK5A CK5BA030 23 200 NONE 12 00 12 00 10 30 CC5A CD5AA024 23 000 NONE 11 70 11 70...

Страница 9: ...TXV 12 00 10 70 CK5PW024 22 800 TXV 12 00 10 65 CK5PW030 23 000 TXV 12 00 10 70 F A B 4BN F C 024 23 000 TDR 12 00 12 00 10 75 F A B 4BN F C 030 23 400 TDR 12 00 12 00 10 85 FC4CNF024 23 000 TDR TXV...

Страница 10: ...11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BA024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BA030 22 600 TDR 13 00 13 00 11 75 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13...

Страница 11: ...00 10 40 COILS 315 A J AV036070 VARIABLE SPEED FURNACE CC5A CD5AA030 27 800 TDR 12 50 12 50 11 10 CC5A CD5AA036 28 800 TDR 13 00 13 00 11 45 CC5A CD5AW030 27 800 TDR 12 50 12 50 11 10 CE3AA030 28 200...

Страница 12: ...12 00 10 55 CC5A CD5AW042 34 800 NONE 12 00 12 00 10 45 CE3AA036 34 600 NONE 11 70 11 70 10 45 CE3AA042 35 000 NONE 12 00 12 00 10 60 CF5AA036 34 800 NONE 12 00 12 00 10 50 CK3BA036 35 000 NONE 12 00...

Страница 13: ...600 TDR TXV 13 00 11 45 CK5PT036 34 600 TDR TXV 13 00 11 40 CK5PT042 34 600 TDR TXV 13 00 11 45 CK5PW036 34 600 TDR TXV 13 00 11 40 COILS 315 A J AV066135 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 T...

Страница 14: ...0 25 CE3AA048 40 000 NONE 12 00 12 00 10 30 CF5AA048 39 500 NONE 12 00 12 00 10 25 CK3BA042 39 500 NONE 11 70 11 70 10 20 CK3BA048 40 000 NONE 12 00 12 00 10 25 CK5A CK5BA042 39 500 NONE 11 70 11 70 1...

Страница 15: ...11 10 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 10 CK5PA042 39 000 TDR TXV 12 50 11 00 CK5PA048 39 500 TDR TXV 12 50 11 10 CK5PT042 39 000 TDR TXV 12 50 11 00 CK5PT048 39 500 TDR TXV 12 50 11 10 CK5PW0...

Страница 16: ...10 35 CD5AA048 45 000 NONE 11 70 11 70 10 15 CE3AA048 45 000 NONE 11 70 11 70 10 25 CE3AA060 46 000 NONE 12 00 12 00 10 40 CF5AA048 44 000 NONE 11 70 11 70 10 20 CK3BA048 45 000 NONE 11 70 11 70 10 2...

Страница 17: ...DR 12 50 12 50 11 25 CK5PA048 44 500 TDR TXV 12 00 10 80 CK5PA060 45 000 TDR TXV 12 50 11 05 CK5PT048 44 500 TDR TXV 12 00 10 80 CK5PT060 45 000 TDR TXV 12 50 11 05 CK5PW048 44 500 TDR TXV 12 00 10 80...

Страница 18: ...85 FC4 B C NB070 58 000 TDR TXV 12 00 10 15 FG3AAA060 56 000 NONE 11 50 11 50 10 10 FK4 C D NB006 58 000 TDR TXV 12 50 12 50 10 75 FV4 A B NB006 58 000 TDR TXV 12 50 10 75 FX4 A B NB060 56 000 TDR TXV...

Страница 19: ...elay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor...

Страница 20: ...16 05 16 05 1 63 15 24 15 24 1 80 14 37 14 37 2 00 13 45 13 45 2 21 675 72 19 82 10 51 1 36 19 79 10 76 1 52 19 60 10 97 1 69 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19...

Страница 21: ...22 5 17 0 2 04 21 1 16 5 2 26 19 4 15 7 2 50 18 2 15 3 2 77 16 2 14 4 3 05 62 23 1 21 9 1 83 22 2 21 4 2 03 20 9 20 8 2 26 20 2 20 2 2 51 18 9 18 9 2 79 17 2 17 2 3 08 57 22 6 22 6 1 82 21 8 21 8 2 03...

Страница 22: ...24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Страница 23: ...62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 7...

Страница 24: ...25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Secti...

Страница 25: ...5 6 2 68 24 3 24 3 2 96 22 9 22 9 3 29 21 4 21 4 3 65 57 28 6 28 6 2 20 26 9 26 9 2 42 25 4 25 4 2 67 24 5 24 5 2 97 23 4 23 4 3 29 21 4 21 4 3 65 1125 72 34 1 17 8 2 30 33 1 17 6 2 54 31 4 17 0 2 79...

Страница 26: ...3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacit...

Страница 27: ...57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Страница 28: ...36 3 36 3 4 36 33 2 33 2 4 82 29 9 29 9 5 33 57 41 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor...

Страница 29: ...92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity P...

Страница 30: ...46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooli...

Страница 31: ...62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers f...

Страница 32: ...36 7 7 64 63 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 5...

Страница 33: ...24 2 18 17 2 133 2 43 15 6 143 2 69 40 TCG SDT KW 28 2 77 1 1 18 26 7 86 7 1 35 25 1 96 3 1 54 23 6 106 1 74 22 0 116 1 97 20 4 125 2 21 18 8 135 2 46 17 0 144 2 72 45 TCG SDT KW 30 8 78 7 1 18 29 1 8...

Страница 34: ...1 25 6 124 3 13 23 3 133 3 48 20 8 142 3 83 40 TCG SDT KW 39 0 78 1 1 71 37 0 87 5 1 95 34 9 97 1 2 22 32 7 107 2 51 30 5 116 2 83 28 1 125 3 17 25 7 134 3 52 23 0 143 3 89 45 TCG SDT KW 42 5 79 9 1 7...

Страница 35: ...Continued ARI listing applies only to systems shown in Ratings and Performance table kW Outdoor Unit Kilowatts only SDT Saturated Temperature Leaving Compressor F SST Saturated Temperature Entering C...

Страница 36: ...Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive prop...