background image

A.

Cleaning the Cell

For optimum performance the electronic cells must be washed
regularly to remove the dirt cleaned from the air. The required
frequency of cell washing varies from one environment to another,
depending on a large number of variables. In nearly all cases, the
correct period is between 1 and 6 months. Where building
infiltration and internal generation of dust is low, as in a smaller
home, washing every 5 or 6 months may be adequate. Where there
is considerable infiltration, cooking, dust, and tobacco smoke,
more frequent washing will be required. If a heavy buildup of dirt
is found on the collector plates or the cell is not clean after
washing, it should be cleaned more often. If there is only light dirt
on collector plates, the period between washing can probably be
lengthened. The electronic plate cells may be washed a number of
different ways, depending on homeowner preference.

1. Automatic Dishwasher Washing—The easiest and most

convenient way to remove the accumulated dirt from the
plate-type electronic cells is to wash them in an automatic
dishwasher.

a. Place electronic cells on sides with ionizer section down

(airflow arrows pointing up) on lower rack of dish-
washer.

CAUTION:

Use care to avoid damage to the collector

plates when placing the cells in the dishwasher.

NOTE:

For some dishwashers with a center spray arm, it may be

necessary to remove the top basket to fit one or both cells inside.

b. Use detergent in accordance with dishwasher manufac-

turer’s instructions.

c. Allow dishwasher to run through its complete wash

cycle. You may also allow it to run through its complete
dry cycle, although this is not necessary.

CAUTION:

The electronic cell will be very hot at the

end of the dishwasher’s cycle. Allow it to cool before
handling. Hot water may accumulate in the tubes sup-
porting the collector plates. Tip the cells to drain tubes.

Fig. 19—EAC Connection to Multipoise Fixed

Capacity Furnace Control Board

A94081

HUM-HUMIDIFIER
TERMINAL
(24-VAC 0.5 AMP MAX)

LED OPERATION
& DIAGNOSTIC LIGHT

HARNESS
CONNECTOR

24V TRASFORMER
SEC-2

SPARE 1

SPARE 2

EAC 1 (BLACK)

EAC-ELECTRONIC AIR
CLEANER TERMINALS
(115-VAC 1 AMP MAX)

EAC 2 (WHITE)

115-VAC (L2) NEUTRAL

CONNECTION

24-VOLT
THERMOSTAT
TERMINALS

HEAT

COOL

BLOWER OFF-DELAY
ADJUSTMENT SWITCH

SEC-1

G

R

Y

W

Com

3-AMP FUSE

Fig. 17—EAC Connection to Electronic Condensing Upflow

Gas Furnace

A91490

ACCR

CIRCUIT

BREAKER

R

Y

W

G

C

Fig. 20—EAC Connection to Multipoise Variable Speed

Furnace Control Board

A94082

EAC-ELECTRONIC AIR CLEANER
    TERMINALS (115-VAC
                           1 AMP MAX)

MAIN BLOWER

CONTROL WIRE

CONNECTOR

CONTINUOUS

FAN (CF) SETUP

SWITCHES

HOT SURFACE
IGNITOR CONNECTOR

HUM-HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX)

24-VOLT
THERMOSTAT
TERMINALS

TRANSFORMER
24-VOLT
CONNECTIONS

3-AMP FUSE

STATUS AND
DIAGNOSTIC
LED LIGHTS

SETUP SWITCHES
(SW) AND
BLOWER OFF DELAY
SETUP SWITCHES

Fig. 18—EAC Connection to Continuous Pilot Gas Furnace

A91226

MAX. 1.0 AMPS
115-VAC

SEC-2

SEC-1

GROUND
SCREW
REQUIRED

FU

3-AMP
FUSE

BLOWER
OFF-DELAY

24-VAC
COMMON

CES0110074-00

W

Y

R

C

G

EAC-2

EAC-1

COM

PR-2

L2

CFR

HI

HFR

L1

PR-1

PL-1

1

2

3

4

5

6

7

8

9

1

3

IDR

24-VAC COMMON

BLOWER
OFF-TIME
ADJUSTMENT

24-VAC
THERMOSTAT
TERMINALS

COOLING
SPEED TAP
TERMINAL

HEATING

SPEED TAP

TERMINAL

115-VAC

NEUTRAL

TERMINALS

115-VAC
LINE
VOLTAGE

115-VAC
TRANSFORMER

9-PIN
CONNECTOR

ELECTRONIC

AIR-CLEANER

TERMINALS

24-VAC POWER

LO

24-VAC FUSE
3-AMP ONLY

UNCUT: 120 SEC
CUT: 180 SEC

—9—

Содержание 901KAX

Страница 1: ...units Cabinets are designed to support up to 400 pounds when used in under the furnace applications A Cabinet The cabinet includes an electrical junction box and power safety interlock and houses the air cleaner components These compo nents are 1 Mechanical pre filters Expanded aluminum mesh first stage filter that removes lint and large dust particles 2 Cell assemblies Cells consisting of combine...

Страница 2: ...4 A91466 8 1 2 7 8 IN ELECTRICAL ENTRANCE FOR DUCT APPLICATION REAR MOUNTING FLANGE A 3 16 7 8 2 1 16 C B 21 REMOVABLE POWER DOOR ELECTRICAL ENTRANCE 5 8 IN DIA FOR FURNACE APPLICATIONS LOGO OPERATION LIGHT KNOB ON OFF SWITCH 1 TABLE 1 COMPONENT INFORMATION MODEL 901KAX012 901KAX016 901KAX020 Air Volume Range 300 1400 500 1800 700 2000 Electrical Data Input to power door 120v single phase 60 Hz 12...

Страница 3: ... lower than 40 F can cause ionizer wire failure under certain conditions NOTE The maximum operating temperature of the EAC is 125 F II INSTALLATION NOTE See Fig 4 for suggested installation positions CAUTION Turn off all power to furnace or fan coil before beginning installation Proceed as follows to install EAC 1 Remove and discard existing furnace mechanical filters They are not required when us...

Страница 4: ...ONNECTIONS All wiring must comply with applicable local and national codes To determine best power wiring routing refer to Section A for Internal Electrical Connections and Section B for External Elec trical Connections NOTE For general information a line to line wiring diagram is provided See Fig 9 Fig 4 Typical Applications A86134 DOWNFLOW APPLICATION RETURN AIR PLENUM FAN COIL UNIT SUPPLY AIR P...

Страница 5: ...s a Single Speed Furnaces EAC is wired in parallel with fan motor See Fig 11 b Multispeed Direct Drive Motor If the EAC is wired to a multispeed direct drive motor it must be isolated by a relay or sail switch Use either air cleaner relay P N P283 1203 or sail switch P N 69105D1 See Fig 12 or 13 c Furnaces with Printed Circuit Boards EAC is wired to furnace terminals EAC 1 and EAC 2 See Fig 14 for...

Страница 6: ...th fan motor See Figure 16 The secondary leads of transformer 120v connect to electronic air cleaner for proper opera tion A field supplied accessory relay 240v may also be used in place of the 240v conversion kit See Figure 16 Apply 240v relay coil in parallel with fan motor Connect white common wire from EAC to N O contacts then to neutral at service panel Check for 120v 60hz 1ph and ensure sepa...

Страница 7: ... and unit components 5 Unit can be installed with airflow through cabinet in either direction Apply provided airflow decal to cabinet observ ing actual airflow direction See Fig 24 IV STARTUP AND ADJUSTMENTS The electronic components of the unit convert the incoming vac to vdc power supply Unfiltered contaminated air passes through an aluminum mesh pre filter which removes large airborne particles...

Страница 8: ...evel produced by an EAC Because normal maintenance cleaning is so simple most home owners will choose to personally perform the necessary operations Clean the unit where dust from air cleaner cells will not soil carpets or floor CAUTION Before removing the electronic cells be sure to de energize the system fan to avoid any possibility of circulating unfiltered air back into the system To gain acce...

Страница 9: ...omplete dry cycle although this is not necessary CAUTION The electronic cell will be very hot at the end of the dishwasher s cycle Allow it to cool before handling Hot water may accumulate in the tubes sup porting the collector plates Tip the cells to drain tubes Fig 19 EAC Connection to Multipoise Fixed Capacity Furnace Control Board A94081 HUM HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX LED OPERATION...

Страница 10: ... children c Before placing cells in washing container pour in detergent Use approximately 3 4 cup per cell if con tainer is about size of cell Add enough very hot water to cover cell s d After detergent has completely dissolved place elec tronic cell s in container e Soak cells for 15 to 20 minutes slosh several times and remove f Rinse cells with fine water spray Fig 21 EAC Connection to 2 Stage ...

Страница 11: ...asional arcing will occur Continuous arcing may indicate cleaning is necessary The EAC should operate only when the system blower is running B Isolating Malfunctions Switch on the EAC and energize the blower system If the light does not glow remove the cells and replace the door If the light glows with the cells removed the problem is within the cell or cabinet Proceed to items 1 through 3 However...

Страница 12: ...age current on 7300vdc 1 MA The LED light circuit output can be checked with a voltmeter The reading should be 4vac 8 Check power supply a Place screwdriver on ground plate access panel At the same time move shank portion of screwdriver towards high voltage output of power supply If arcing occurs when screwdriver comes within approximately 1 8 in of power supply power supply is operating properly ...

Страница 13: ...evenly covered with dirt In the case of the 2 cell units each cell should have an even load ing pattern Install turning vanes of air baffles CAUTION Do not block off any of the entering air side opening to the unit Radio or TV interference Accumulation of foreign particles lodged in ionizer sec tion Remove Unit improperly grounded Provide good ground to power pack Ground line of supply line voltag...

Страница 14: ... 1994 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 14 901k124 Catalog No BDP 3390 107 ...

Отзывы: