background image

IX.

MAKE ELECTRICAL CONNECTIONS

WARNING:

To avoid personal injury or death, do not

supply power to unit with compressor terminal box cover
removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance (3 phase)
may fluctuate above or below permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

NOTE:

Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.

A.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
control box.

WARNING:

The unit cabinet must have an uninter-

rupted or unbroken ground to minimize personal injury if
an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. Failure to
follow this warning can result in an electric shock, fire, or
death.

B.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 7.

C.

Connect Control Wiring

Route 24v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 8 and 9.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than 100 ft from unit, as measured
along the control voltage wires, use No. 16 AWG color-coded wire
to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.

Use furnace transformer, fan coil transformer, or accessory trans-
former for control power, 24v/40va minimum.

NOTE:

Use of available 24v accessories may exceed the mini-

mum 40va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.

D.

Final Wiring Check

IMPORTANT:

Check factory wiring and wire connections to

ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

X.

COMPRESSOR CRANKCASE HEATER

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to
outdoor unit. A crankcase heater is required if refrigerant tubing is
longer than 50 ft.

XI.

COMPRESSOR CRANKCASE HEATER

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to
outdoor unit. A crankcase heater is required if refrigerant tubing is
longer than 50 ft.

XII.

INSTALL ELECTRICAL ACCESSORIES

Refer to the individual instructions packaged with kits or acces-
sories when installing.

XIII.

START-UP

CAUTION:

To prevent compressor damage or personal

injury, observe the following:
•Do not overcharge system with refrigerant.
•Do not operate unit in a vacuum or at negative pressure.
•Do not disable low-pressure switch.
In scroll compressor applications:
•Dome temperatures may be hot.

Fig. 6—Liquid Service Valve with Sweat Adapter Tube

A97512

PISTON  BODY

PISTON

PISTON 
RETAINER

SWEAT/FLARE  ADAPTER

STRAINER

Fig. 7—Line Power Connections

A94025

DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

—4—

Содержание 661C

Страница 1: ...t and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING Before installing modifying or servicing system main electrical...

Страница 2: ...e for wind baffle construction NOTE Unit must be level to within 2 3 8 in ft per compressor manufacturer specifications III CLEARANCE REQUIREMENTS When installing allow sufficient space for airflow cl...

Страница 3: ...onnected to Factory Approved In door Unit Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or factory acce...

Страница 4: ...measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace trans...

Страница 5: ...wires from crimp nut in indoor fan coil when installing outdoor thermostats IMPORTANT When using outdoor thermostats W2 must be energized when requesting supplemental heat EHR EHR EHR 24 VAC HOT R G...

Страница 6: ...an coil when installing outdoor thermostats IMPORTANT When using outdoor thermostats W2 must be energized when requesting supplemental heat EHR EHR EHR IF AVAILABLE 24 VAC HOT R C W2 Y G R W3 W2 E G R...

Страница 7: ...E If the phasing is incorrect the contactor will not be energized To correct the phasing interchange any two of the three power connections on the field side When thermostat is satisfied its contacts...

Страница 8: ...it This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units If pressure and temperature do not match on chart...

Отзывы: