SM619PHA-03 Specifications subject to change without notice.
15
HEATING Mode
Compressor control
1. Reach the configured temperature:
• If the following conditions are satisfied, the compressor ceases
operation.
• While the calculated frequency (fb) is less than the minimum
limit frequency (FminC).
• When the protective time is more than or equal to ten minutes.
• When T1 is higher than or equal to Tsc+HDIFTEMP2.
NOTE: HDIFTEMP2 is the EEPROM setting parameter.
It is 4
°
F (2
°
C).
• If one of the following conditions is satisfied, regardless of
time.
• Compressor running frequency is more than test frequency.
• When the compressor running frequency is equal to the test
frequency, T4 is more than 59°F (15°C) or no T4 or T4 fault.
• Change the setting temperature.
•
TURBO
or
SLEEP
function on or off.
2. When the current is higher than the predefined safe value, the surge
protection is activated, causing the compressor to
cease
operations.
Indoor Fan Control
1. In the
HEATING
mode, the indoor fan operates continuously. The
fan speed can be set to 1%-100%, or muted.
2.
AUTO
fan
• Rise curve
• When T1-Tsc is higher than -3°F (-1.5°C), fan speed reduces
to 80%;
• When T1-Tsc is higher than 0°F (0°C), fan speed reduces to
60%;
• When T1-Tsc is higher than 1°F (0.5°C), fan speed reduces to
40%;
• When T1-Tsc is higher than 2°F (1°C), fan speed reduces to
20%.
•Descent curve
•When T1-Tsc is lower than or equal to 1°F (0.5°C), fan speed
increases to 20%;
• When T1-Tsc is lower than or equal to 0°F (0°C), fan speed
increases to 60%;
• When T1-Tsc is lower than or equal to -3°F (-1.5°C), fan
speed increases to 80%;
• When T1-Tsc is lower than or equal to -1.5°F (-3°C), fan
speed increases to 100%.
Outdoor Fan Control
•The outdoor unit runs at a different fan speed according to T4
and compressor running frequency.
• For different outdoor units, the fan speeds differ.
DEFROSTING Mode
• The unit enters defrosting mode according to changes in the
temperature value of T3, T4 as well as the compressor running
time.
• In the
DEFROSTING
mode, the compressor continues to run, the
indoor and outdoor motor will cease operation, the defrost light of
the indoor unit will turn on, and the symbol appears.
• If any one of the following conditions is satisfied, defrosting ends
and the machine switches to the normal
HEATING
mode:
• T3 rises above TCDE1C.
• T3 maintained above TCDE2C for 80 seconds.
• Unit runs for 15 minutes consecutively in the
DEFROSTING
mode.
Evaporator Temperature Protection
•
Off
: Compressor stops.
•
Decrease
: Decrease the running frequency to the lower level per
20 seconds.
•
Hold
: Keep the current frequency.
•
Resume
: No limitation for frequency.
AUTO Mode
• This mode can be selected with the remote controller and the
setting temperature can be changed between 61°F~86°F
(16°C~30°C).
• In the
AUTO
mode, the machine selects the
COOLING
,
HEATING
,
AUTO-DRYING
or
FAN-ONLY
mode on the basis
of T1,Ts, T4 and relative humidity.
• If the setting temperature is modified, the machine selects a new
running function.
DRY Mode
In the
DRY
mode, the air conditioner operates the same as auto fan in
the
COOLING
mode.
1. Mute function is active.
• All protections are activated and operate the same as they do
that in
COOLING
mode.
2. Low Room Temperature Protection
• If the room temperature is lower than 50°F (10°C), the
compressor ceases operations and does not resume until the
room temperature exceeds 54°F (12°C).
“
”