background image

—6—

D. Installing the Indoor Unit Body to the Wall Hanging
Bracket

1. Pass the pipes through the wall sleeve and then hook

the indoor unit body on top of the wall hanging

bracket.

2. For left-hand piping, hang the unit on top of the wall

hanging bracket and incline the unit using a tool such

as a screwdriver set between the middle area of the

body and bottom right of the wall hanging bracket.

Connecting the pipe can be done more easily if the

unit is inclined.

3. Fix the bottom part of the unit to the wall hanging

bracket by pushing it carefully until the two bracket

hooks fit into the marked places at the base of the

unit until it snaps into place. Refer to Fig. 11.

NOTE:

• Do not crush or kink the indoor piping. Avoid sharp bends

with a bend radius of less than 4 inches.

• Do not over bend the same part of the pipe frequently.

• Do not remove the flare nut from the indoor unit pipe

until the piping is connected.

E. Outdoor Units

Outdoor units may be connected to indoor units using field-

supplied tubing of refrigerant grade and condition. See

Table 3 for correct line sizes. Do not use less than 10 ft of

interconnecting tubing.

If either refrigerant tubing or indoor coil is exposed to the

atmosphere, the system must be evacuated following good

refrigeration practices.
Run refrigerant tubes as directly as possible, avoiding

unnecessary turns and bends. Suspend refrigerant tubes so

they do not damage insulation on vapor tube and do not

transmit vibration to structure. Also, when passing refriger-

ant tubes through a wall, seal the opening so that vibration

is not transmitted to structure. Leave some slack in refriger-

ant tubes between structure and outdoor unit to absorb

vibration.

CAUTION: 

 

DO  NOT  BURY  MORE  THAN  36  IN.

OF REFRIGERANT PIPE IN THE GROUND. If any

section of pipe is buried, there must be a 6-in. vertical

rise to the valve connections on the outdoor unit. If

more than the recommended length is buried, refriger-

ant may migrate to cooler, buried section during

extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start-up.

Indoor side

Outdoor side

1/4 to 1/2 in. lower

Drill at Slope

Drain Hose

Drain Cap

Fig. 7 — Placement of Connection Piping

Fig. 8 — Location of Drain Hose and Cap

Fig. 9 — Location of Piping

2

3

2

3

Fig. 10 — Location of Piping, Hose and Wiring

Содержание 619ENF

Страница 1: ...EC for special installation requirements GENERAL These instructions cover the installation start up and service of cooling only and heat pump duct free systems INSTALLATION I STEP 1 COMPLETE PRE INSTALLATION CHECKS A Unpack Units See Fig 1 Move the unit to final location Remove unit from carton being careful not to damage service valves and grilles See Table 1A for installation materials included ...

Страница 2: ...eless Remote Control Mounting Bracket 1 For wireless remote control installation NAME SPECIFICATIONS Connection Pipe nominal capacity Liquid line 3 8 in 619ENF ENQ018 036 Mixed Phase line 5 8 in 619ENF01824 and 619ENQ018 024 3 4 in 619ENF ENQ030 036 Wall Sleeve Wall Cap Finishing Tape PVC Film Fastening Tape Pipe Insulation Drain Hose 5 8 in 619ENF01824 and 619ENQ018 024 3 4 in 619ENF ENQ030 036 S...

Страница 3: ... 619ENF ENQ 16 16 16 20 18 18 18 18 Circuits 5 5 9 9 FILTERS Quantity Size in 2 12 5 x 16 1 2 12 5 x 16 1 3 17 3 x 16 1 3 17 3 x 16 1 AIR SWEEP Horizontal Manual Manual Automatic Automatic Vertical Automatic Automatic Automatic Automatic OPERATING LIMITS Heating Min Max 81 F db Cooling Min Max 59 F wb 70 F db 74 F wb 90 F db CONTROLS Integrated Microprocessor Remote Controller Options Wireless CRC...

Страница 4: ...in min min 4 in 4 in 80 in 8 in Fig 2 Unit Dimensions 619ENF01824 619ENQ018 024 DIMENSIONS in 619ENF ENQ 030 036 DIMENSIONS in A 42 5 57 5 B 11 6 13 4 C 7 9 9 5 619ENF ENQ 619ENF ENQ UNITS Fig 3 Unit Clearances ...

Страница 5: ...P 3 COMPLETE REFRIGERANT PIPING CONNECTIONS When running the piping for indoor units the piping can be con nected as rear piping or side or bottom piping Refer to Fig 4 A Rear Piping Route the piping behind the indoor unit so that the piping is concealed by the unit For rear piping installation drill a 21 2 in diameter hole in the wall at point A or B in Fig 6 Drill the hole at a slope so that the...

Страница 6: ... line sizes Do not use less than 10 ft of interconnecting tubing If either refrigerant tubing or indoor coil is exposed to the atmosphere the system must be evacuated following good refrigeration practices Run refrigerant tubes as directly as possible avoiding unnecessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to struc...

Страница 7: ...Do not use the unit refrigerant gas to purge the connecting pipes Remove the caps from the valves Create a vacuum with a vacuum pump connected to the service connection of the suc tion shut off valves completely shut until a 50 Pa vacuum has been reached Open the mixed phase valve for 3 seconds then quickly shut it to check for possible leaks Replace caps and check for leaks using a leak detector ...

Страница 8: ...e possibility of personal injury if an electrical fault should occur This ground may consist of electrical wire connected to unit ground lug in control compart ment or conduit approved for electrical ground when installed in accordance with NEC and local electrical codes Failure to follow this warning could result in the installer being liable for the personal injury of others CAUTION Unit failure...

Страница 9: ... 9 Fig 16 619ENF01824 Matched with 538ENF Typical Wiring Schematic ...

Страница 10: ... 10 Fig 17 619ENQ018 024 Matched with 538QNF Typical Wiring Schematic ...

Страница 11: ... 11 Fig 18 619ENF030 036 Matched with 538ENF Typical Wiring Schematic ...

Страница 12: ... 12 Fig 19 619ENQ030 036 Matched with 538QNF Typical Wiring Schematic ...

Страница 13: ...re being installed in the same room working independently two remote controls need to be con figured for proper operation A Unit Configuration Turn the unit off by pressing the Press and hold the and buttons of the remote control for more than 5 seconds The display will be cleared and the time segments will display the first configuration item rAdr remote address and the temperature segments will ...

Страница 14: ...t in operation the green LED on the indoor unit flashes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 3 seconds elapses Table 6 Green LED Indoor Unit Fault WARNING Before performing recommended maintenance be sure unit main power switch is turned off Failure to do so ...

Страница 15: ...on Indoor temperature setting too low or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other noncondensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refrigerant to the atmosphere use refrigerant recovery equipment Obstructions at air intake or dirty indoor unit filters Remove obstruction and or clean filter Frequent I...

Страница 16: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619E0001 SI ...

Отзывы: