Bryant 598A Series D Скачать руководство пользователя страница 3

VI.

MAKE PIPING CONNECTIONS

WARNING:

Relieve pressure and recover all refrigerant

before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

CAUTION:

If ANY refrigerant tubing is buried, provide

6-in. vertical rise at service valve. Refrigerant tubing
lengths up to 36 in. may be buried without further special
consideration. For lengths above 36 in., consult your local
distributor.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. Tubing diameters listed in Table 1 are adequate
for equivalent lengths up to 100 ft. DO NOT INSTALL EQUIVA-
LENT INTERCONNECTING TUBING LENGTHS GREATER
THAN 100 FT. Do not increase or decrease interconnecting tubing
diameters.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

A.

Outdoor Unit Connected to Factory-Approved

Indoor Unit

See Product Data Sheet for factory-approved indoor units.
Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft of
field-supplied or factory-accessory tubing. Check refrigerant
charge for maximum efficiency.

B.

Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.

C.

Sweat Connection

CAUTION:

To avoid valve damage while brazing, ser-

vice valves must be wrapped in a heat-sinking material
such as a wet cloth.

Service valves are closed from factory and ready for brazing. After
wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non-silver bearing
brazing material. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.

VII.

MAKE ELECTRICAL CONNECTIONS

WARNING:

To avoid personal injury or death, do not

supply power to unit with compressor terminal box cover
removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

NOTE:

Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.

A.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
control box. Size wires per NEC but not smaller than minimum
wire size shown in Product Data Sheet.

WARNING:

The unit cabinet must have an uninter-

rupted or unbroken ground to minimize personal injury if
an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. Failure to
follow this warning can result in an electric shock, fire, or
death.

B.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for
safety. Connect power wiring to leads provided as shown in Fig. 6.

C.

Connect Control Wiring

Route 24-v control wires through control wiring grommet and
connect to leads provided in control box. (See Table 2 and Fig. 7.)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than 100 ft from unit, as measured
along the control voltage wires, use No. 16 AWG color-coded wire
to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
The outdoor unit requires a minimum of 27-va, 24-vac control
power.

Fig. 5—Positioning of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

TABLE 1—REFRIGERANT CONNECTIONS AND

RECOMMENDED LIQUID AND VAPOR TUBE

DIAMETERS (IN.)

UNIT

SIZE

LIQUID

VAPOR

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

036, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

NOTES:
1. Tube diameters are for lengths up to 100 equivalent ft.
2. Do not increase or decrease tubing sizes.

—3—

Содержание 598A Series D

Страница 1: ...om improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refrigerant tu...

Страница 2: ...ient in cooling mode is 125 F V REMOVE INDOOR CHECK FLO RATER PISTON AND REPLACE WITH TXV CAUTION For proper unit operation and reliability the outdoor unit must be installed with the factory supplied balance port hard shutoff TXV Do not install with evaporator coils having capillary tube metering devices After removing existing Check Flo Rater from indoor coil install factory supplied thermostati...

Страница 3: ...oved Be sure field wiring complies with local and national fire safety and electrical codes and voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating...

Страница 4: ... a Bryant Thermidistat which controls temperature and humidity level without the need for an additional humidistat and relay LCC OPERATION FOR TYPICAL PSC FURNACES The standard blower operation of systems with typical PSC furnaces is covered in Fig 7J K M N P or R The blower runs in high or low speed in conjunction with compressor high or low speed operation When the LCC is wired according to Fig ...

Страница 5: ...AC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See notes 6 and 8 W2 Y E R W3 Y1 L H R1 D A97458 R C C Y1 TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See note 8 Y G W2 R Y2 E W3 L H R1 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 Y1 OTHER BRAND TWO SPEED THERMOSTATS COOL STAGE 1 B A97453 24 V...

Страница 6: ...PROGRAMMABLE THERMOSTAT MODEL 2S FK4C FAN COIL J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING TWO SPEED AIR CONDITIONER See notes 6 8 and 19 DH Y1 Y1 W W1 O W2 Y1 W2 W1 Y Y2 Y2 Y Y2 O W2 H A97459 R Y2 R Y2 C C C R L Y1 OTHER BRAND TWO SPEED THERMOSTATS FK4C FAN COIL TWO SPEED AIR CONDITIONER J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING G G Y Y2 DH W W1 Y1 W2 Y1 O W2 24 VAC HOT 24 VAC COM FAN COOL STAG...

Страница 7: ... W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER See note 6 W R Y1 R G L Y H R1 M A97455 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS SINGLE STAGE FURNACE TWO SPEED AIR CONDITIONER G W R Y Y2 L Y1 H R1 COOL STAGE 1 K A97450 24 VAC HOT 2...

Страница 8: ... 1 FAN HEAT STAGE 1 COOL STAGE 2 HEAT STAGE 2 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 A97457 24 VAC HOT 24 VAC COM HEAT STAGE 1 COOL STAGE 2 FAN R C G W Y2 R C Y1 C OTHER BRAND TWO SPEED THERMOSTATS TWO STAGE FURNACE WITH PSC BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 7 and 17 G R Y2 L W W1 Y Y2 W2 Y...

Страница 9: ...W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C BRYANT PROGRAMMABLE THERMOSTAT MODEL 2S TWO STAGE VARIABLE SPEED FURNACE WITH ICM BLOWER MOTOR TWO SPEED AIR CONDITIONER See notes 6 7 16 and 17 R Y1 R G L W W1 Y Y2 W2 Y1 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN R C G W W1 Y Y2 R C HEAT STAGE 2 COOL STAGE 1 N A OUTDOOR SENSOR CONNECTION Y1 B S1 S2 C BRYANT...

Страница 10: ... FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 11 12 13 15 16 and 17 O W2 W W1 Y1 W2 G R BRYANT THERMIDISTAT CONTROL VARIABLE SPEED CONDENSING FURNACE TWO SPEED AIR CONDITIONER W W1 G Y Y2 C Y2 R Y1 C DHUM HUM B S1 S2 W2 R C HEAT STAGE 1 COOL STAGE 1 COOL STAGE 2 HEAT STAGE 2 FAN 24 VAC HOT 24 VAC COMM DEHUMIDIFY HUMIDI...

Страница 11: ...DIFY FUNCTION ON FK4C REMOVE J1 JUMPER AT FAN COIL CONTROL BOARD 11 THERMIDISTAT DIP SWITCH 1 SHOULD BE SET IN THE OFF POSITION FOR AIR CONDITIONER INSTALLA TIONS THIS IS THE FACTORY DEFAULT 12 THERMIDISTAT DIP SWITCH 2 SHOULD BE SET IN THE ON POSITION FOR 2 SPEED COMPRESSOR OPERATION 13 REFER TO INDOOR EQUIPMENT INSTALLATION INSTRUCTIONS FOR PROPER SETUP 14 TO ACTIVATE DEHUMIDIFY FEATURE ON CURRE...

Страница 12: ...ASY SELECT control board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections refer to Table 5 This fan coil has an adjustable blower off delay factory set at 90 sec for high and low speed blower operation TABLE 3 AIRFLOW SELECTION FOR 333 B J AV FURNACES CFM 598A UNIT SIZE FURNACE MODEL HEATING SIZE FUR...

Страница 13: ...TO or ON as desired Wait for appropriate time delay s and 2 minute minimum low speed run time Operate unit for 15 minutes Check refrigerant charge XI CHECK CHARGE WARNING Service valve gage ports are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses and gl...

Страница 14: ...delay and if a pressure switch or compressor PTC overload should trip I Second Stage Latching Mechanical thermostats operate with a staging differential of 2 F droop Bryant electronic thermostats are droopless meaning that they maintain room temperature at set point without latching second stage If system is installed with a mechanical thermostat or second stage latching is desired the following i...

Страница 15: ...ystem Functions section for individual function information HEADER PIN HOUSING The header pin housing is the plastic assembly which holds the stripped lead ends for field connections The 2 speed control receives 24 vac low voltage control system inputs through the housing pins The housing also contains jumpers which the control uses for system configuration such as heat pump versus air conditioner...

Страница 16: ...MAINTENANCE For continuing high performance and to minimize possible equip ment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applications TABLE 9 TWO SPEED COMPRESSOR WINDING RESISTANCE AT 70 F 20 WINDING 3 TON 4 TON 5 TON T1 T2 0 80 0 70 0 60 T1 T3 3 20 2 20 1 80 T1 T7 1 30 1 00 1 00 T1 T8 3 10 2...

Отзывы: