GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI
Standard 210.

Unit will be certified for capacity, efficiency, and listed in the lat-
est ARI directory.

Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 150 psig and
pressure tested at 300 psig.

Unit constructed in ISO 9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory-assembled, single-piece, air-cooled air conditioner unit.
Contained within the unit enclosure will be all factory wiring, pip-
ing, controls, compressor, refrigerant charge (R22), and special
features required prior to field start-up.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air
upward.

Air-Cooled, Split-System

Air Conditioner

597C

1-1/2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with steel wire safety
guards.

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum fins mechanically bonded
to copper tubes which are then cleaned, dehydrated, and
sealed.

Refrigeration Components

Refrigeration circuit components will include liquid line shutoff
valve with sweat connections, suction line shutoff valves with
sweat connections, system charge of R22 refrigerant, and com-
pressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a
suction temperature of _____ °F. The power consumption at full
load will not exceed _____ kw.

Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of _____ Btuh or greater at
conditions of _____ CFM entering air temperature at the evapo-
rator at _____ °F wet bulb and _____ °F dry bulb, and air enter-
ing the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or greater at
DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single
phase, 60 hertz. The unit will be capable of satisfactory opera-
tion within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection.

Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.

Содержание 597C (60 Hz)

Страница 1: ...will last for many years All screws on cabinet exterior are coated for a long lasting rust resistant quality appearance TOTALLY ENCLOSED FAN MOTOR Provides greater reliabil ity under adverse weather conditions and dependable perfor mance for many years The permanent split capacitor type motor was designed for optimum efficiency Then under extreme conditions the motor was tested and qualified to he...

Страница 2: ...3 8 15 2 15 16 26 x 32 060 F 39 13 16 30 33 5 1 16 9 11 16 27 15 16 34 3 8 7 8 16 1 2 20 3 8 15 2 15 16 26 x 32 ACCESS PANEL 1 1 4 1 Allow 30 in clearance to service end of unit 48 in above unit 6 in on one side 12 in on remaining side and 24 in between units for proper airflow Minimum outdoor operating ambient in cooling mode is 55 F unless low ambient control is used max 125 F 2 Series designati...

Страница 3: ...cations Maximum Diameter 018 024 3 8 3 8 5 8 3 4 030 036 3 4 7 8 042 048 7 8 1 1 8 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 F 55 024 F 61 030 F 67 036 F 76 042 F 82 048 G 90 048 F 93 060 F 101 UNIT SIZE SERIES REQUIRED SUBCOOLING F 018 F 10 024 F 12 030 F 15 036 F 12 042 F 12 048 G F 11 060 F 12 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED ...

Страница 4: ...1 Condenser Airflow CFM 1500 2000 2000 3000 3000 3000 3300 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0101SML KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA KSAHS1601AAA Start Assist PTC Type KAACS0201PTC TXV RPB KAATX0201RPB KAATX0301RPB KAATX0401RPB KAATX0501RPB KAATX0601RP...

Страница 5: ...er than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 Time delay fuse or circuit breaker Charge quantity is for 15 ft of interconnecting tubing For tubing lengths longer than 15 ft add 0 6 oz of refrigerant per ft of tube length in excess of 15 ft Do not use hard s...

Страница 6: ...as where power interruptions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evaporator Freeze Thermostat An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze up conditions SUGGESTED USE All units where Winter Start Control ...

Страница 7: ...e temperature at a remote location outdoors to be displayed at the thermostat SUGGESTED USE All corporate programmable thermostats 16 Support Feet Four stick on plastic feet which raise the unit 4 in above the mounting pad This allows sand dirt and other debris to be flushed from the unit base minimizing corrosion SUGGESTED USE Coastal installations Windy areas or where debris is normally circulat...

Страница 8: ...ONE 12 20 12 20 12 20 11 10 CF5AA024 23 000 NONE 12 00 12 00 12 00 10 95 CK3BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK3BA030 23 200 NONE 12 20 12 20 12 20 11 05 CK5A CK5BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK5A CK5BA030 23 200 NONE 12 20 12 20 12 20 11 05 CK5A CK5BW024 23 000 NONE 12 00 12 00 12 00 10 85 CK5A CK5BW030 23 200 NONE 12 20 12 20 12 20 11 05 F A B 4ANF024 23 200 TDR 12 00 12 00 ...

Страница 9: ... CE3AA036 29 800 TDR 13 50 13 50 11 80 CK3BA030 29 000 TDR 13 00 13 00 11 30 CK3BA036 29 600 TDR 13 50 13 50 11 85 CK5A CK5BA030 29 000 TDR 13 00 13 00 11 30 CK5A CK5BA036 29 600 TDR 13 50 13 50 11 85 CK5A CK5BN036 27 600 TDR 13 00 13 00 11 70 CK5A CK5BW030 29 000 TDR 13 00 13 00 11 30 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AA036 30 000 TDR 13 50 13 50 12 05 CE3AA036 29 800 TDR 13 5...

Страница 10: ... FURNACE CC5A CD5AA042 35 400 TDR 13 00 13 00 11 65 CE3AA042 35 400 TDR 13 00 13 00 11 70 CK3BA036 35 000 TDR 13 00 13 00 11 45 CK3BA042 35 000 TDR 13 00 13 00 11 35 CK5A CK5BA036 35 000 TDR 13 00 13 00 11 45 CK5A CK5BN036 33 000 TDR 12 50 12 50 11 65 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AA042 35 400 TDR 13 00 13 00 11 65 CE3AA042 35 400 TDR 13 00 13 00 11 70 CK3BA036 35 000 TDR 1...

Страница 11: ...R 12 00 12 00 10 50 F A B 4AN F B 048 41 500 TDR 12 20 12 20 10 70 FC4BN F B 042 41 000 TDR TXV 12 00 10 50 FC4BN F B 048 41 500 TDR TXV 12 20 10 70 FC4BNB054 43 000 TDR TXV 13 00 11 40 FG3AAA048 41 000 NONE 12 20 12 20 12 20 10 65 FK4BNB005 42 000 TDR TXV 13 50 11 75 FK4BNB006 43 000 TDR TXV 14 00 12 10 FK4BNF003 41 500 TDR TXV 13 00 11 30 FK4CNB006 43 000 TDR TXV 14 00 12 10 FK4CNF003 41 500 TDR...

Страница 12: ... CK5BW048 47 500 NONE 12 00 12 00 12 00 10 60 CK5A CK5BX060 48 500 NONE 12 40 12 40 12 40 11 00 F A B 4AN F B C 048 47 500 TDR 12 00 12 00 10 55 F A B 4AN F B C 060 48 000 TDR 12 10 12 10 10 60 FC4BN F B 048 47 500 TDR TXV 12 00 10 55 FC4BN F B 060 48 000 TDR TXV 12 10 10 60 FC4BNB054 48 500 TDR TXV 12 50 11 05 FC4BNB070 48 000 TDR TXV 12 20 11 00 FG3AAA048 47 500 NONE 12 00 12 00 12 00 10 55 FG3A...

Страница 13: ...00 10 65 CC5A CD5AW060 48 000 TDR 12 80 12 80 11 25 CD5AA048 47 000 TDR 12 50 12 50 10 90 CK3BA048 47 000 TDR 12 50 12 50 10 95 CK3BA060 47 000 TDR 12 50 12 50 11 20 CK5A CK5BA048 47 000 TDR 12 50 12 50 10 95 CK5A CK5BX060 48 000 TDR 12 80 12 80 11 45 COILS 355MAV060120 VARIABLE SPEED FURNACE CC5A CD5AA060 47 000 TDR 12 50 12 50 11 00 CC5A CD5AW048 47 000 TDR 12 50 12 50 10 90 CC5A CD5AW060 48 000...

Страница 14: ...5 6 1 56 15 0 15 0 1 75 14 5 14 5 1 96 13 8 13 8 2 19 675 72 20 0 10 4 1 46 19 2 10 1 1 63 18 4 9 81 1 82 17 6 9 51 2 03 16 7 9 19 2 26 67 18 3 13 5 1 44 17 6 13 2 1 61 16 9 12 9 1 80 16 1 12 6 2 01 15 2 12 3 2 24 62 16 8 16 4 1 43 16 2 16 0 1 60 15 5 15 5 1 79 14 9 14 9 2 00 14 2 14 2 2 23 57 16 6 16 6 1 43 16 0 16 0 1 59 15 5 15 5 1 78 14 8 14 8 1 99 14 2 14 2 2 22 Multipliers for Determining th...

Страница 15: ...3 20 9 2 17 20 4 20 3 2 38 19 5 19 5 2 6 18 7 18 7 2 91 57 21 8 21 8 1 96 21 1 21 1 2 16 20 3 20 3 2 38 19 5 19 5 2 6 18 7 18 7 2 90 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 1 00 1 00 COILS 333 B J AV036060 VARIABLE SPEED FURNACE 030 1 01 1 00 CC5A CD5AA 030 1 03 0 90 ...

Страница 16: ...ity Power CC5A CD5AA 030 1 00 1 00 CK3BA 030 1 00 0 93 036 1 02 1 00 036 1 02 0 91 CC5A CD5AW 030 1 00 1 00 CK5A CK5BW 030 1 00 0 93 CD5AW 036 1 02 1 00 036 1 02 0 91 CE3AA 030 1 00 1 00 COILS 355MAV042040 VARIABLE SPEED FURNACE 036 1 02 1 00 CC5A CD5AA 030 1 02 0 94 CF5AA 036 1 02 1 00 036 1 03 0 93 CK3BA 030 1 00 1 00 CK3BA 030 1 00 0 96 036 1 02 1 00 036 1 02 0 95 CK5A CK5BA 030 1 00 1 00 CK5A ...

Страница 17: ...2 1 01 0 93 042 100 1 00 CK3BA 036 1 00 0 92 CC5A CD5AW 042 1 00 1 00 042 1 00 0 93 CD5AW 036 1 00 1 00 CK5A CK5BA 042 1 00 0 93 CE3AA 036 0 99 1 00 CK5A CK5BW 036 1 00 0 92 042 1 01 1 00 COILS 333 B J AV060100 VARIABLE SPEED FURNACE CF5AA 036 1 01 1 00 CC5A CD5AA 042 1 01 0 93 CK3BA 036 1 00 1 00 CE3AA 042 1 01 0 93 042 1 00 1 00 CK3BA 036 1 00 0 92 CK5A CK5BA 036 1 00 1 00 042 1 00 0 92 042 1 00...

Страница 18: ... 33 4 24 7 3 60 31 8 24 1 3 9 30 2 23 5 4 39 62 33 4 31 4 2 94 32 0 30 7 3 24 30 6 29 9 3 59 29 1 28 9 3 9 27 8 27 8 4 34 57 32 5 32 5 2 93 31 4 31 4 3 25 30 3 30 3 3 58 29 0 29 0 3 9 27 8 27 8 4 35 1350 72 40 3 21 0 3 03 38 5 20 4 3 33 36 9 19 8 3 69 35 1 19 2 4 0 33 2 18 5 4 47 67 36 9 27 4 3 01 35 3 26 7 3 31 33 8 26 2 3 66 32 2 25 5 4 0 30 3 24 8 4 42 62 33 9 33 1 3 00 32 5 32 2 3 29 31 2 31 2...

Страница 19: ... 1 00 1 00 CK5A CK5BA 042 1 00 0 93 CC5A CD5AC 048 0 99 1 00 CK5A CK5BW 048 1 00 0 93 CC5A CD5AW 042 1 00 1 00 COILS 333 B J AV060120 VARIABLE SPEED FURNACE 048 1 00 1 00 CD5AA 048 1 00 0 92 CD5AA 048 1 00 1 00 CE3AA 048 1 00 0 92 CE3AA 042 1 00 1 00 CK3BA 042 1 00 0 93 048 1 01 1 00 048 1 00 0 93 CF5AA 048 1 01 1 00 CK5A CK5BA 042 1 00 0 93 CK3BA 042 1 00 1 00 CK5A CK5BW 048 1 00 0 93 048 1 00 1 ...

Страница 20: ... CK5BA 060 0 98 0 94 CC5A CD5AC 048 0 98 0 99 CK5A CK5BW 048 0 98 0 94 CC5A CD5AW 048 0 99 1 00 CK5A CK5BX 060 1 01 0 93 060 1 01 1 00 COILS 333 B J AV060120 VARIABLE SPEED FURNACE CD5AA 048 0 99 1 00 CC5A CD5AA 060 0 98 0 94 CE3AA 048 0 99 1 00 CC5A CD5AW 048 0 98 0 94 060 1 00 1 00 060 1 01 0 94 CF5AA 048 0 99 0 99 CK3BA 048 0 98 0 94 CK3BA 048 0 99 1 00 CK5A CK5BA 060 0 98 0 94 060 1 00 1 00 CK...

Страница 21: ...1 62 53 1 47 1 4 83 51 0 46 1 5 34 48 9 45 1 5 90 46 8 44 0 6 53 44 6 42 8 7 21 57 50 4 50 4 4 80 48 8 48 8 5 31 47 2 47 2 5 88 45 5 45 5 6 50 43 7 43 7 7 19 2000 72 64 8 32 5 5 09 62 3 31 6 5 62 59 7 30 6 6 20 57 0 29 7 6 84 54 2 28 6 7 50 67 59 3 41 5 5 01 57 0 40 6 5 53 54 6 39 6 6 11 52 1 38 6 6 73 49 6 37 6 7 43 62 54 2 50 2 4 94 52 0 49 1 5 46 49 8 47 9 6 02 47 6 46 6 6 65 45 4 45 1 7 34 57 ...

Страница 22: ...5 0 KW 1 10 1 25 1 42 1 61 1 82 2 04 2 29 55 TCG 33 2 32 4 31 5 30 4 29 1 27 6 26 1 SDT 75 4 85 3 95 3 105 0 115 0 125 0 135 0 KW 1 07 1 22 1 39 1 59 1 80 2 03 2 27 597C030 F 30 TCG 27 5 26 3 25 0 23 7 22 4 20 9 19 4 SDT 75 0 85 0 95 0 105 0 115 0 125 0 135 0 KW 1 41 1 65 1 91 2 20 2 52 2 86 3 22 35 TCG 30 3 29 0 27 7 26 3 24 8 23 3 21 8 SDT 75 1 85 1 95 1 105 0 115 0 125 0 135 0 KW 1 36 1 60 1 86...

Страница 23: ...03 3 48 3 96 4 48 5 03 35 TCG 50 9 48 6 46 3 43 9 41 5 39 0 36 4 SDT 77 0 86 5 96 1 106 0 115 0 125 0 135 0 KW 2 30 2 65 3 04 3 47 3 95 4 46 5 02 40 TCG 55 6 53 2 50 8 48 2 45 7 43 0 40 3 SDT 78 8 88 3 97 8 107 0 117 0 126 0 136 0 KW 2 33 2 68 3 07 3 51 3 98 4 50 5 05 45 TCG 60 6 58 0 55 4 52 7 50 0 47 2 44 3 SDT 80 8 90 2 99 7 109 0 119 0 128 0 138 0 KW 2 35 2 71 3 11 3 55 4 03 4 55 5 12 50 TCG 6...

Страница 24: ...g refrigerant tube lengths between 50 and 175 ft consult the Residential Split System Long Line Application Guideline available from equipment distributor 7 If any refrigerant tubing is buried provide a minimum 6 in vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in may be buried without further consideration For buried lines longer than 3 ft consult your loc...

Страница 25: ... 25 A98599 MATCHED SYSTEM ...

Страница 26: ... 26 ...

Страница 27: ... 27 ...

Страница 28: ...t Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 597C 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resista...

Отзывы: