ACCESSORY USAGE GUIDELINE

 

*

 

For tubing line sets between 50 and 175 ft and/or 20 ft vertical differential, refer to the Residential Split-System Long-Line Application Guideline.

† Only when low-pressure switch is used.
‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster Control only.

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

 

1.

 

Ball Bearing Fan Motor

 

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. 

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.

 

Coastal Filter

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. 

SUGGESTED USE: In geographic areas where salt damage could occur.

3.

 

Compressor Start Assist — Capacitor/Relay Type

 

Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.

4.

 

Compressor Start Assist — PTC Type

 

Solid state electrical device which gives a “soft” boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.

5.

 

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication 
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. 

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.
All commercial installations.

6.

 

Cycle Protector

 

Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has 
been interrupted for any reason, including normal room thermostat cycling. 

SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to “play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.

7.

 

Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. 

SUGGESTED USE: All units where Winter Start Control has been added.

8.

 

Filter Drier

 

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.

SUGGESTED USE: All split system air conditioners.

9.

 

High-Pressure Switch 

 

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 
psig and resets at  298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow.  To prevent rapid compressor recycling, 
Cycle Protector can be used with this switch.

SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.

Installations where condenser inlet air temperature exceeds 125°F (51.7°C).

10.

 

Liquid-Line Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant 
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

 

NOTE: 

 

Compressor Start Assist — Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

In certain long line-applications. Refer to Residential Split System Long-Line Application Guideline.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS

 

*

 

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

 

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Control,

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

Содержание 597

Страница 1: ...ked on providing each unit with a durable finish that will last for many years All screws on cabinet exterior are coated for a long lasting rust resistant quality appearance TOTALLY ENCLOSED FAN MOTOR Provides greater reliabil ity under adverse weather conditions and dependable perfor mance for many years The permanent split capacitor type motor was designed for optimum efficiency Then under extre...

Страница 2: ... 20 3 8 15 2 15 16 26 x 32 060 F G 39 13 16 30 33 5 1 16 9 11 16 27 15 16 34 3 8 7 8 16 1 2 20 3 8 15 2 15 16 26 x 32 ACCESS PANEL 1 1 4 1 Allow 30 in clearance to service end of unit 48 in above unit 6 in on one side 12 in on remaining side and 24 in between units for proper airflow Minimum outdoor operating ambient in cooling mode is 55 F unless low ambient control is used max 125 F 2 Series des...

Страница 3: ...6 3 4 7 8 042 048 7 8 1 1 8 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 F G 55 024 F G 61 030 F G 67 036 F G 76 042 F G 82 048 F H 93 060 F G 101 UNIT SIZE SERIES REQUIRED SUBCOOLING F 018 F G 10 024 F G 12 030 F G 15 036 F G 12 042 F G 12 048 F H 11 060 F G 12 CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI REGISTERED QUALITY SYSTEM As an ENERGY STAR Partn...

Страница 4: ... Hertz Phase 208 230 60 1 Condenser Airflow CFM 1500 2000 2000 3000 3000 3000 3300 OPTIONAL EQUIPMENT Support Feet KSASF0101AAA Coastal Filter KAACF0101SML KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA KSAHS1601AAA Start Assist PTC Type KAACS0201PTC TXV RPB KAATX0201RPB KAATX0301RPB KAATX0401RPB ...

Страница 5: ...er than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 Time delay fuse or circuit breaker Charge quantity is for 15 ft of interconnecting tubing For tubing lengths longer than 15 ft add 0 6 oz of refrigerant per ft of tube length in excess of 15 ft Do not use hard s...

Страница 6: ...STED USE Installations in areas where power interruptions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evaporator Freeze Thermostat An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze up conditions SUGGESTED USE All unit...

Страница 7: ...ther debris to be flushed from the unit base minimizing corrosion SUGGESTED USE Coastal installations Windy areas or where debris is normally circulating Rooftop installations For improved sound rating 16 Thermostatic Expansion Valve TXV A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evap...

Страница 8: ...000 NONE 12 00 12 00 12 00 10 85 CC5A CD5AW030 23 200 NONE 12 20 12 20 12 20 10 95 CE3AA024 23 000 NONE 12 00 12 00 12 00 10 95 CE3AA030 23 200 NONE 12 20 12 20 12 20 11 10 CF5AA024 23 000 NONE 12 00 12 00 12 00 10 95 CK3BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK3BA030 23 200 NONE 12 20 12 20 12 20 11 05 CK5A CK5BA024 23 000 NONE 12 00 12 00 12 00 10 85 CK5A CK5BA030 23 200 NONE 12 20 12 20 12 2...

Страница 9: ... 55 FK4 C D NF003 30 000 TDR TXV 13 80 12 10 FK4 C D NF004 30 200 TDR TXV 14 00 12 00 COILS 315 A J AV036070 VARIABLE SPEED FURNACE CC5A CD5AA030 28 600 TDR 12 5 12 5 11 5 CC5A CD5AA036 29 000 TDR 13 13 11 9 CC5A CD5AW030 28 600 TDR 12 5 12 5 11 5 CE3AA030 28 600 TDR 12 5 12 5 11 7 CE3AA036 29 000 TDR 12 5 12 5 11 75 CK3BA030 28 600 TDR 12 5 12 5 11 6 CK3BA036 29 000 TDR 13 13 11 95 CK5A CK5BA030 ...

Страница 10: ...XV 12 00 10 65 FC4 B C N F B 042 35 400 TDR TXV 12 00 10 70 FG3AAA036 34 600 NONE 11 80 11 80 11 80 10 50 FK4 C D NB005 36 000 TDR TXV 14 00 12 10 FK4 C D NB006 36 000 TDR TXV 14 00 12 35 FK4 C D NF001 35 000 TDR TXV 12 20 10 95 FK4 C D NF002 35 000 TDR TXV 12 50 11 00 FK4 C D NF003 35 400 TDR TXV 13 00 11 60 FK4 C D NF004 35 400 TDR TXV 13 00 11 40 FK4 C D NF005 36 000 TDR TXV 14 00 12 10 COILS 3...

Страница 11: ...0 TDR 12 50 12 50 11 45 COILS 355MAV060080 VARIABLE SPEED FURNACE CK3BA036 35 000 TDR 12 50 12 50 11 30 CK3BA042 35 000 TDR 13 00 13 00 11 40 CK5A CK5BA042 35 000 TDR 13 00 13 00 11 40 CK5A CK5BW036 35 000 TDR 12 50 12 50 11 30 COILS 355MAV060100 VARIABLE SPEED FURNACE CC5A CD5AA036 35 200 TDR 13 00 13 00 11 60 CC5A CD5AA042 35 200 TDR 13 00 13 00 11 70 CK3BA036 35 000 TDR 13 00 13 00 11 65 CK3BA0...

Страница 12: ... 55 CE3AA042 40 000 TDR 12 5 12 5 11 45 CE3AA048 40 500 TDR 13 13 11 5 CK3BA042 40 000 TDR 12 5 12 5 11 4 CK3BA048 40 500 TDR 13 13 11 6 CK5A CK5BA042 40 000 TDR 12 5 12 5 11 4 CK5A CK5BA048 40 500 TDR 13 13 11 6 CK5A CK5BT042 40 000 TDR 12 5 12 5 11 4 CK5A CK5BT048 40 500 TDR 13 13 11 6 CK5A CK5BW048 40 500 TDR 13 13 11 6 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CC5A CD5AA042 40 000 TDR 12 5...

Страница 13: ...05 FC4 B C NB070 48 000 TDR TXV 12 20 11 00 FG3AAA048 47 500 NONE 12 00 12 00 12 00 10 55 FG3AAA060 48 000 NONE 12 20 12 20 12 20 10 75 FK4 C D NB006 48 500 TDR 13 50 11 95 FK4 C D NF005 47 500 TDR 13 20 11 65 COILS 315 A J AV048090 VARIABLE SPEED FURNACE CC5A CD5AC048 46 000 TDR 12 12 10 8 CD5AA048 46 500 TDR 12 12 10 9 CE3AA048 46 500 TDR 12 12 10 9 CE3AA060 47 000 TDR 12 5 12 5 11 3 CK3BA048 46...

Страница 14: ...50 11 00 CC5A CD5AW048 47 000 TDR 12 50 12 50 10 90 CC5A CD5AW060 48 000 TDR 13 00 13 00 11 30 CK5A CK5BA060 47 000 TDR 12 50 12 50 11 25 CK5A CK5BW048 47 000 TDR 12 50 12 50 11 00 CK5A CK5BX060 48 000 TDR 13 00 13 00 11 50 060 F G CC5A CD5AW060 57 000 NONE 12 00 12 00 12 00 10 30 CC5A CD5AA060 55 000 NONE 12 00 12 00 12 00 10 20 CE3AA060 57 000 NONE 12 00 12 00 12 00 10 40 CK3BA060 55 000 NONE 12...

Страница 15: ...ergy Efficiency Ratio TDR Time Delay Relay TXV Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for electric air conditioners Ratings for other com binations are determined under DOE computer simulati...

Страница 16: ...6 13 8 13 8 2 19 675 72 20 0 10 4 1 46 19 2 10 1 1 63 18 4 9 81 1 82 17 6 9 51 2 03 16 7 9 19 2 26 67 18 3 13 5 1 44 17 6 13 2 1 61 16 9 12 9 1 80 16 1 12 6 2 01 15 2 12 3 2 24 62 16 8 16 4 1 43 16 2 16 0 1 60 15 5 15 5 1 79 14 9 14 9 2 00 14 2 14 2 2 23 57 16 6 16 6 1 43 16 0 16 0 1 59 15 5 15 5 1 78 14 8 14 8 1 99 14 2 14 2 2 22 Multipliers for Determining the Performance With Other Indoor Secti...

Страница 17: ...0 3 2 38 19 5 19 5 2 6 18 7 18 7 2 91 57 21 8 21 8 1 96 21 1 21 1 2 16 20 3 20 3 2 38 19 5 19 5 2 6 18 7 18 7 2 90 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 1 00 1 00 CE3AA 024 1 00 0 91 030 1 01 1 00 030 1 01 0 90 CC5A CD5AW 024 1 00 1 00 CK3BA 024 1 00 0 90 030 1 01 1...

Страница 18: ...6 1 02 1 00 036 1 00 0 90 CC5A CD5AW 030 1 00 1 00 CK3BA 030 0 99 0 91 CD5AW 036 1 02 1 00 036 1 00 0 89 CE3AA 030 1 00 1 00 CK5A CK5BA 030 0 99 0 91 036 1 02 1 00 036 1 00 0 89 CF5AA 036 1 02 1 00 CK5A CK5BW 030 0 99 0 91 CK3BA 030 1 00 1 00 036 1 00 0 89 036 1 02 1 00 COILS 355MAV042040 VARIABLE SPEED FURNACE CK5A CK5BA 030 1 00 1 00 CC5A CD5AA 030 1 02 0 94 036 1 02 1 00 036 1 03 0 93 CK5A CK5B...

Страница 19: ...0 CK5A CK5BE 042 1 00 0 92 CD5AW 036 1 00 1 00 CK5A CK5BT 036 0 99 0 92 CE3AA 036 0 99 1 00 042 1 00 0 93 042 1 01 1 00 CK5A CK5BW 036 0 99 0 92 CF5AA 036 1 01 1 00 COILS 315 A J AV066110 VARIABLE SPEED FURNACE CK3BA 036 1 00 1 00 CC5A CD5AA 036 0 99 0 92 042 1 00 1 00 042 1 00 0 92 CK5A CK5BA 036 1 00 1 00 CC5A CD5AW 036 0 99 0 92 042 1 00 1 00 042 0 99 0 92 CK5A CK5BN 036 0 94 1 00 CE3AA 036 0 9...

Страница 20: ... 40 3 21 0 3 03 38 5 20 4 3 33 36 9 19 8 3 69 35 1 19 2 4 0 33 2 18 5 4 47 67 36 9 27 4 3 01 35 3 26 7 3 31 33 8 26 2 3 66 32 2 25 5 4 0 30 3 24 8 4 42 62 33 9 33 1 3 00 32 5 32 2 3 29 31 2 31 2 3 64 29 9 29 9 4 0 28 5 28 5 4 40 57 33 5 33 5 2 99 32 4 32 4 3 31 31 2 31 2 3 64 29 9 29 9 4 0 28 5 28 5 4 40 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Coo...

Страница 21: ...ity Power Capacity Power CC5A CD5AA 042 1 00 1 00 COILS 315 A J AV066110 VARIABLE SPEED FURNACE CC5A CD5AC 048 0 99 1 00 CC5A CD5AA 042 0 98 0 91 CC5A CD5AW 042 1 00 1 00 CC5A CD5AC 048 0 96 0 90 048 1 00 1 00 CC5A CD5AW 042 0 98 0 92 CD5AA 048 1 00 1 00 048 0 99 0 91 CE3AA 042 1 00 1 00 CD5AA 048 0 99 0 91 048 1 01 1 00 CE3AA 042 0 98 0 91 CF5AA 048 1 01 1 00 048 0 99 0 91 CK3BA 042 1 00 1 00 CK3...

Страница 22: ...62 45 5 23 7 3 98 43 6 23 1 4 37 41 6 22 4 4 8 39 6 21 7 5 28 67 43 3 31 6 3 59 41 5 31 0 3 94 39 8 30 3 4 32 38 0 29 5 4 7 36 2 28 8 5 22 62 39 5 38 2 3 56 38 0 37 2 3 90 36 5 36 2 4 28 35 0 35 0 4 7 33 6 33 6 5 19 57 38 9 38 9 3 55 37 6 37 6 3 89 36 3 36 3 4 28 34 9 34 9 4 7 33 6 33 6 5 19 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor S...

Страница 23: ...2 CC5A CD5AC 048 0 98 0 99 060 0 98 0 90 CC5A CD5AW 048 0 99 1 00 CK3BA 048 0 97 0 92 060 1 01 1 00 060 0 98 0 91 CD5AA 048 0 99 1 00 CK5A CK5BA 048 0 97 0 92 CE3AA 048 0 99 1 00 060 0 98 0 91 060 1 00 1 00 CK5A CK5BT 048 0 97 0 92 CF5AA 048 0 99 0 99 060 0 98 0 91 CK3BA 048 0 99 1 00 CK5A CK5BW 048 0 97 0 92 060 1 00 1 00 CK5A CK5BX 060 1 00 0 91 CK5A CK5BA 048 0 99 1 00 COILS 315 A J AV066135 VA...

Страница 24: ...2 0 4 55 40 5 40 5 5 06 38 9 38 9 5 63 37 3 37 3 6 23 1800 72 55 5 27 9 4 25 53 2 27 1 4 75 51 0 26 3 5 30 48 5 25 4 5 87 45 9 24 5 6 50 67 50 8 35 8 4 21 48 7 35 0 4 69 46 5 34 1 5 22 44 3 33 2 5 79 42 0 32 3 6 41 62 46 3 43 3 4 16 44 5 42 3 4 64 42 5 41 2 5 17 40 5 39 9 5 73 38 4 38 4 6 33 57 44 9 44 9 4 15 43 4 43 4 4 63 41 8 41 8 5 16 40 1 40 1 5 73 38 3 38 3 6 32 Multipliers for Determining t...

Страница 25: ...6 12 48 4 48 4 6 75 46 4 46 4 7 45 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AW 060 1 00 1 00 CK5A CK5BT 060 0 96 0 93 CC5A CD5AA 060 0 96 0 97 CK5A CK5BX 060 0 98 0 93 CE3AA 060 1 00 1 00 COILS 315 A J AV066135 VARIABLE SPEED FURNACE CK3BA 060 0 96 1 00 CC5A CD5AA 060 0 96 0 ...

Страница 26: ...5 0 KW 1 10 1 25 1 42 1 61 1 82 2 04 2 29 55 TCG 33 2 32 4 31 5 30 4 29 1 27 6 26 1 SDT 75 4 85 3 95 3 105 0 115 0 125 0 135 0 KW 1 07 1 22 1 39 1 59 1 80 2 03 2 27 597C030 F G 30 TCG 27 5 26 3 25 0 23 7 22 4 20 9 19 4 SDT 75 0 85 0 95 0 105 0 115 0 125 0 135 0 KW 1 41 1 65 1 91 2 20 2 52 2 86 3 22 35 TCG 30 3 29 0 27 7 26 3 24 8 23 3 21 8 SDT 75 1 85 1 95 1 105 0 115 0 125 0 135 0 KW 1 36 1 60 1 ...

Страница 27: ...03 3 48 3 96 4 48 5 03 35 TCG 50 9 48 6 46 3 43 9 41 5 39 0 36 4 SDT 77 0 86 5 96 1 106 0 115 0 125 0 135 0 KW 2 30 2 65 3 04 3 47 3 95 4 46 5 02 40 TCG 55 6 53 2 50 8 48 2 45 7 43 0 40 3 SDT 78 8 88 3 97 8 107 0 117 0 126 0 136 0 KW 2 33 2 68 3 07 3 51 3 98 4 50 5 05 45 TCG 60 6 58 0 55 4 52 7 50 0 47 2 44 3 SDT 80 8 90 2 99 7 109 0 119 0 128 0 138 0 KW 2 35 2 71 3 11 3 55 4 03 4 55 5 12 50 TCG 6...

Страница 28: ...et Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 597C 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resist...